02.01.2015 Views

HGP-SIV Volume meter - Brunata

HGP-SIV Volume meter - Brunata

HGP-SIV Volume meter - Brunata

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>HGP</strong>-<strong>SIV</strong> <strong>Volume</strong> <strong>meter</strong><br />

Installation and users manual


Please read this before installation<br />

This manual is intended for skilled personal having a formal knowledge to water <strong>meter</strong>s.<br />

The <strong>Brunata</strong> <strong>HGP</strong>-<strong>SIV</strong> volume <strong>meter</strong> must only be used and installed as described in<br />

the manual.<br />

The working data of the <strong>meter</strong> are shown on the label of the <strong>meter</strong>. For further information<br />

we refer to the data sheet.<br />

INPORTANT: Seals and void labels must not be removed or damaged. This will infringe<br />

the warranty of the <strong>meter</strong>.<br />

The <strong>meter</strong> contains of following parts:<br />

1. Flow sensor<br />

2. Flow electronic unit<br />

3. Display unit<br />

4. Signal cable between flow electronics and display unit<br />

5. Installation and users manual<br />

When unpacking the <strong>meter</strong>, please check that all parts are enclosed. The serial<br />

numbers of the flow sensor and the electronic units must be identical, since the parts<br />

are calibrated. The serial number is also programmed into the memory of the <strong>meter</strong>,<br />

please refer to display functions later in this manual.<br />

Versions and ordering code<br />

x: Flow of the <strong>meter</strong><br />

(q p<br />

)in m 3 /h<br />

yy: Connection size:<br />

- 39 = G2B 300 mm<br />

- 40 = DN40 300 mm<br />

- 50 = DN50 270 mm<br />

- 65 = DN65 300 mm<br />

- 80 = DN80 300 mm<br />

- 100 = DN100 360 mm<br />

- 125 = DN125 360 mm<br />

- 150 = DN150 500 mm<br />

z: Menu/display:<br />

174: Standard version with<br />

peak values<br />

178: Tariff <strong>meter</strong><br />

107: Without display<br />

<strong>HGP</strong>-<strong>SIV</strong>x-yy-17z/ABCDE<br />

A: Power supply:<br />

1: 230 VAC<br />

2: 24 VAC<br />

B: Display backlight:<br />

B: with /-: without<br />

C: Programmed for external<br />

<strong>meter</strong>s: 0, 1 or 2<br />

D: Communication module:<br />

M-Bus / LonWorks / RS232 /<br />

- none<br />

E: Nos. of accounting periods:<br />

0 / 6 / 12 / 24<br />

2


Installation<br />

Preparation for installation<br />

Please note that the installation must be done in such a way that it meets the requirements<br />

for internal fitting, distances that have to be respected, etc. Straight pipe sections<br />

before or after the <strong>meter</strong> are not required.<br />

It is recommended that stop valves are fitted before and after the <strong>meter</strong> to<br />

make it easier to remove and reinstall the <strong>meter</strong> if service and verification are<br />

required. To ensure that there are no foreign bodies in the pipe section, it is recommended<br />

that the pipes are flushed through before the <strong>meter</strong> is installed. A<br />

adapter pipe can be used for this purpose. After installation, the valves should<br />

be opened in the order which provides correct flow through the <strong>meter</strong>.<br />

The HG-<strong>meter</strong> has been approved for installation in industrial areas, but it is recommended<br />

that installation close to components that may cause strong electromagnetic<br />

interference is avoided.<br />

Installation of the flow sensor<br />

The flowsensor is installed with the arrow in the flow direction. The flow sensor can be<br />

installed in any direction (vertically, horizontally etc), only the flow sensor must always be<br />

filled with water when running.<br />

Do not insulate the housing of the flow sensor.<br />

Fitting and connection of flow electronic unit, fig. 1<br />

Place the flow electronic unit on an even surface with 3 screws. All connections to the<br />

<strong>meter</strong> must be fitted before mains voltage is connected.<br />

The connection cable from the Flow Sensor is inserted into the socket marked Flow<br />

