<strong>Weishaupt</strong> <strong>gas</strong> <strong>burners</strong><br />
<strong>Sizes</strong> <strong>30</strong> <strong>to</strong> <strong>70</strong><br />
<strong>Version</strong> <strong>LN</strong> / 1<strong>LN</strong> (Low NO x )<br />
2/2003 CA
Description<br />
<strong>Weishaupt</strong> <strong>burners</strong> of sizes <strong>30</strong> <strong>to</strong> <strong>70</strong> were specially designed and developed for<br />
industrial applications. The Monoblock-Burners are characterized with multiple<br />
excellent features such as:<br />
• Big firing range and wide area of applications<br />
• Stable air fan performance – excellent combustion characteristics<br />
• Burner casing can be swung opened<br />
• Easy <strong>to</strong> install, setup and maintenance<br />
• Air damper closed off during burner s<strong>to</strong>p<br />
• Compliance with the most stringent directives and emission limits<br />
Typical Low NO x flame pattern<br />
Control<br />
Control of air and fuel is performed according<br />
<strong>to</strong> the fuel type, burner size and<br />
requirement:<br />
• Sliding two stage<br />
On sliding two stage regulation, the<br />
low fire and high fire points are assigned<br />
within the control range. The<br />
burner slides depending on heat re<br />
quirement between both operating<br />
points. There is no sudden increase or<br />
decrease of supplied fuel amount.<br />
• Modulating<br />
Modulating <strong>burners</strong> operate according<br />
<strong>to</strong> the heat requirement at any operating<br />
point within the control range.<br />
Reduced capacity at start-up<br />
The <strong>burners</strong> start at ignition position, set<br />
via the <strong>gas</strong> butterfly (<strong>LN</strong>) or an additional<br />
pilot line (1<strong>LN</strong>). In this way only a small<br />
amount of <strong>gas</strong> flows in<strong>to</strong> the combustion<br />
chamber. After a short delay the burner<br />
moves <strong>to</strong> low fire.<br />
Controlled shutdown from low fire<br />
Controlled shutdown of the burner is<br />
performed only at low fire. Sudden pressure<br />
surge in the <strong>gas</strong> supply line can be<br />
avoided.<br />
Gas train<br />
As standard, <strong>Weishaupt</strong> <strong>gas</strong> and dual<br />
fuel <strong>burners</strong> are always equipped with<br />
two main <strong>gas</strong> valves.<br />
Gas train can be built according <strong>to</strong> most<br />
applicable North American codes and<br />
standards.<br />
Digital combustion manager<br />
W-FM100 and W-FM200 combustion<br />
manager control all essential burner<br />
functions, e.g. fuel and air supply and<br />
moni<strong>to</strong>r the flame with digital precision.<br />
The target is optimization of operating<br />
conditions, maximization of economical<br />
aspect and minimizing the emissions.<br />
Thanks <strong>to</strong> the digital combustion technology,<br />
such optimization is available<br />
<strong>to</strong>day at reasonable cost. Expenses for<br />
installation and maintenance are even<br />
clearly lower than with conventional<br />
technologies. For example, a separate<br />
remote panel is no longer required for<br />
burner control. Furthermore, remote<br />
operation, remote diagnostic and remote<br />
moni<strong>to</strong>ring of the appliances are now<br />
realizable. This increases the safety and<br />
comfort for opera<strong>to</strong>r.<br />
Applications<br />
The <strong>burners</strong> can be used with heat<br />
exchanger such as heating boiler, steam<br />
boiler, air heater and for certain process<br />
applications. Due <strong>to</strong> the fact that the<br />
burner is capable of overcoming high<br />
combustion chamber pressure, they are<br />
most compatible with modern high performance<br />
boilers.<br />
Fuels<br />
The <strong>gas</strong> <strong>burners</strong> have been tested for<br />
operation with the following <strong>gas</strong>es:<br />
<strong>LN</strong> version:<br />
