maximo - Aircotech
maximo - Aircotech
maximo - Aircotech
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>maximo</strong> new<br />
air cooled liquid chillers with free-cooling system<br />
91<br />
RCGROUP SpA<br />
cooling capacity<br />
free-cooling<br />
compressors<br />
refrigerant<br />
fan type<br />
microprocessor<br />
19,4 ÷ 185,0 kW<br />
18,9 ÷ 179,0 kW<br />
scroll<br />
R410A<br />
axial / plug-fan<br />
MP.COM<br />
C_GNR_0310
92<br />
MAXIMO<br />
air cooled liquid chillers with free-cooling system<br />
VERSIONS:<br />
<strong>maximo</strong><br />
MULTIPLICITY OF VERSIONS<br />
AND COMPONENTS<br />
The wide range of cooling capacity and the available<br />
versions, make possible the use and the combination of<br />
diverse components on the refrigeration and hydraulic<br />
circuits in the MAXIMO Free-Cooling chillers range.<br />
MAXIMO (R410A)<br />
new<br />
Cooling capacity 21,5 ÷ 307,0 kW<br />
Free-cooling capacity 18,4 ÷ 172,0 kW<br />
Free-cooling liquid chiller equipped with scroll<br />
compressors and axial fans.<br />
new<br />
MAXIMO PF (R410A) Plug fan<br />
Cooling capacity 21,0 ÷ 287,0 kW<br />
Free-cooling capacity 17,0 ÷ 158,0 kW<br />
Free-cooling liquid chiller equipped with scroll<br />
compressors and Plug-fans.<br />
The MAXIMO series is a type of liquid chillers equipped<br />
with a built-in additional coil making Free Cooling using<br />
the outdoor air as cooling media.<br />
The free-cooling system installed on these chillers has<br />
been designed and applied by RC GROUP for the first<br />
time in the early 70’s and the today’s series is the result of<br />
more than 40 years experience.<br />
These chillers allow to achieve remarkable energy savings<br />
when installed in cold and temperate climate zones.<br />
MAXIMO PF<br />
Units for installation indoor.<br />
The Plug-fan allow the MAXIMO PF installation also<br />
inside offices with ducted air intake/exhaustion.<br />
The components completeness together with the wide<br />
range of available optional accessories allow very quick<br />
and easy installation operations; the units simply need<br />
electrical and hydraulic connections.<br />
C_GNR_0310<br />
maRCGROUP SpA
MAXIMO<br />
air cooled liquid chillers with free-cooling system<br />
93<br />
MAIN COMPONENTS<br />
• Housing in epoxy painted galvanized steel<br />
sheet.<br />
• Scroll compressors<br />
• Axial fans (MAXIMO)<br />
• Plug fan with EC motor (MAXIMO PF)<br />
• Welded plate evaporator<br />
• Pump-Down stop system<br />
• Proportional free-cooling system<br />
• MP.COM microprocessor control<br />
• Electrical box in separate compartment<br />
• Main switch with door lock safety<br />
MAIN OPTIONAL ACCESSORIES<br />
• Pumping group<br />
• Water tank<br />
• LNO kit for noise reduction<br />
• ELN kit for extreme noise reduction<br />
• Partial heat reclaim<br />
• Water flow safety switch<br />
• Brine kit for glycol solution production with<br />
