Section 7. Installation<br />

7.8.8.2 I/O Ports<br />

The <strong>CR1000</strong> supports two-way serial communication with other instruments<br />

through ports listed in table <strong>CR1000</strong> Serial Ports (p. 202). A serial device will often<br />

be supplied with a nine-pin D-type connector serial port. Check the manufacture's<br />

pinout for specific information. In most cases, the standard nine-pin RS-232<br />

scheme is used. If that is the case then,<br />

• Connect sensor RX (receive, pin 2) to datalogger Tx (transmit, channel C1,<br />

C3, C5, C7).<br />

• Connect sensor TX (transmit, pin 3) to datalogger Rx (receive, channel C2,<br />

C4, C6, C8).<br />

• Connect sensor ground (pin 5) to datalogger ground (G terminal)<br />

Note Rx and Tx lines on nine-pin connectors are sometimes switched by the<br />

manufacturer.<br />

Table 31. <strong>CR1000</strong> Serial Ports<br />

Serial Port Voltage Level Logic<br />

RS-232 (9-pin) RS-232 Full-duplex asynchronous RS-232<br />

CS I/O (9-pin) TTL Full-duplex asynchronous RS-232<br />

COM1 (C1 - C2) TTL Full-duplex asynchronous RS-232/TTL<br />

COM2 (C3 - C4) TTL Full-duplex asynchronous RS-232/TTL<br />

COM3 (C5 - C6) TTL Full-duplex asynchronous RS-232/TTL<br />

COM4 (C7 - C8) TTL Full-duplex asynchronous RS-232/TTL<br />

C1 5 Vdc SDI-12<br />

C3 5 Vdc SDI-12<br />

C5 5 Vdc SDI-12<br />

C7 5 Vdc SDI-12<br />

C1, C2, C3 5 Vdc<br />

SDM (used with <strong>Campbell</strong> <strong>Scientific</strong><br />

peripherals only)<br />

7.8.8.3 Protocols<br />

PakBus is the protocol native to the <strong>CR1000</strong> and transparently handles routine<br />

point-to-point and network communications among PCs and <strong>Campbell</strong> <strong>Scientific</strong><br />

dataloggers. Modbus and DNP3 are industry-standard networking SCADA<br />

protocols that optionally operate in the <strong>CR1000</strong> with minimal configuration by the<br />

user. PakBus®, Modbus, and DNP3 operate on the RS-232, CS I/O, and four<br />

COM ports. SDI-12 is a protocol used by some smart sensors that requires<br />

minimal configuration on the <strong>CR1000</strong>.<br />

Read More! See SDI-12 Recording (p. 323), SDI-12 Sensor Support (p. 172), PakBus<br />

Overview (p. 351), DNP3 (p. 364), and Modbus (p. 367).<br />

Many instruments require non-standard protocols to communicate with the<br />

<strong>CR1000</strong>.<br />