Natural Gas<br />
1<strong>LN</strong> version:<br />
Natural <strong>gas</strong><br />
Propane<br />
Installation location<br />
The <strong>burners</strong> are designed for indoor<br />
operation with temperature of 5F<br />
(–15°C) up <strong>to</strong> 100F (+40°C) and relative<br />
humidity of max. 80%<br />
Certification<br />
The <strong>burners</strong> are in compliance with most<br />
applicable European and North<br />
American standards<br />
Excellent service<br />
<strong>Weishaupt</strong> has a high density sales and<br />
service network all over the world. The<br />
cus<strong>to</strong>mer service is available every day<br />
around the clock. Optimum in house<br />
training conditions ensure high quality of<br />
service personnel.<br />
2
Variants<br />
Digital combustion manager<br />
(W-FM 100)<br />
Electronic ratio controller (RVW)<br />
with O 2 trim<br />
Mechanical linkage<br />
Digital combustion manager<br />
(W-FM 100)<br />
with modulating controller<br />
Electronic ratio controller (RVW)<br />
with speed control<br />
Digital combustion manager<br />
(W-FM 100)<br />
with modulating controller<br />
and speed control<br />
Digital combustion manager<br />
(W-FM 200)<br />
with modulating controller<br />
O2 trim and speed control<br />
Electronic ratio controller (RVW)<br />
with O 2 trim and<br />
speed control<br />
Standard<br />
Special version<br />
Capacity regulation<br />
Sliding two<br />
stage (ZM)<br />
HF G<br />
Modulating (ZM)<br />
HF G<br />
LF K<br />
LF K<br />
ZIP<br />
IP Z<br />
ON Ein<br />
OFF Aus<br />
ON Ein<br />
OFF Aus<br />
HF = High fire<br />
LF = Low fire<br />
IP=Ignition position<br />
Burner designation<br />
G 40/1 – B, Vers. ZM-1<strong>LN</strong><br />
LowNO x<br />
Sliding two stage or modulating<br />
Index for mixing head<br />
Code for capacity range<br />
Size<br />
Fuel: Gas<br />
3
The advantages of digital<br />
combustion management<br />
Control and Display Unit<br />
Digital combustion management<br />
means optimum combustion figures,<br />
continuous repeatability of setting<br />
values and ease of use.<br />
<strong>Weishaupt</strong> <strong>burners</strong> are equipped with<br />
electronic ratio controller and digital<br />
combustion management <strong>to</strong> satisfy the<br />
requirements of modern combustion<br />
technology, which demand a precise and<br />
continuously reproducible supply of fuel<br />
and combustion air. Only in this way<br />
optimal combustion figures can be<br />
ensured over extended periods of time.<br />
If required, the <strong>burners</strong> can also be<br />
equipped with O 2 trim* and variable<br />
speed control.<br />
Error free operation via AZL display<br />
and control unit<br />
Setting and control of the burner functions<br />
are achieved using a control and<br />
display unit, the AZL, which is equipped<br />
with an LCD display. The AZL is connected<br />
<strong>to</strong> the combustion manager via a<br />
safety bus system and can be positioned<br />
anywhere according <strong>to</strong> the user’s<br />
preferences within 325 ft. (100 m) distance<br />
from the burner.<br />
Flexible communication possibilities<br />
The integrated communication interface<br />
enables all necessary information and<br />
functions <strong>to</strong> be transmitted <strong>to</strong> a BMS<br />
system. If required, remote operation and<br />
remote diagnosis functions, which are<br />
accessible via modem, can be installed<br />
(e.g. oil/<strong>gas</strong> change-over, adjustment of<br />
setting values).<br />
Communication with external systems<br />
via BUS<br />
If data has <strong>to</strong> be exchanged between<br />
<strong>burners</strong> and other heating systems with<br />
PLC devices, the information can be<br />
accessible via eBUS or MODBUS<br />
communication system.<br />
Integration with building management<br />
For control and management functions,<br />
<strong>Weishaupt</strong> offers ProGraf NT - a<br />
software product that provides a real<br />
