<strong>Wisotronic</strong> <strong>dialog</strong> 1-<strong>Channel</strong> <strong>Central</strong><br />

<strong>Control</strong> <strong>Unit</strong> <strong>EWFS</strong> ® The slat angle can be adjusted at outside venetian blinds and internal venetian<br />

7.2.3 Turn time<br />

blinds in order to change or optimize the light incidence in a room.<br />

The following figure illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Outside<br />

Inside<br />

+80° 0°<br />

-80°<br />

Fig. 7-7:<br />

Slat angle at external venetian blinds and internal venetian blinds<br />

It is obvious that a drive motor requires a certain time when turning the slat until<br />

(as in our simple example) the slats have been turned from the position "+80°" to<br />

the position "-80°". In addition this turn time differs for various product types. For<br />

example, an internal venetian blind requires approximately 0.5 seconds, whereas<br />

this procedure can also take 1.6 seconds for an outside venetian blind, type<br />

E80A6. If this turn time is known, you only have to store it once in your<br />

<strong>Wisotronic</strong> together with the minimum and maximum possible turning angle.<br />

Afterwards the turning angles can be specified by simply entering angle degrees.<br />

Time-consuming determining of turn times and experimenting are superfluous.<br />

The following table shows the most common product types and their turn times/<br />

turning angles (only WAREMA products are listed here. If you want to control<br />

products of other manufacturers, please contact the respective manufacturer).<br />

Slat type<br />

Description Max.<br />

Min. Turntime<br />

(slat) angle (°) angle (°) (Sec.)<br />

E80A6 flanged +80 -80 1,6<br />

E80AF Flat slat +80 0 0,8<br />

E60A6 flanged +75 -75 1,3<br />

E60A2 flanged +70 -70 1,3<br />

E100AF Flat slat +80 0 1,1<br />

E50A1 Flat slat +70 -70 1,0<br />

If, for example, you have mounted external venetian blinds of the type E80A6,<br />

you have to set a value of 1.6 seconds for the turn time, a value of +80° for the<br />

maximum turning angle and -80° for the minimum turning angle.<br />

TIP<br />

Minor adjustments may be necessary depending on the<br />

package weight and motor type.<br />

932806A0•816757•7974k0•08.10.2004 We reserve the right to carry out improvements 83