Head [8] in fig. 1. Note the locking system and how the cable exits the box. To dismantle<br />

the plug, use a small screwdriver to lift the lock. Never shorten nor lengthen the cables<br />

for the flowsensor. If the cable must be rolled up, the dia<strong>meter</strong> of the roll should<br />

at least be 30 cm.<br />

The power supply cable (230 or 24 V) is inserted through the strain relief, which must<br />

be tightened before tightening the terminal connections [1] in fig. 1.<br />

Signal cable to display unit are installed in terminals A1, A2, B1 and B2, [11] in fig. 1.<br />

3


Fitting and connection of display unit, fig 2<br />

Place the display unit on an even surface with 3 screws. All connections to the <strong>meter</strong><br />

must be fitted before mains voltage is connected.<br />

The connecting cable from flow electronic unit is connected to plug M57, see fig 4.<br />

The other cables that need to be connected are led through rubber membrane and<br />

bypass and connected with their respective terminals. Pulse inputs are connected with<br />

terminal [9] and [10], and the remote reading with terminal [5] and [6]. A small screwdriver<br />

or the like can be used to perforate the rubber membrane.<br />

The power supply cable for 230 Volt (possibly 24 Volt) is led through the rubber<br />

membrane and connected with terminal [4] in fig.1, then the strain relief is tightened<br />

moderately. Earth connection is not required.<br />

4


NINGSKLEMMER<br />

Connecting terminals<br />

Flow electronic unit<br />

24 V AC)<br />

ængde<br />

abel<br />

isplayenhed *<br />

ndstikskort *<br />

Fig. 1 Connecting <br />

terminals <strong>HGP</strong> flow electronics<br />

<br />

<br />

No. Indication Connection<br />

1. 230V AC Power (24VAC is possible)<br />

2. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

3. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

4. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

5. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

<br />

<br />

på <strong>HGP</strong>-<strong>SIV</strong><br />

varme rør (rød)<br />

kolde rør (blå)<br />

an være 24VAC)<br />

r datakommunikation, M-Bus, Lon eller RS232<br />

r datakommunikation, M-Bus, Lon eller RS232<br />

pulsudgang, volumen<br />

<br />

<br />

<br />

<br />

6. VOL +/- Pulse out, water volume<br />

7. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

8. FLOW HEAD Stik til flowsensorkabel<br />

9. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

10. Not on <strong>HGP</strong>-<strong>SIV</strong><br />

11. A1,A2,B1,B2 Cable connection to Display unit *<br />

12. HF-plug Connection to insertion module *<br />

* see next page<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

5


Ledningsförbindelser och anslutningsklämmer<br />

Displayenhet Display unit<br />

1<br />

13<br />

12<br />

11<br />

10<br />

9<br />

2 3 4<br />

5 6 7 8<br />

NR. MÄRKNING ANSLUTNING Fig. 2 Connecting terminals <strong>HGP</strong>-<strong>SIV</strong> Display Unit<br />

1 FLÖDESSENSOR .. 4-polig, skärmad stickkontakt till flödessensorkabel<br />

PULSVÄRDEN:<br />

2 HIGH No. TEMP. Indication ........... Temperatursensor, Installation varma rör (röd)<br />

3 LOW TEMP............. Temperatursensor, kalla rör (blå)<br />

Mätarens volymp<br />

4 230 VAC.................. 1 FLOWSENSOR Strömspänning 4 legged (Kan vara shielded 24 VAC) plug for flow sensor cable är beroende av<br />

5 A1 B1. ................... 1. Anslutning av datakommunikation, M-Bus, Lon eller RS232 mätarens storlek.<br />

2 HIGH TEMP. Not used on volume <strong>meter</strong><br />

6 A2 B2. ................... 2. Anslutning av datakommunikation, M-Bus, Lon eller RS232 Framgår av<br />

7 - VOL. 3+................... LOW TEMP. Öppen kollektor Not pulsutgång, used on volume volym <strong>meter</strong><br />

typmärket.<br />

8 - ENERGI +. ............ Öppen kollektor pulsutgång, energi<br />

4 230 VAC. Power (24VAC is possible)<br />

Energipuls har<br />

9 - AUX2 +. ................ Extern pulsingång från t ex elmätare<br />

samma värde som<br />

10 - AUX1 5+. ................ A1 B1. Extern pulsingång 1. Installation från t ex of kallvattenmätare<br />

