05.01.2015 Views

maximo - Aircotech

maximo - Aircotech

maximo - Aircotech

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>maximo</strong> new<br />

air cooled liquid chillers with free-cooling system<br />

91<br />

RCGROUP SpA<br />

cooling capacity<br />

free-cooling<br />

compressors<br />

refrigerant<br />

fan type<br />

microprocessor<br />

19,4 ÷ 185,0 kW<br />

18,9 ÷ 179,0 kW<br />

scroll<br />

R410A<br />

axial / plug-fan<br />

MP.COM<br />

C_GNR_0310


92<br />

MAXIMO<br />

air cooled liquid chillers with free-cooling system<br />

VERSIONS:<br />

<strong>maximo</strong><br />

MULTIPLICITY OF VERSIONS<br />

AND COMPONENTS<br />

The wide range of cooling capacity and the available<br />

versions, make possible the use and the combination of<br />

diverse components on the refrigeration and hydraulic<br />

circuits in the MAXIMO Free-Cooling chillers range.<br />

MAXIMO (R410A)<br />

new<br />

Cooling capacity 21,5 ÷ 307,0 kW<br />

Free-cooling capacity 18,4 ÷ 172,0 kW<br />

Free-cooling liquid chiller equipped with scroll<br />

compressors and axial fans.<br />

new<br />

MAXIMO PF (R410A) Plug fan<br />

Cooling capacity 21,0 ÷ 287,0 kW<br />

Free-cooling capacity 17,0 ÷ 158,0 kW<br />

Free-cooling liquid chiller equipped with scroll<br />

compressors and Plug-fans.<br />

The MAXIMO series is a type of liquid chillers equipped<br />

with a built-in additional coil making Free Cooling using<br />

the outdoor air as cooling media.<br />

The free-cooling system installed on these chillers has<br />

been designed and applied by RC GROUP for the first<br />

time in the early 70’s and the today’s series is the result of<br />

more than 40 years experience.<br />

These chillers allow to achieve remarkable energy savings<br />

when installed in cold and temperate climate zones.<br />

MAXIMO PF<br />

Units for installation indoor.<br />

The Plug-fan allow the MAXIMO PF installation also<br />

inside offices with ducted air intake/exhaustion.<br />

The components completeness together with the wide<br />

range of available optional accessories allow very quick<br />

and easy installation operations; the units simply need<br />

electrical and hydraulic connections.<br />

C_GNR_0310<br />

maRCGROUP SpA


MAXIMO<br />

air cooled liquid chillers with free-cooling system<br />

93<br />

MAIN COMPONENTS<br />

• Housing in epoxy painted galvanized steel<br />

sheet.<br />

• Scroll compressors<br />

• Axial fans (MAXIMO)<br />

• Plug fan with EC motor (MAXIMO PF)<br />

• Welded plate evaporator<br />

• Pump-Down stop system<br />

• Proportional free-cooling system<br />

• MP.COM microprocessor control<br />

• Electrical box in separate compartment<br />

• Main switch with door lock safety<br />

MAIN OPTIONAL ACCESSORIES<br />

• Pumping group<br />

• Water tank<br />

• LNO kit for noise reduction<br />

• ELN kit for extreme noise reduction<br />