temperatures down to -12°C.<br />
• Serial port<br />
• Optimizer system<br />
• Glycol-free system<br />
<strong>maximo</strong> PF<br />
MAXIMO PF - Condenser air discharge<br />
Remove a panel for the condenser air discharge<br />
(as indicated in the picture)<br />
ximo<br />
RCGROUP SpA<br />
C_GNR_0310
94<br />
MAXIMO<br />
air cooled liquid chillers with free-cooling system<br />
TECHNICAL DATA AND NOMINAL PERFORMANCES<br />
new<br />
MAXIMO<br />
single circuit / axial fans<br />
MODEL<br />
Size<br />
Cooling capacity (1)<br />
kW<br />
Free-cooling capacity (2) kW<br />
Compressors n.<br />
Power input (1)<br />
kW<br />
Gas circuits n.<br />
Weight<br />
kg<br />
Sound pressure (3) dB(A)<br />
21 24 28 30 34 40 50 52 58<br />
P1 S P1 S P1 S P1 S P1 S P1 S P1 S P2 S P2 S<br />
C1 C1 C1 C1 C2 C2 C2 C2 C3<br />
19,4 21,8 25,8 28,5 34,1 38,4 47,3 49,1 57,1<br />
18,9 19,9 24,1 25,0 32,3 36,5 43,6 44,1 55,2<br />
1 1 1 1 1 1 1 2 2<br />
6,2 7,3 8,4 9,9 10,6 12,5 16,4 17,4 18,8<br />
1 1 1 1 1 1 1 1 1<br />
430 440 440 440 600 600 740 700 930<br />
60,7 61,1 62,5 62,7 63,9 66,9 70,0 68,5 69,8<br />
MODEL<br />
Size<br />
Cooling capacity (1)<br />
kW<br />
Free-cooling capacity (2) kW<br />
Compressors n.<br />
Power input (1)<br />
kW<br />
Gas circuits n.<br />
Weight<br />
kg<br />
Sound pressure (3) dB(A)<br />
62 65 76 98 124 158 180 197 230<br />
P1 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P3 S<br />
C3 C3 C3 C4 C4 C4 C5 C5 C5<br />
60,8 64,2 73,6 95,5 117,0 151,0 174,0 187,0 214,0<br />
57,7 60,2 66,7 84,9 100,0 115,0 135,0 141,0 152,0<br />
1 2 2 2 2 2 2 2 3<br />
20,3 21,4 25,6 32,3 41,8 55,1 60,8 70,3 87,4<br />
1 1 1 1 1 1 1 1 1<br />
970 940 1000 1470 1610 1660 2240 2220 2370<br />
72,6 71,7 71,5 71,9 78,8 81,9 81,6 82,0 82,9<br />
new<br />
MAXIMO<br />
double circuit / axial fans<br />
MODEL<br />
52 58 65 76 98 124 158 180 197 240<br />
P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P4 D<br />
Size<br />
C2 C3 C3 C3 C4 C4 C4 C5 C5 C5<br />
Cooling capacity (1)<br />
kW 49,1 57,5 64,3 73,4 94,4 116,0 153,0 174,0 190,0 224,0<br />
Free-cooling capacity (2) kW 44,1 55,3 60,2 66,6 84,5 99,9 116,0 135,0 142,0 154,0<br />
Compressors n. 2 2 2 2 2 2 2 2 2 4<br />
Power input (1)<br />
kW 17,4 18,8 21,4 25,6 32,1 41,6 55,3 61,1 70,7 90,4<br />
Gas circuits n. 2 2 2 2 2 2 2 2 2 2<br />
Weight<br />
kg 700 920 930 1000 1470 1610 1640 2210 2230 2510<br />
Sound pressure (3) dB(A) 68,5 69,8 71,7 71,5 71,9 78,8 81,9 81,6 82,0 84,0<br />
(1) Referred to chilled water temperature 12/7°C / 20% glycol and air to the condenser at 35°C<br />
(2) Referred to water inlet temperature at 15°C / 20% glycol and outdoor temperature at 3°C<br />
(3) Sound pressure 1m far in free field conditions according to ISO3744 norms<br />
POWER SUPPLY: 400.3.50+N<br />
C_GNR_0310<br />
RCGROUP SpA
MAXIMO<br />
air cooled liquid chillers with free-cooling system<br />
95<br />
TECHNICAL DATA AND NOMINAL PERFORMANCES<br />
