Appendix B. Status Table and Settings<br />

Table 121. Status-Table Fields and Descriptions<br />

Fieldname Description Variable Type Default Range Edit Info Type<br />

Low12VCount5<br />

Number of times system<br />

voltage dropped below 9.6<br />

between resets. When this<br />

condition is detected, the<br />

<strong>CR1000</strong> ceases<br />

measurements and goes into<br />

a low-power mode until<br />

proper system voltage is<br />

restored.<br />

Integer 0 0-99<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

Low5VCount<br />

Number of occurrences of<br />

the 5V supply dropping<br />

below a functional threshold.<br />

Integer 0 0-99<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

CompileResults<br />

StartUpCode6<br />

ProgErrors<br />

Contains error messages<br />

generated by compilation or<br />

during runtime.<br />

A flag indicating that the<br />

currently running program<br />

was compiled due to a<br />

power-up reset.<br />

The number of compile or<br />

runtime errors for the current<br />

program.<br />

String 0 Error<br />

Integer 0 0 or 1 Status / Error<br />

Integer 0 Error<br />

VarOutOfBound7<br />

Number of times an array<br />

was accessed out of bounds.<br />

Integer 0 0<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

SkippedScan<br />

Number of skipped scans that<br />

have occurred while running<br />

the current program instance.<br />

Does not include scans<br />

intentionally skipped as may<br />

occur with the use of<br />

ExitScan and Do / Loop<br />

instructions.<br />

Integer 0<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

SkippedSystemScan8<br />

The number of scans skipped<br />

in the background<br />

calibration.<br />

Integer array 0<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

SkippedSlowScan9<br />

The number of scans skipped<br />

in a SlowSequence.<br />

Integer array. 0<br />

Yes<br />

Reset by<br />

changing to 0<br />

Error<br />

ErrorCalib8<br />

The number of erroneous<br />

calibration values measured.<br />

The erroneous value is<br />

discarded (not included in the<br />

filter update).<br />

Integer 0 0 Error<br />

MemorySize<br />

Total amount of SRAM<br />

(bytes) in this device.<br />

2097152 (2M)<br />

4194304 (4M)<br />

Status<br />

530