Section 5. System Overview<br />

5.1.10.2.1 Security By-Pass<br />

Security can be bypassed at the datalogger using a external keyboard /<br />

displaykeyboard display. Pressing and holding the "Del" key while powering up a<br />

<strong>CR1000</strong> will cause it to abort loading a program and provide a 120 second<br />

window to begin changing or disabling security codes in the settings editor (not<br />

Status table) with the keyboard display.<br />

Keyboard display security bypass does not allow telecommunications access<br />

without first correcting the security code.<br />

Note This feature is not operable in <strong>CR1000</strong>KDs with serial numbers less than<br />

1263. Contact <strong>Campbell</strong> <strong>Scientific</strong> for information on upgrading the <strong>CR1000</strong>KD<br />

operating system.<br />

5.1.10.3 Passwords<br />

5.1.10.3.1 .csipasswd<br />

Passwords are used to secure IP based communications. They are set in various<br />

telecommunications schemes via the .csipasswd file, CRBasic PakBus<br />

instructions, CRBasic IS instructions, and in <strong>CR1000</strong> settings.<br />

The .csipasswd file is a file created and edited through DevConfig, and which<br />

resides on the CPU: drive of the <strong>CR1000</strong>. It contains credentials (usernames and<br />

passwords) required to access datalogger functions over IP telecommunications.<br />

See Web API for details concerning the .csipasswd file.<br />

5.1.10.3.2 PakBus Instructions<br />

The following CRBasic PakBus instructions have provisions for password<br />

protection:<br />

• ModemCallBack()<br />

• SendVariable()<br />

• SendGetVariables()<br />

• SendFile()<br />

• GetVariables()<br />

• GetFile()<br />

• GetDataRecord()<br />

5.1.10.3.3 IS Instructions<br />

The following CRBasic instructions that service <strong>CR1000</strong> IP capabilities have<br />

provisions for password protection:<br />

• EMailRecv()<br />

• EMailSend()<br />

• FTPClient()<br />