200<br />

Section 7. Installation<br />

Table 37. Parameters for Analog Burst Mode (601 to 2000 Hz)<br />

CRBasic<br />

Analog<br />

Voltage<br />

Input<br />

Parameters<br />

Destination<br />

Repetitions<br />

Voltage Range<br />

Single-Ended<br />

Channel<br />

Differential<br />

Channel<br />

Measure Offset<br />

Measurements<br />

per Excitation<br />

Reverse Ex<br />

Rev Diff<br />

Settling Time<br />

Integ<br />

Multiplier<br />

Offset<br />

Description when in Burst Mode<br />

A variable array dimensioned to store all measurements from a single channel.<br />

For example, the command,<br />

Dim FastTemp(500)<br />

dimensions array FastTemp() to store 500 measurements (one second of data at<br />

500 Hz, one-half second of data at 1000 Hz, etc.)<br />

The dimension can be any integer from 1 to 65535.<br />

The number of measurements to make on a single channel. This number<br />

usually equals the number of elements dimensioned in the Destination array.<br />

Valid arguments range from 1 to 65535.<br />

The analog input voltage range to be used during measurements. No change<br />

from standard measurement mode. Any valid voltage range can be used.<br />

However, ranges appended with 'C' cause measurements to be slower than<br />

other ranges.<br />

The single-ended analog input channel number preceded by a dash (-). Valid<br />

arguments range from -1 to -16.<br />

The differential analog input channel number preceded by a dash (-). Valid<br />

arguments range from -1 to -8.<br />

No change from standard measurement mode. False allows for faster<br />

measurements.<br />

Must equal the value entered in Repetitions<br />

No change from standard measurement mode. For fastest rate, set to False.<br />

No change from standard measurement mode. For fastest rate, set to False.<br />

Sample interval in µs. This argument determines the measurement rate.<br />

500 µs interval = 2000 Hz rate<br />

750 µs interval = 1333.33 Hz rate<br />

Ignored if set to an integer. _50Hz and _60Hz are valid for AC rejection but are<br />

seldom used in burst applications.<br />

No change from standard measurement mode. Enter the proper multiplier.<br />

This is the slope of the linear equation that equates output voltage to the<br />

measured phenomena. Any number greater or less than 0 is valid.<br />

No change from standard measurement mode. Enter the proper offset. This is<br />

the Y intercept of the linear equation that equates output voltage to the<br />

measured phenomena.<br />

7.8.13 String Operations<br />

String operations are performed using CRBasic string functions, as listed in String<br />

Functions (p. 502).<br />

236