• Partial heat reclaim<br />

• Water flow safety switch<br />

• Brine kit for glycol solution production with<br />

temperatures down to -12°C.<br />

• Serial port<br />

• Optimizer system<br />

• Glycol-free system<br />

<strong>maximo</strong> PF<br />

MAXIMO PF - Condenser air discharge<br />

Remove a panel for the condenser air discharge<br />

(as indicated in the picture)<br />

ximo<br />

RCGROUP SpA<br />

C_GNR_0310


94<br />

MAXIMO<br />

air cooled liquid chillers with free-cooling system<br />

TECHNICAL DATA AND NOMINAL PERFORMANCES<br />

new<br />

MAXIMO<br />

single circuit / axial fans<br />

MODEL<br />

Size<br />

Cooling capacity (1)<br />

kW<br />

Free-cooling capacity (2) kW<br />

Compressors n.<br />

Power input (1)<br />

kW<br />

Gas circuits n.<br />

Weight<br />

kg<br />

Sound pressure (3) dB(A)<br />

21 24 28 30 34 40 50 52 58<br />

P1 S P1 S P1 S P1 S P1 S P1 S P1 S P2 S P2 S<br />

C1 C1 C1 C1 C2 C2 C2 C2 C3<br />

19,4 21,8 25,8 28,5 34,1 38,4 47,3 49,1 57,1<br />

18,9 19,9 24,1 25,0 32,3 36,5 43,6 44,1 55,2<br />

1 1 1 1 1 1 1 2 2<br />

6,2 7,3 8,4 9,9 10,6 12,5 16,4 17,4 18,8<br />

1 1 1 1 1 1 1 1 1<br />

430 440 440 440 600 600 740 700 930<br />

60,7 61,1 62,5 62,7 63,9 66,9 70,0 68,5 69,8<br />

MODEL<br />

Size<br />

Cooling capacity (1)<br />

kW<br />

Free-cooling capacity (2) kW<br />

Compressors n.<br />

Power input (1)<br />

kW<br />

Gas circuits n.<br />

Weight<br />

kg<br />

Sound pressure (3) dB(A)<br />

62 65 76 98 124 158 180 197 230<br />

P1 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P3 S<br />

C3 C3 C3 C4 C4 C4 C5 C5 C5<br />

60,8 64,2 73,6 95,5 117,0 151,0 174,0 187,0 214,0<br />

57,7 60,2 66,7 84,9 100,0 115,0 135,0 141,0 152,0<br />

1 2 2 2 2 2 2 2 3<br />

20,3 21,4 25,6 32,3 41,8 55,1 60,8 70,3 87,4<br />

1 1 1 1 1 1 1 1 1<br />

970 940 1000 1470 1610 1660 2240 2220 2370<br />

72,6 71,7 71,5 71,9 78,8 81,9 81,6 82,0 82,9<br />

new<br />

MAXIMO<br />

double circuit / axial fans<br />

MODEL<br />

52 58 65 76 98 124 158 180 197 240<br />

P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P4 D<br />

Size<br />

C2 C3 C3 C3 C4 C4 C4 C5 C5 C5<br />

Cooling capacity (1)<br />

kW 49,1 57,5 64,3 73,4 94,4 116,0 153,0 174,0 190,0 224,0<br />

Free-cooling capacity (2) kW 44,1 55,3 60,2 66,6 84,5 99,9 116,0 135,0 142,0 154,0<br />

Compressors n. 2 2 2 2 2 2 2 2 2 4<br />

Power input (1)<br />

kW 17,4 18,8 21,4 25,6 32,1 41,6 55,3 61,1 70,7 90,4<br />

Gas circuits n. 2 2 2 2 2 2 2 2 2 2<br />

Weight<br />

kg 700 920 930 1000 1470 1610 1640 2210 2230 2510<br />

Sound pressure (3) dB(A) 68,5 69,8 71,7 71,5 71,9 78,8 81,9 81,6 82,0 84,0<br />

(1) Referred to chilled water temperature 12/7°C / 20% glycol and air to the condenser at 35°C<br />

(2) Referred to water inlet temperature at 15°C / 20% glycol and outdoor temperature at 3°C<br />

(3) Sound pressure 1m far in free field conditions according to ISO3744 norms<br />