datacommunication, MBus, Lon or RS232 sista siffran i<br />

11 Kontakter 1 & 2 ....... Kontakter för tillkoppling av intern +5 V till AUX- ingångarna<br />

displayen.<br />

12 0 V +5<br />

6<br />

V. ................<br />

A2 B2.<br />

Genemsam<br />

2.<br />

noll<br />

Installation<br />

och +5 V<br />

of<br />

DC<br />

datacommunication,<br />

utgång<br />

MBus or Lon<br />

Har t ex MWh-display<br />

13 M52. ........................ 7 - VOL. +. Stickkontakt Open för datakommunikationskort, collector pulse out, volume M-Bus, pulse Lon eller is shown RS232 on siffror display<br />

efter kommat, ä<br />

8 - ENERGI +. Not used on volume <strong>meter</strong><br />

Pulsutgångar 9 för - AUX2 volym +. och energi Ext. incoming pulse from f.inst. electricity <strong>meter</strong><br />

Pulsutgångens optokopplare strömförsörjs via belastningsmotstånd R, som dimensioneras enl. tabell<br />

10 - AUX1 +. Ext. incoming pulse from f.inst. cold water <strong>meter</strong><br />

11 Switches 1&2 Switches for connection of internal +5V to AUX terminals<br />

Inställning av extern<br />

+Vmax<br />

<br />

5.1<br />

28 V<br />

Motstånd R<br />

strömförsörjning 12 0V +5V. R Common VV<br />

Imax 20 mA<br />

5mA<br />

zero and +5V DC exit<br />

(från mätare: 5 VDC)<br />

Von max 1,5 V<br />

13 M52. Connector for data communication module, MBus, Lon<br />

+V R för I=5 mA<br />

ton=toff=140 ms är standardinställning<br />

Pulsperiod or T= RS232<br />

ton + toff = 280 ms.<br />

5 700 <br />

+<br />

+Voff<br />

10 1,7 k<br />

15 Values 2,7 of k pulse<br />

20 3,7 k<br />

Von toff ton<br />

24 <strong>Volume</strong> GND (0V)<br />

4,5<br />

pulse<br />

k<br />

HGG-<strong>SIV</strong>-<strong>meter</strong> pulse value depends on Fig. size 2 Anslutningsexempel of the <strong>meter</strong>. Please för consult<br />

Pulsperioder från 40 till 1560 ms kan förekomma<br />

volympulsutgång med intern 5 V<br />

28 the type<br />

5,3<br />

sign.<br />

k<br />

försörjning<br />

6


af forbindelsesledning mellem flowelektronik og displayenhed<br />

ation skal der være slukket for netspændingen til såvel flowelektronikken som displayenheden.<br />

egel er <strong>HGP</strong>-<strong>SIV</strong> Connecting måleren cable leveret som en komplet enhed,<br />

modulet <strong>HGP</strong>-HF-SD-conv. monteret i <strong>HGP</strong> flowmåleren.<br />

konverterer<br />

Before<br />

hurtigpuls<br />

installation,<br />

signalet<br />

the<br />

fra flowmåleren<br />

mains voltage<br />

til et<br />

to<br />

hurtigder<br />

kan anvendes electronics af displayenhed.<br />

as well as to the display unit must be<br />

the flow<br />

turned off.<br />

odulet leveret<br />

If the<br />

som<br />

<strong>HGP</strong><br />

løst<br />

<strong>SIV</strong><br />

tilbehør<br />

<strong>meter</strong><br />

(se<br />

is delivered<br />

fig 3) gøres<br />

as<br />

følgende:<br />

a complete unit<br />

t monteres<br />

the<br />

på<br />

insertion<br />

stikket i måleren,<br />

module<br />

se<br />

is already<br />

tegning.<br />

installed<br />

Sørg for,<br />

in<br />

at<br />

the<br />

alle<br />

<strong>HGP</strong><br />

ads i stikket. Den nye skillebøjle monteres i kassen i stedet<br />

flow <strong>meter</strong>. The insertion module transforms the<br />

terende, og det 2-polede stik monteres på M12 i måleren.<br />

fast pulse signal from the flow <strong>meter</strong> into a fast<br />

pulse signal usable for the display unit.<br />

Fig. <br />

3 Insertion module with<br />

division clamp<br />

If the insertion module comes as a separate item<br />

the following guidelines must be observed: The insertion module is mounted on<br />

