Section 10. Troubleshooting<br />

Battery Test<br />

If using a rechargeable power supply,<br />

disconnect the charging source (i.e., solar panel<br />

or AC transformer) from the battery pack.<br />

Wait 20 minutes before proceeding with this<br />

test.<br />

Test Voltage at Charging Regulator<br />

Set a voltmeter to read DC voltage as high as<br />

15 Vdc. Measure the voltage between a 12V<br />

and G terminal on the charging regulator.<br />

Is the voltage > 11.0 Vdc<br />

No<br />

Yes<br />

Test the Battery Under Load<br />

Program the <strong>CR1000</strong> to measure battery<br />

voltage using a 0.01-second scan rate. Use the<br />

voltmeter to measure the voltage between a<br />

12V and G terminal on the charging regulator.<br />

Is the voltage > 10.8 Vdc<br />

No<br />

Is the battery a sealed, rechargeable<br />

battery<br />

Yes<br />

Is the voltage ≥ 10.5 Vdc<br />

No<br />

No<br />

Replace battery / batteries*<br />

Yes<br />

Yes<br />

Recharge battery.*<br />

Is the battery voltage > 12 Vdc<br />

The battery is good.<br />

Yes<br />

No<br />

Battery voltage is adequate for <strong>CR1000</strong> operation. However, if the <strong>CR1000</strong> is to function<br />

for a long period, <strong>Campbell</strong> <strong>Scientific</strong> recommends replacing, or, if using a sealed,<br />

rechargeable battery, recharging the battery so the voltage is > 12 Vdc.<br />

*When using a sealed, rechargeable battery that is recharged with primary power provided by solar panel or ac/ac - ac/dc transformer, testing the<br />

charging regulator is recommended. See Charging Regulator with Solar Panel Test (p. 437) or Charging Regulator with Transformer Test (p. 439).<br />

10.5.3.2 Charging Regulator with Solar-Panel Test<br />

The procedure outlined in this flow chart tests PS100 and CH100 charging<br />

regulators that use solar panels as the power source. If a need for repair is<br />

indicated after following the procedure, see Warranty and Assistance (p. 3) for<br />

information on sending items to <strong>Campbell</strong> <strong>Scientific</strong>.<br />