<strong>Wisotronic</strong> <strong>dialog</strong> 1-<strong>Channel</strong> <strong>Central</strong><br />
<strong>Control</strong> <strong>Unit</strong> <strong>EWFS</strong> ® The slat angle can be adjusted at outside venetian blinds and internal venetian<br />
7.2.3 Turn time<br />
blinds in order to change or optimize the light incidence in a room.<br />
The following figure illustrates the setting of the slat angle:<br />
Positive value: Slats are turned outwards<br />
Negative value: Slats are turned inwards<br />
Setting 0°: The slats remain in a horizontal position<br />
Outside<br />
Inside<br />
+80° 0°<br />
-80°<br />
Fig. 7-7:<br />
Slat angle at external venetian blinds and internal venetian blinds<br />
It is obvious that a drive motor requires a certain time when turning the slat until<br />
(as in our simple example) the slats have been turned from the position "+80°" to<br />
the position "-80°". In addition this turn time differs for various product types. For<br />
example, an internal venetian blind requires approximately 0.5 seconds, whereas<br />
this procedure can also take 1.6 seconds for an outside venetian blind, type<br />
E80A6. If this turn time is known, you only have to store it once in your<br />
<strong>Wisotronic</strong> together with the minimum and maximum possible turning angle.<br />
Afterwards the turning angles can be specified by simply entering angle degrees.<br />
Time-consuming determining of turn times and experimenting are superfluous.<br />
The following table shows the most common product types and their turn times/<br />
turning angles (only WAREMA products are listed here. If you want to control<br />
products of other manufacturers, please contact the respective manufacturer).<br />
Slat type<br />
Description Max.<br />
Min. Turntime<br />
(slat) angle (°) angle (°) (Sec.)<br />
E80A6 flanged +80 -80 1,6<br />
E80AF Flat slat +80 0 0,8<br />
E60A6 flanged +75 -75 1,3<br />
E60A2 flanged +70 -70 1,3<br />
E100AF Flat slat +80 0 1,1<br />
E50A1 Flat slat +70 -70 1,0<br />
If, for example, you have mounted external venetian blinds of the type E80A6,<br />
you have to set a value of 1.6 seconds for the turn time, a value of +80° for the<br />
maximum turning angle and -80° for the minimum turning angle.<br />
TIP<br />
Minor adjustments may be necessary depending on the<br />
package weight and motor type.<br />