the connector M52, see drawing. Pay attention when mounting the insertion module<br />

and make sure that all pins are placed correctly in the connector. The enclosed<br />

division clamp is installed instead of the existing one and finally the 2-poled<br />

connector is mounted.<br />

<strong>HGP</strong> electronics<br />

M57<br />

1<br />

n mellem <strong>HGP</strong> flowelektronik og displayenhed sker ved anvendelse af det medfølgende 4-leder<br />

rbindes i flowelektronikkens terminaler A1, A2, B1 og B2 som vist i fig 4. Det hvide stik monteres<br />

i displayenheden, og ledning og gummimembran <strong>HGP</strong> HP-SD Conv. trykkes på plads i aflastningen.<br />

M57 USB<br />

<br />

<br />

M12<br />

inaler Ledningsfarve, tegning Ledningsfarve<br />

1<br />

M57-stik (<strong>HGP</strong>-<strong>SIV</strong>) Signal<br />

A1 A2<br />

B1 B2<br />

Rød Rød 5 +5V<br />

Sort Sort 1 GND<br />

Gul Gul 4 Data<br />

Grøn Grøn 2 Clock<br />

ing af måleren<br />

<strong>HGP</strong> HP-SD Conv.<br />

g tilsluttes til begge enheder, og måleren vil straks begynde at registrere, hvis 1 der Blacker vandflow.<br />

Green<br />

er ikke skade, såfremt der ikke er vand på anlægget, men kan, hvis flowsensoren ikke er helt<br />

Yellow<br />

gistrere et tilfældigt flow.<br />

1<br />

Red<br />

Red<br />

M12<br />

Black<br />

odulet er der i øverste højre hjørne to lysdioder til indikation af signal. Grøn diode indikerer mod-<br />

Yellow<br />

nal fra <strong>HGP</strong>, og når der er flow,<br />

Green<br />

A1 blinker A2 dioden. Hvis den ikke blinker, kan det skyldes manglen-<br />

B1 B2<br />

at stikket er faldet af eller er vendt forkert.<br />

M57<br />

dikerer at der sendes data til Beregningsenheden. Den blinker for hvert 1,6 sekund, og hvis den<br />

undersøges det om stikket på M57 er korrekt monteret, samt forbindelserne A1, A2, B1, B2 er i<br />

ema og skitser.<br />

7<br />

er tilsluttet, og der løber vand gennem flowsensoren blinker en firkant i display i takt med vand-


Connection between the <strong>HGP</strong> flow electronics and the display unit takes place using<br />

the enclosed 4-poled cable which is connected in the terminals A1, A2, B1 and B2 of<br />

the flow electronics as shown on the drawing. The white connector is mounted on connector<br />

M57 of the display unit and the cable and rubber membrane are pressed to fit<br />

at the strain relief.<br />

<strong>HGP</strong><br />

terminals<br />

Wire colour<br />

M57 pin no.<br />

(<strong>HGP</strong>-<strong>SIV</strong>)<br />

Signal<br />

A1 Red 5 +5V<br />

A2 Black 1 GND<br />

B1 Yellow 4 Data<br />

B2 Green 2 Clock<br />

Putting the <strong>meter</strong> into operation<br />

Mains voltage is connected to both units and the <strong>meter</strong>s starts registration at once. The<br />