POWER SUPPLY: 400.3.50+N<br />

C_GNR_0310<br />

RCGROUP SpA


MAXIMO<br />

air cooled liquid chillers with free-cooling system<br />

95<br />

TECHNICAL DATA AND NOMINAL PERFORMANCES<br />

new<br />

MAXIMO PF<br />

single circuit / plug-fans<br />

MODEL<br />

Size<br />

Cooling capacity (1)<br />

kW<br />

Free-cooling capacity (2) kW<br />

Compressors n.<br />

Power input (1)<br />

kW<br />

Gas circuits n.<br />

Weight<br />

kg<br />

Sound pressure (3) dB(A)<br />

22 24 28 32 36 42 53 67<br />

P1 S P1 S P1 S P1 S P1 S P1 S P1 S P1 S<br />

C1 C1 C1 C1 C1 C1 C2 C2<br />

21,4 24,3 28,4 32,2 35,9 41,1 52,4 66,4<br />

18,4 20,0 23,4 26,5 28,8 30,7 43,1 53,2<br />

1 1 1 1 1 1 1 1<br />

6,3 7,3 8,5 9,7 11,0 13,4 16,4 20,5<br />

1 1 1 1 1 1 1 1<br />

450 460 460 470 470 480 750 790<br />

70,7 72,3 76,4 9,7 77,9 78,9 77,8 80,0<br />

MODEL<br />

Size<br />

Cooling capacity (1)<br />

kW<br />

Free-cooling capacity (2) kW<br />

Compressors n.<br />

Power input (1)<br />

kW<br />

Gas circuits n.<br />

Weight<br />

kg<br />

Sound pressure (3) dB(A)<br />

55 62 71 85 107 135 170 195 220 250<br />

P2 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P3 S<br />

C2 C2 C2 C3 C3 C4 C4 C4 C5 C5<br />

55,5 62,3 70,3 83,7 106,0 131,0 170,0 187,0 216,0 246,0<br />

46,7 51,6 56,7 68,8 82,7 102,0 126,0 129,0 160,0 170,0<br />

2 2 2 2 2 2 2 2 2 3<br />

17,0 19,4 21,9 25,2 32,4 40,9 52,6 62,4 66,7 83,0<br />

1 1 1 1 1 1 1 1 1 1<br />

740 810 820 1050 1240 1690 1800 1850 2320 2490<br />

76,4 70,3 72,6 76,5 81,3 74,1 77,6 77,6 77,6 77,9<br />

new<br />

MAXIMO PF<br />

double circuit / plug-fans<br />

MODEL<br />

55 62 71 85 107 135 170 195 220 265 290<br />

P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P4 D P4 D<br />

Size<br />

C2 C2 C2 C3 C3 C4 C4 C4 C5 C5 C5<br />

Cooling capacity (1)<br />

kW 55,6 62,7 70,3 83,5 104,0 129,0 168,0 190,0 220,0 261,0 285,0<br />

Free-cooling capacity (2) kW 46,7 51,7 56,7 68,7 82,5 101,0 125,0 130,0 161,0 174,0 179,0<br />

Compressors n. 2 2 2 2 2 2 2 2 2 4 4<br />

Power input (1)<br />

kW 17,0 19,5 21,9 25,2 32,7 40,7 52,3 62,8 67,1 84,2 102,0<br />

Gas circuits n. 2 2 2 2 2 2 2 2 2 2 2<br />

Weight<br />

kg 740 810 820 1050 1240 1690 1780 1820 2330 2670 2720<br />

Sound pressure (3) dB(A) 76,4 70,3 72,6 76,5 81,3 74,1 77,6 77,6 77,6 78,0 78,0<br />

(1) Referred to chilled water temperature 12/7°C / 20% glycol and air to the condenser at 35°C<br />

(2) Referred to water inlet temperature at 15°C / 20% glycol and outdoor temperature at 3°C<br />

(3) Sound pressure 1m far in free field conditions according to ISO3744 norms<br />

POWER SUPPLY: 400.3.50<br />

RCGROUP SpA<br />

C_GNR_0310


96<br />

MAXIMO<br />

air cooled liquid chillers with free-cooling system<br />

dimensionS (mm)<br />

MAXIMO<br />

Size a b c<br />

C1 1.250 1.010 1.950<br />

C2 1.800 1.180 2.000<br />

C3 2.600 1.340 2.000<br />

C<br />

C4 3.700 1.490 2.000<br />

C5 4.950 1.500 2.040<br />

A<br />

B<br />

MAXIMO PF<br />

Size a b c<br />

C1 1.250 1.010 1.950<br />

C2 1.800 1.180 2.000<br />

C3 2.600 1.340 2.000<br />

C<br />

C4 3.700 1.490 2.000<br />

C5 4.950 1.500 2.040<br />

B<br />

A<br />

C_GNR_0310<br />

RCGROUP SpA

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!