For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616<br />

<strong>Approvals</strong> for world markets<br />

A1/32<br />

Motor-protective circuit-breakers<br />

Type E Starters<br />

600 V<br />

PKZM0<br />

Type E starters to UL 508 are<br />

assembled from a st<strong>and</strong>ard PKZM <strong>and</strong><br />

a special incoming terminal or<br />

terminal shroud: Maximum motor<br />

rating<br />

Setting ranges<br />

AC<br />

HP = PS<br />

Overload<br />

Releases<br />

Short-circuit<br />

releases<br />

Rated short-circuit breaking<br />

capacity<br />

200 V 230 V 460 V 575 V 240 V 480 V<br />

277 V 2) 347 V 2)<br />

HP HP HP HP A A kA kA kA<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Type<br />

Motor-protective<br />

circuit-breaker<br />

Type<br />

Incomingterminal<br />

PKZM0 motor-protective circuit-breakers “Manual self-protected motor starters”<br />

1) 0.1 – 0.16 2.2 50 50 50 PKZM0-0,16 BK25/3-PKZ0-E<br />

0.16 – 0.25 3.4 50 50 50 PKZM0-0,25 BK25/3-PKZ0-E<br />

0.25 – 0.4 5.6 50 50 50 PKZM0-0,4 BK25/3-PKZ0-E<br />

0.4 – 0.63 8.8 50 50 50 PKZM0-0,63 BK25/3-PKZ0-E<br />

½ ½ 0.63 – 1 14 50 50 50 PKZM0-1 BK25/3-PKZ0-E<br />

¾ 1 1 – 1.6 22 50 50 50 PKZM0-1,6 BK25/3-PKZ0-E<br />

½ ½ 1 1½ 1.6 – 2.5 35 50 50 50 PKZM0-2,5 BK25/3-PKZ0-E<br />

1 1 2 3 2.5 – 4 56 50 50 50 PKZM0-4 BK25/3-PKZ0-E<br />

1½ 1½ 3 5 4 – 6.3 88 50 50 50 PKZM0-6,3 BK25/3-PKZ0-E<br />

3 3 7½ 10 6.3 – 11 140 50 50 50 PKZM0-10 BK25/3-PKZ0-E<br />

3 3 7½ 10 9 … 12 168 42 42 18 PKZM0-12 BK25/3-PKZ0-E<br />

3 5 10 10 10 – 16 224 42 42 18 PKZM0-16 BK25/3-PKZ0-E<br />

5 5 10 – 16 … 20 280 18 18 – PKZM0-20 BK25/3-PKZ0-E<br />

5 7½ 15 – 20 … 25 350 18 18 – PKZM0-25 BK25/3-PKZ0-E<br />

7½ 10 20 – 24 … 32 448 18 18 – PKZM0-32 BK25/3-PKZ0-E<br />

3 5 10 15 10 … 16 224 50 50 25 PKZM4-16 BK50/3-PKZ4-E<br />

5 7½ 15 20 16 … 27 350 50 50 25 PKZM4-25 BK50/3-PKZ4-E<br />

7½ 10 25 30 24 … 34 448 50 50 25 PKZM4-32 BK50/3-PKZ4-E<br />

10 15 30 30 32 … 40 560 50 50 25 PKZM4-40 BK50/3-PKZ4-E<br />

10 15 30 – 40 … 52 700 50 50 – PKZM4-50 BK50/3-PKZ4-E<br />

15 15 40 – 50 … 56 812 50 50 – PKZM4-58 BK50/3-PKZ4-E<br />

15 15 40 – 52 … 58 882 50 50 – PKZM4-63 BK50/3-PKZ4-E<br />

http://catalog.moeller.net<br />

For use with<br />

Price<br />

See Price<br />

List<br />

Std. pack<br />

Incoming terminal<br />

For surface mounting type E starters for North<br />

America<br />

PKZM0<br />

PKZM4<br />

Terminal shroud<br />

For surface mounting type E starters for North America<br />

PKZM4<br />

Part no.<br />

BK25/3-PKZ0-E<br />

262518<br />

BK50/3-PKZ4-E<br />

272165<br />

HB-PKZ4<br />

256581<br />

5 off For three-phase commoning link,<br />

finger <strong>and</strong> back-of-h<strong>and</strong>-proof,<br />

U e = 690 V, I u = 60 A<br />

for conductor cross-sections:<br />

2.5 … 25 mm 2 flexible<br />

2.5 … 16 mm 2 flexible with ferrule<br />

AWG 14 … 6<br />

Can be combined with B3...-PKZ4<br />

three-phase commoning link<br />

Notes<br />

Type E starters do not need an upstream protective device.<br />

For use in Canada, the PKZM0/PKZM4 must be fitted with an<br />

AK-PKZ0.<br />

Service Factor (SF)<br />

Set value I r , on the current scale, depending on the load<br />

factor<br />

SF = 1.15 l I r = 1 x I n mot<br />

SF = 1 l I r = 0.9 x I n mot<br />

1) Calculate motor power in this range according to the rated current.<br />

Stated values to NEC Table 430 … 150<br />

2) Suitable for networks with earthed star-point