<strong>meter</strong> does not sustain damage if there is no water in the system, but it may register a<br />

random flow in case the flow sensor is not completely filled with water.<br />

In the upper right corner of the PCB are two lightemitting diodes (LEDs) for indication<br />

of signals. The green LED indicates received flow signal from <strong>HGP</strong> an when you have<br />

flow the LED flashes. If it does not flash it could be due to lack of flow, the connector<br />

has fallen out or has been reversed.<br />

The red LED indicates that data is being sent to the calculation unit. It flashes every 1.6<br />

seconds and if it does not flash it is advised to check if the connector M57 is installed<br />

correctly and that the connections A1, A2, B1 and B2 are working correctly. See table<br />

and drawings.<br />

When the <strong>meter</strong> is connected and water is running through the flow sensor a square in<br />

the display is flashing concurrently with the water pulses.<br />

Attention: The <strong>meter</strong>’s counter cannot be zeroed after delivery.<br />

8


Specification of Output Pulses:<br />

Pulse output for volume and energy<br />

The open collector pulse out is power supplied with load resistance R, whic<br />

The open collector pulse out is power supplied with load resistance R, which is dimensioned<br />

according to table<br />

table below.<br />

below.<br />

Setting of external + V − 5.1 V<br />

voltage supply R =<br />

5mA<br />

(from <strong>meter</strong>: 5 VDC) <br />

+V R for I=5 mA <br />

5 700 Ω Ω<br />

<br />

10 1,7 k Ω Ω <br />

15 2,7 k Ω Ω <br />

<br />

20 3,7 k Ω Ω<br />

Ω<br />

24 4,5 k Ω<br />

lied with load resistance R, which is dimensioned Ω according to<br />

28 5,3 k Ω<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

V5.1<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Insertion og communication module<br />

A communication module RS262, M-Bus or LON is plugged into the display<br />

nected to the terminals A1+B1 and A2+B2, [5] and [6] in fig 2.<br />

+<br />

Connection of external <strong>meter</strong>s with pulse outlet<br />

NB only valid for <strong>meter</strong>s, which has been programmed for connection<br />

The <strong>meter</strong> accepts active as well as passive signal source. The most comm<br />

<br />

which are connected to the terminals AUX 1 or AUX 2 and the switch in pos<br />

Fig. 5 Example of connection for volume pulse output with internal 5V<br />

fig. 6. <br />

<br />

Insertion og<br />

Connection<br />

communication<br />

of <strong>meter</strong>s<br />

module<br />

with active signal source is done as illustrated in pictu<br />

position OFF.<br />

A communication module RS262, M-Bus or LON is plugged into the display unit, and<br />

the signal cable Each is connected of the 2 input to the AUX1 terminals and A1+B1 AUX2 and can A2+B2. be set separately. Please note th<br />

r LON is plugged into the display unit, and the signal cable is con-<br />

Connection of external <strong>meter</strong>s with pulse outlet<br />

, [5] and [6] in fig 2.<br />

(only valid for <strong>meter</strong>s, which has been programmed for connection of external <strong>meter</strong>s)<br />

The <strong>meter</strong> accepts active as well as passive signal source. The most common is passive<br />

<br />

signal source, which are connected to the terminals AUX 1 or AUX 2 and the switch in<br />

pulse outlet<br />

position ON as shown in picture B, fig. 6.<br />

n programmed for connection of external <strong>meter</strong>s.<br />

e signal source. Connection The of most <strong>meter</strong>s common with active is signal passive source signal is done source, as illustrated in picture B, fig. 6 <br />

with the switch in position OFF.<br />

1 or AUX 2 and the switch in position ON as shown in picture B,<br />

<br />

Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity, <br />

<br />

see fig. 6.<br />

<br />

<br />

urce is done as illustrated in picture B, fig. 6 with the switch in<br />

<br />

e set separately. Please note the polarity, see fig. 6.<br />

9


Connection of <strong>meter</strong>s with active signal source is done as illustrated in picture B, fig. 6 with the switch in<br />

position OFF.<br />

Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity, see fig. 6.<br />

<br />

+V on<br />

<br />

GND (0V)<br />

<br />

<br />

<br />

Input-specifikation<br />

<br />

<br />

+ -<br />

Minus<br />

Von<br />

V<br />

>2,5 V<br />

on<br />

>2,5 V<br />

Voff 50 ms<br />

<br />

A. Aktiv signalkälla B. Passiv signalkälla<br />

<br />

Kontakter 1 & 2: OFF<br />

Kontakter 1 & 2: ON Fig. 3 Anslutning av externa mätare<br />

Galvaniskt A. Active åtskilt signal source B. Potential-free Ej galvaniskt switch-connection<br />

