Section 10. Troubleshooting<br />

Table 110. Warning Message Examples<br />

Example of Warning Message<br />

Warning: Machine self-calibration failed.<br />

Warning: Slow Seq 1, Scan 1, will skip<br />

scans if running with Scan 1<br />

Warning: Table [tablename] is declared<br />

but never called.<br />

Warning: Units:<br />

a_units_name_that_is_more_than_38_char<br />

a... too long will be truncated to 38 chars.<br />

Warning: Voice word TEH is not in<br />

Voice.TXT file<br />

Meaning<br />

Indicates a problem with the analog<br />

measurement hardware during the self<br />

calibration. An invalid external sensor signal<br />

applying a voltage beyond the internal ±8-Vdc<br />

supplies on a voltage input can induce this error.<br />

Removing the offending signal and powering up<br />

the logger will initiate a new self-calibration. If<br />

the error does not occur on power-up, the<br />

problem is corrected. If no invalid external<br />

signals are present and / or self-calibration fails<br />

again on power-up, the <strong>CR1000</strong> should be<br />

repaired by a qualified technician.<br />

SlowSequence scan rate is