Section 7. Installation<br />

Example:<br />

Probe: Water Content<br />

Power Usage:<br />

• Quiescent: 0.25 mA<br />

• Measurement: 120 mA<br />

• Measurement Time: 15 s<br />

• Active: 66 mA<br />

• Timeout: 15 s<br />

Probes 1, 2, 3, and 4 are connected to SDI-12 / Control Port 1.<br />

The time line in table Example Power Usage Profile for a Network of SDI-12<br />

Probes (p. 186) shows a 35-second power-usage profile example.<br />

For most applications, total power usage of 318 mA for 15 seconds is not<br />

excessive, but if 16 probes were wired to the same SDI-12 port, the resulting<br />

power draw would be excessive. Spreading sensors over several SDI-12 terminals<br />

will help reduce power consumption.<br />

Table 28. Example Power Usage Profile for a Network of SDI-12 Probes<br />

Sec<br />

Command<br />

All<br />

Probes<br />

Awake<br />

Time<br />

Out<br />

Expires 1 mA 2 mA 3 mA 4 mA<br />

Total<br />

mA<br />

1 1M! Yes 120 66 66 66 318<br />

2 120 66 66 66 318<br />

• • • • • •<br />

• • • • • •<br />

• • • • • •<br />

14 120 66 66 66 318<br />

15 Yes 120 66 66 66 318<br />

16 1D0! Yes 66 66 66 66 264<br />

17 66 66 66 66 264<br />

• • • • • •<br />

• • • • • •<br />

• • • • • •<br />

29 66 66 66 66 264<br />

30 Yes 66 66 66 66 264<br />

31 0.25 0.25 0.25 0.25 1<br />

• • • • • •<br />

• • • • • •<br />

• • • • • •<br />

35 0.25 0.25 0.25 0.25 1<br />

186