åtskilt<br />

<br />

Switch 1 & 2: OFF<br />

Switch 1 & 2: ON<br />

Galvanic separated NOT galvanic separated<br />

<br />

Sealing<br />

Vesterlundvej 14 DK-2730 Herlev Denmark Tel:+45 7777 7000 Fax: +45 7777 7001<br />

E-mail: brunata@brunata.com Internet: www.brunata.com<br />

<br />

V off t on t off<br />

Fig. 6 Connection of external <strong>meter</strong>s<br />

The flow electronic unit is from the factory sealed through the transparent lid and<br />

the screw allowing access to the terminals. After mounting and connecting the unit the<br />

black lid is screwed on and the unit can be sealed using sealing wire and a seal.<br />

The display unit is sealed electronically when delivered. The box is closed and sealed<br />

with <strong>Brunata</strong> special seal made of plastic, which is pushed into the narrow hole on the<br />

bottom of the box. The seal can be removed with a screwdriver. The broken piece of<br />

the seal is to be pushed into the box with the screwdriver and hereafter the box can be<br />

opened. Alternatively the box can be closed with the enclosed screw and sealed with<br />

thread through the hole next to the screw for the lid.<br />

<br />

energi-IV-BV-DK4/08.05.2006 Copyright © <strong>Brunata</strong> a/s 2006 Sida 4<br />

<strong>Brunata</strong> a/s • Kapplöpningsg. 14 • Box 5066 • S-250 05 Helsingborg • Sverige • Tel:+46 (0)42-13 37 59<br />

Fax: +46 (0)42-18 74 65 • E-mail: brunata@brunata.se • Internet: www.brunata.se<br />

10


Operating manual<br />

perating the <strong>meter</strong><br />

he menu of The the <strong>meter</strong> menu is of structured the <strong>meter</strong> in is 3-4 structured menus, and in 3-4 you navigate menus, and from you one navigate display to from another one using display the<br />

ush button on to another display using unit. the The push following button illustration the shows display the unit. standard The following menu structure illustration a <strong>Brunata</strong> shows<br />

G volume <strong>meter</strong> the standard menu structure on a <strong>Brunata</strong> HG volume <strong>meter</strong><br />

3)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

1)<br />

1)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

<br />

<br />

<br />

<br />

<br />

<br />

1)<br />

1)<br />

2)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Remarks<br />

1) Only in <strong>meter</strong> programmed for pulse input from external <strong>meter</strong>s<br />

emarks 2) Only in <strong>meter</strong> type -178 programmed for tariff functions<br />

1) Only 3) in <strong>meter</strong> File menu programmed is included for pulse only if input <strong>meter</strong> from is external programmed <strong>meter</strong>s for storage of data<br />

2) Only 4) in <strong>meter</strong> Only in programmed <strong>meter</strong> programmed for remote for reading remote reading<br />

3) Only in <strong>meter</strong> type -178 programmed for tariff functions<br />

4) File menu is included only if <strong>meter</strong> is programmed for storage of data<br />

11


Operating the <strong>meter</strong><br />

Introduction<br />

The <strong>meter</strong> is operated using the push button on the<br />

front of the electronic unit. Pressing once you step<br />

down in the actual menu you are in. By pressing<br />

the button in a few seconds, you can step from one<br />

menu to the next.<br />

Except for the User Menu the No. of the actual<br />

menu is shown in the display.<br />

Push<br />

button<br />

In case the <strong>meter</strong> is delivered with Storage Menu, the <strong>meter</strong> read itself and stores data<br />

as default on the 1st each month or at an optional selected date, see the order confirmation<br />

or consult the Service Menu. Until the first date occur the menu will be empty,<br />

displaying _ _._ _._ _._ _<br />

Peak values are registered in the period from the 1st in actual month. Values are reset<br />

(zeroed) at each turn of the month.<br />

With <strong>meter</strong>s supplied with module for remote reading, the user himself in the User<br />