new<br />
MAXIMO PF<br />
single circuit / plug-fans<br />
MODEL<br />
Size<br />
Cooling capacity (1)<br />
kW<br />
Free-cooling capacity (2) kW<br />
Compressors n.<br />
Power input (1)<br />
kW<br />
Gas circuits n.<br />
Weight<br />
kg<br />
Sound pressure (3) dB(A)<br />
22 24 28 32 36 42 53 67<br />
P1 S P1 S P1 S P1 S P1 S P1 S P1 S P1 S<br />
C1 C1 C1 C1 C1 C1 C2 C2<br />
21,4 24,3 28,4 32,2 35,9 41,1 52,4 66,4<br />
18,4 20,0 23,4 26,5 28,8 30,7 43,1 53,2<br />
1 1 1 1 1 1 1 1<br />
6,3 7,3 8,5 9,7 11,0 13,4 16,4 20,5<br />
1 1 1 1 1 1 1 1<br />
450 460 460 470 470 480 750 790<br />
70,7 72,3 76,4 9,7 77,9 78,9 77,8 80,0<br />
MODEL<br />
Size<br />
Cooling capacity (1)<br />
kW<br />
Free-cooling capacity (2) kW<br />
Compressors n.<br />
Power input (1)<br />
kW<br />
Gas circuits n.<br />
Weight<br />
kg<br />
Sound pressure (3) dB(A)<br />
55 62 71 85 107 135 170 195 220 250<br />
P2 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P2 S P3 S<br />
C2 C2 C2 C3 C3 C4 C4 C4 C5 C5<br />
55,5 62,3 70,3 83,7 106,0 131,0 170,0 187,0 216,0 246,0<br />
46,7 51,6 56,7 68,8 82,7 102,0 126,0 129,0 160,0 170,0<br />
2 2 2 2 2 2 2 2 2 3<br />
17,0 19,4 21,9 25,2 32,4 40,9 52,6 62,4 66,7 83,0<br />
1 1 1 1 1 1 1 1 1 1<br />
740 810 820 1050 1240 1690 1800 1850 2320 2490<br />
76,4 70,3 72,6 76,5 81,3 74,1 77,6 77,6 77,6 77,9<br />
new<br />
MAXIMO PF<br />
double circuit / plug-fans<br />
MODEL<br />
55 62 71 85 107 135 170 195 220 265 290<br />
P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P2 D P4 D P4 D<br />
Size<br />
C2 C2 C2 C3 C3 C4 C4 C4 C5 C5 C5<br />
Cooling capacity (1)<br />
kW 55,6 62,7 70,3 83,5 104,0 129,0 168,0 190,0 220,0 261,0 285,0<br />
Free-cooling capacity (2) kW 46,7 51,7 56,7 68,7 82,5 101,0 125,0 130,0 161,0 174,0 179,0<br />
Compressors n. 2 2 2 2 2 2 2 2 2 4 4<br />
Power input (1)<br />
kW 17,0 19,5 21,9 25,2 32,7 40,7 52,3 62,8 67,1 84,2 102,0<br />
Gas circuits n. 2 2 2 2 2 2 2 2 2 2 2<br />
Weight<br />
kg 740 810 820 1050 1240 1690 1780 1820 2330 2670 2720<br />
Sound pressure (3) dB(A) 76,4 70,3 72,6 76,5 81,3 74,1 77,6 77,6 77,6 78,0 78,0<br />
(1) Referred to chilled water temperature 12/7°C / 20% glycol and air to the condenser at 35°C<br />
(2) Referred to water inlet temperature at 15°C / 20% glycol and outdoor temperature at 3°C<br />
(3) Sound pressure 1m far in free field conditions according to ISO3744 norms<br />
POWER SUPPLY: 400.3.50<br />
RCGROUP SpA<br />
C_GNR_0310
96<br />
MAXIMO<br />
air cooled liquid chillers with free-cooling system<br />
dimensionS (mm)<br />
MAXIMO<br />
Size a b c<br />
C1 1.250 1.010 1.950<br />
C2 1.800 1.180 2.000<br />
C3 2.600 1.340 2.000<br />
C<br />
C4 3.700 1.490 2.000<br />
C5 4.950 1.500 2.040<br />
A<br />
B<br />
MAXIMO PF<br />
Size a b c<br />
C1 1.250 1.010 1.950<br />
C2 1.800 1.180 2.000<br />
C3 2.600 1.340 2.000<br />
C<br />
C4 3.700 1.490 2.000<br />
C5 4.950 1.500 2.040<br />
B<br />
A<br />
C_GNR_0310<br />
RCGROUP SpA