05.01.2015 Views

Approvals and certificates - Moeller Electric Parts

Approvals and certificates - Moeller Electric Parts

Approvals and certificates - Moeller Electric Parts

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616<br />

Rotary switches, Switch-Disconnectors<br />

Switch-disconnectors<br />

A1/27<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

P5<br />

Rating data for approved types P5-125 P5-160 P5-250 P5-315<br />

UL-File No. E36332<br />

Contacts<br />

Rated operational voltage U i V 600 600 600 600<br />

Rated impulse withst<strong>and</strong> voltage 1) U imp V AC 8000 8000 8000 8000<br />

Rated uninterrupted current 2) I u A 125 160 250 300<br />

Rated operational current<br />

Ampere-Rating On/Off switches I e A 125 2) 160 2) 250 2) 300 2)<br />

Changeover I e A 125 2) 160 2) – –<br />

switches<br />

Non inductive <strong>and</strong> slightly inductive loads<br />

rated Switching duty<br />

DOL-Rating (similar to AC-3)<br />

3-phase, 3 polig<br />

120 V HP 15 20 30 40<br />

240 V HP 30 40 60 75<br />

480 V HP 60 60 75 100<br />

600 V HP 60 60 75 100<br />

Short-circuit rating<br />

max. back-up fuse, gL characteristic A 125 160 250 315<br />

rated short-time withst<strong>and</strong> current (1-s-current) A 2500 3000 4600 5800<br />

Terminal capacity<br />

Cu cable<br />

Solid or str<strong>and</strong>ed to box<br />

terminal<br />

AWG 3/0 3/0 – –<br />

MCM – – 350 350<br />

Flexible without ferrule AWG 2/0 2/0 – –<br />

MCM – – 300 300<br />

Connection with cable lug or busbar M10 x M10 x M12 x M12 x<br />

Terminal screw mm 20 20 20 20<br />

max. Width mm 20 20 25 25<br />

max. width with terminal cover mm 25 25 34 34<br />

Ambient temperature open on 100 % I u /I th 50 ° C over 24 hours with peaks up to 55 °C<br />

enclosed on 100% I the 35 ° C over 24 hours with peaks up to 40 °C<br />

<strong>Approvals</strong> for world markets<br />

Notes 1) valid for mains with earth star point, overvoltage category III, pollution degree 3<br />

2) valid for connection with cables for 75°C<br />

Rating data for approved types P3-30…MCS P3-60…MCS P3-90…MCS<br />

UL-File No. E14<br />

CSA-File No. 1342868 (LR12528)<br />

Switching capacity 1)<br />

Sym. rms (60 Hz)<br />

480 V kA 10 10 10<br />

Terminal capacity<br />

Cu cable AWG 10 4 2<br />

Torque Nm 3 3 3<br />

Notes 1) with protection by CLASS H fuses of max 100 A.<br />

Caution no overvoltage protection<br />

P3… P3…/N P3…/3N/HI11 P3…/HI11 P3…/2HI11<br />

L1<br />

L2 L3<br />

L1<br />

1<br />

L2 L3<br />

3 5<br />

N<br />

L1<br />

1<br />

L2 L3<br />

3 5<br />

N 13 21<br />

L1<br />

1<br />

L2 L3<br />

3 5<br />

13 21<br />

L1<br />

1<br />

L2 L3<br />

3 5<br />

13 21<br />

31<br />

43<br />

I<br />

0<br />

T1 T2 T3<br />

2 4 6<br />

T1 T2 T3<br />

I<br />

0<br />

N<br />

2 4 6<br />

T1 T2 T3<br />

I<br />

0<br />

N 14<br />

22<br />

2 4 6<br />

T1 T2 T3<br />

I<br />

0<br />

14<br />

22<br />

2 4 6<br />

T1 T2 T3<br />

I<br />

0<br />

14 22<br />

32<br />

44

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!