04.01.2015 Views

Wisotronic dialog 1-Channel Central Control Unit EWFS - Warema

Wisotronic dialog 1-Channel Central Control Unit EWFS - Warema

Wisotronic dialog 1-Channel Central Control Unit EWFS - Warema

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Wisotronic</strong> <strong>dialog</strong> 1-<strong>Channel</strong> <strong>Central</strong><br />

<strong>Control</strong> <strong>Unit</strong> <strong>EWFS</strong> ®<br />

6.1.7 Sun control limit "OPEN" This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. This specifies the<br />

brightness from which the slats of external or internal venetian blinds are to be<br />

turned to a horizontal position, for example in order to let more light into the room<br />

when the sky is covered but bright. The setting range is from 0 - 99 klx. If you do<br />

not want to evaluate the limit "OPEN", you can also set the value "0"<br />

(---) here. Proceed as follows in order to change the setting value:<br />

■<br />

Change to the sun control menu as described above. Turn the function dial<br />

until the following display appears:<br />

Sun<br />

limit OPEN<br />

28 klx<br />

— + | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). If you want to exit the menu without saving the changes,<br />

press the } button twice consecutively. This completes the process.<br />

6.1.8 Sun control delay "OPEN"<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. A delay period can<br />

be assigned to the "OPEN" limit so that the slats are not turned open immediately<br />

whenever the intensity of brightness changes (for example if the clouds only<br />

become denser temporarily). This smooths the movement behavior of the sun<br />

protection and thus increases the comfort. The turn command is triggered and the<br />

slats are turned open if the limits are reached or if the value drops below these<br />

limits for the duration of the delay period. The setting range is from 0 - 99<br />

minutes. Proceed as follows in order to change the setting value:<br />

■ Change to the sun control menu as described above. Turn the function dial<br />

until the following display appears:<br />

Sun<br />

delay OPEN<br />

0 minutes<br />

— + | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). If you want to exit the menu without saving the changes,<br />

press the } button twice consecutively. This completes the process.<br />

6.1.8.1 The "OPEN" limit<br />

The following instructions for the setting of the "DOWN", "OPEN" and "UP" limits<br />

have to be observed in order for the sun control to function properly in connection<br />

with the "OPEN" limit:<br />

■<br />

■<br />

■<br />

The lowest value must always be the value for "UP", for example 5 klx<br />

The highest value must always be the value for "DOWN", for example 30 klx<br />

The value for "OPEN" must be set between these values, for example 10 klx.<br />

TIP<br />

In order to find the optimal setting for your sun protection<br />

system you should test various values on a bright day with<br />

varying cloud situations. This is the only way of obtaining the<br />

optimum result.<br />

28<br />

We reserve the right to carry out improvements<br />

932806A0•816757•7974k0•08.10.2004

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!