Menu can check the time where the <strong>meter</strong> has been read. The communication address<br />

of the <strong>meter</strong> appears in the Service Menu.<br />

Normal operation – User menu<br />

By pushing the button once you will see the accumulated volume in the display (m3).<br />

If the <strong>meter</strong> is sup-plied with display light, pushing the button activates this function.<br />

Pushing once again the display will change to different pictures (see illustration).<br />

When the pushbutton has not been activated for approx. 1 minute the display will automatically<br />

return to accumulated volume (m3) and the light (if delivered) will turn off.<br />

Advanced operation – all menus<br />

When holding down the button for a short while, the display will change from one<br />

menu to the next. The menu reached is indicated in the upper part of the display (except<br />

Menu 1). The order of the menus is there-fore: [none], 2 ,3 and 4.<br />

When you reach the needed menu, release the pushbutton and the menu is now activated.<br />

By pushing once the different display pictures will show (as mentioned above).<br />

Display pictures containing peak flow will automatically alternate between peak value<br />

and date/time of regis-tration.<br />

For <strong>meter</strong>s delivered with tariff function the consumption is displayed in Tariff volume<br />

$, according to the criteria’s selected. The selected criteria can be seen in the service<br />

menu.<br />

12


Stored data menu<br />

If the <strong>meter</strong> is programmed for storage of data, in menu 3 you find data stored for 24<br />

accounting periods, and you can step through the different periods by pressing the button<br />

quickly twice. The date and time when the data has been stored is shown as first<br />

display in each accounting period. The first period showed are the most recent. You<br />

can step through the information stored by pressing the button once. By pressing the<br />

button quickly twice you step to the next period, and after having reached the latest<br />

reading (register 24) you will again see the most recent readings.<br />

Information and error codes<br />

Should an error occur in the <strong>meter</strong>, the display will be flashing ”Error” followed by one<br />

of following error codes:<br />

1. Interruption of power supply. The information is logged in the error register, and<br />

not showed in the display.<br />

2. Not used for volume <strong>meter</strong>s<br />

3. Not used for volume <strong>meter</strong>s<br />

4. Not used for volume <strong>meter</strong>s<br />

5. Low voltage in back-up battery [V Bat<br />

< V Treshold<br />

].<br />

6. Short circuit of magnet coil in the flowsensor [Coil current exceeds limit value for<br />

more than 8 sec].<br />

7. Error in the programming of the <strong>meter</strong> [RAM not initialised].<br />

8. Not used for volume <strong>meter</strong>s<br />

9. Wrong time/date in the <strong>meter</strong> (see Service Menu) – clock must be adjusted.<br />

In case of error the <strong>meter</strong> automatically will registers when (date and time) the error has<br />

occurred and also the accumulated error time.<br />

When two errors occur at the same time, both codes are shown. Example: Error code 71<br />

indicates error in the programming, and interruption of power supply.<br />

At code no. 6 the error message is shown in the display as long as the error occurs. The<br />

hours with error are registered in the register for Accumulated error hours. If the power<br />

supply is terminated, the time without power is registered in the error hours register.<br />

At code 5, 7 and 9 the error message is shown in the display as long as the error occurs,<br />

but will not be reg-istered in the register for Accumulated error hours.<br />

By interruption of the power supply the display will be blank. When the power is reestablished<br />

the <strong>meter</strong> will immediately start registering again.<br />

By error code 5, low battery-supply, the <strong>meter</strong> will continue the normal registration as<br />

long as it is powered but the battery must be replaced as soon as possible.<br />

13


By error code 9, the <strong>meter</strong> has been without power supply, and battery-supply. The <strong>meter</strong><br />

will continue the normal registration when power is restored, but the internal clock<br />

should be adjusted. Please contact nears <strong>Brunata</strong> service department.<br />

In case of questions, you are always welcome to contact your local <strong>Brunata</strong> service<br />

department, or send an e-mail to service@brunata.dk.<br />

14


Notes<br />

15


Notes<br />

<strong>Brunata</strong> a/s · Vesterlundvej 14 · DK-2730 Herlev · tel. +45 77 77 70 00<br />

fax +45 77 77 70 01 · www.brunata.com · brunata@brunata.com<br />

UK-QB 10.1487/30.05.2008<br />

16

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!