11 CONC 12<br />

NO 14<br />

A2 coil A1<br />

11 CONC 12<br />

NO 14<br />

A2 coil A1<br />

11 CONC 12<br />

NO 14<br />

A2 coil A1<br />

<strong>Installation</strong> <strong>Instructions</strong><br />

SRMV<br />

Single Relay Module (Voltage)<br />

Important: Retain these instructions<br />

1 UNPACKING<br />

SRMV <strong>Installation</strong> Instruction<br />

91-2853<br />

2 STORING<br />

-40 °C<br />

(-40 °F)<br />

+70 °C<br />

(+158 °F)<br />

3 INSTALLATION<br />

0 <br />

0 %RH 95 %RH<br />

It is recommended that the installation<br />

should comply with the HSE<br />

Memorandum of Guidance on<br />

Electricity at Work Regulations 1989.<br />

For USA install equipment in<br />

accordance with the National<br />

Electric Code.<br />

15.5 mm<br />

(0.61”)<br />

1 Dimensions relay contact<br />

2 Requirements<br />

terminals<br />

coil terminals<br />

a<br />

A2 coil A1<br />

NO 14<br />

11 + <br />

+ 12<br />

75.5 mm (2.97”)<br />

42 mm (1.65”)<br />

SRMV/USA: the unit<br />

is UL rated as<br />

‘UL916 listed open<br />

energy management<br />

equipment<br />

accessory’.<br />

c<br />

-25 °C<br />

(-13 °F)<br />

+85 °C<br />

(+185 °F)<br />

0 0 %RH 90 %RH<br />

Protection: IP20<br />

(NEMA1)<br />

SRMV <strong>Installation</strong> <strong>Instructions</strong> 91-2853 Issue 3/C 22/11/06 1


)<br />

*<br />

+<br />

,<br />

$ % & ' <br />

8<br />

! " # $ % & ' ! " #<br />

" 8<br />

, 2<br />

<br />

6 : 4 :<br />

! " # $ % & ' <br />

) <br />

SRMV<br />

<strong>Installation</strong> <strong>Instructions</strong><br />

3 INSTALLATION (Continued)<br />

3<br />

Fit to DIN rail<br />

b<br />

a<br />

Standard top hat DIN rail (DIN 46277-3, EN50022, BS5584:1978)<br />

4<br />

To Mount on Flat Surface<br />

a<br />

b<br />

Ø 3 mm<br />

(0.118”)<br />

c<br />

d<br />

5<br />

Switch off IQ<br />

6<br />

Ensure IQ Output channel<br />

is Analogue set to Voltage<br />

IQ<br />

IQ<br />

<br />

1<br />

SIG<br />

0 V<br />

V<br />

IQ Controller<br />

<strong>Installation</strong> <strong>Instructions</strong><br />

2<br />

SRMV <strong>Installation</strong> <strong>Instructions</strong> 91-2853 Issue 3/C 22/11/06


<strong>Installation</strong> <strong>Instructions</strong><br />

SRMV<br />

3 INSTALLATION (Continued)<br />

7<br />

Wire module to controller<br />

Terminal size 2 x 2.5 mm 2 (11 AWG) wires - Cu only<br />

I = 17.5 mA<br />

IQ<br />

SRMV<br />

SIG<br />

0 V<br />

A2<br />

Relay<br />

A1 coil<br />

A2 coil A1<br />

NO 14<br />

11 + <br />

+ 12<br />

polarity independent<br />

8<br />

Ensure HVAC Equipment Power Supply is Switched off<br />

<br />

1<br />

Power Supply<br />

SRMV<br />

HVAC<br />

Equipment<br />

Power<br />

9<br />

Connect Relay to HVAC Equipment<br />

250 Vac @ 8A (resistive), 5A (inductive,<br />

cos ø>=0.4)<br />

20 Vdc @ 8A (resistive)<br />

24 Vdc @ 2A (inductive, T


11 CONC 12<br />

NO 14<br />

A2 coil A1<br />

OK<br />

TX RX<br />

12345678910<br />

LAN<br />

)<br />

*<br />

+<br />

,<br />

<br />

$ % & ' <br />

8<br />

6 : 4 : ) <br />

" 8<br />

! " # $ % & ' ! " #<br />

! " # $ % & ' <br />

, 2<br />

SRMV<br />

<strong>Installation</strong> <strong>Instructions</strong><br />

3 INSTALLATION (Continued)<br />

10 Close panel<br />

11 Switch on IQ<br />

IQ<br />

SRMV/USA. The unit is UL rated as ‘UL916<br />

listed open energy management equipment<br />

accessory.<br />

<br />

1<br />

12<br />

Switch on HVAC Equipment Power Supply<br />

<br />

1<br />

Power Supply<br />

SRMV<br />

HVAC<br />

Equipment<br />

Power<br />

13<br />

Check Relay operation<br />

IQ<br />

DP<br />

‘click’<br />

A<br />

B<br />

C<br />

D<br />

16 17 18 19 20<br />

V<br />

24V<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15<br />

A2 coil A1<br />

SRMV<br />

NO 14<br />

11 CO + 12<br />

HVAC<br />

Equipment<br />

4 DISPOSAL<br />

WEEE Directive :<br />

At the end of their useful life the packaging,<br />

and product, should be disposed of by a<br />

suitable recycling centre.<br />

Do not dispose of with normal household waste.<br />

Do not burn.<br />

Manufactured for and on behalf of the Environmental and Combustion <strong>Controls</strong> Division of Honeywell Technologies Sàrl, Ecublens, Route<br />

du Bois 37,Switzerland by its Authorized Representative, <strong>Trend</strong> Control Systems Limited.<br />

<strong>Trend</strong> Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof<br />

without obligation to notify any person of such revisions or changes.<br />

<strong>Trend</strong> Control Systems Limited<br />

P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com<br />

<strong>Trend</strong> Control Systems USA<br />

6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com<br />

4<br />

SRMV <strong>Installation</strong> <strong>Instructions</strong> 91-2853 Issue 3/C 22/11/06