time solution <strong>to</strong> meet all requirements.<br />
The price advantage of the new<br />
technology<br />
With improved technology and ease of<br />
use, combustion plant is becoming even<br />
more economical than ever before.<br />
• No additional burner controls are<br />
required, since this function is already<br />
governed by the combustion manager.<br />
Fuses and burner mo<strong>to</strong>r starter are the<br />
only additional items required.<br />
• Less installation work means less<br />
errors: the <strong>burners</strong> are tested as a<br />
complete unit at the fac<strong>to</strong>ry.<br />
• If required, the W-FM 100 is available<br />
with an integrated modulating controller<br />
and variable speed module. No<br />
separate equipment is required. The<br />
modulating controller and variable<br />
speed module are included as standard<br />
with the W-FM 200.<br />
• Commissioning and service work<br />
takes less time. The initial presetting<br />
of the burner is carried out at the fac<strong>to</strong>ry.<br />
On site, only the site specific<br />
operating points have <strong>to</strong> be adjusted.<br />
• To facilitate O 2 trim, only an O 2 probe<br />
and O 2 module have <strong>to</strong> be installed<br />
and connected with the W-FM 200<br />
via the internal safety BUS.<br />
* In conjunction with the W-FM 200 combustion<br />
manager<br />
4
O 2 probe*<br />
O 2 module*<br />
Gas butterfly<br />
Stepping<br />
mo<strong>to</strong>rs<br />
Air damper<br />
Frequency<br />
converter<br />
Impulse sender<br />
CAN-Bus<br />
W-FM 200<br />
combustion manager<br />
CAN-Bus<br />
Control and<br />
Display Unit<br />
eBus/<br />
MODBUS<br />
BMS<br />
visualization<br />
ProGraf NT<br />
Example of O 2 trim and speed control with W-FM 200<br />
5
<strong>Version</strong>s <strong>LN</strong> and 1<strong>LN</strong> in comparison<br />
Main points in overview<br />
<strong>LN</strong> version<br />
The <strong>LN</strong> series has been proven <strong>to</strong> be successful for many years.<br />
Designed <strong>to</strong> operate with Natural Gas. The burner does not have<br />
separate pilot <strong>gas</strong> connection, since it can start directly with main<br />
<strong>gas</strong> valve.<br />
1<strong>LN</strong> version<br />
The need for Low NO x operation of dual fuel <strong>burners</strong> when firing<br />
on <strong>gas</strong> led <strong>to</strong> the development of a new type of mixing head.<br />
Due <strong>to</strong> the way the combustion air is distributed, which is<br />
different <strong>to</strong> <strong>LN</strong> <strong>burners</strong>, a separate <strong>gas</strong> pilot line is required. The<br />
capacity range is some 10 - 15% higher than the <strong>LN</strong> version, and<br />
the burner is also suitable and tested for use with Propane.<br />
• No separate pilot connection on the burner<br />
• Tested for Natural Gas<br />
• Capacity range up <strong>to</strong> 29,000 MBTU/h<br />
• Separate pilot connection on the burner<br />
• Tested for Natural Gas and Propane<br />
• Capacity range up <strong>to</strong> 34,000 MBTU/h<br />
Capacity ranges of <strong>LN</strong> and 1<strong>LN</strong> versions (MBTU/h)<br />
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 <strong>30</strong>,000 33,000 36,000<br />
G<strong>70</strong>/2-A, version <strong>LN</strong><br />
G<strong>70</strong>/2-A, version 1<strong>LN</strong><br />
Capacity range of G<strong>70</strong>/2-A as an example<br />
Emission figures for <strong>LN</strong> and 1<strong>LN</strong> versions<br />
[ppm]<br />
60<br />
50<br />
40<br />
<strong>30</strong><br />
20<br />
Example for Natural Gas operation<br />
NO x limit* with medium temperature < 2<strong>30</strong>F (110°C)<br />
* According <strong>to</strong> German TA-<br />
Luft regulation<br />
Notes and remarks<br />
Excellent emission values are achievable<br />
depending on the geometry of the<br />
combustion chamber, volume load and<br />
combustion system (3 pass or reverse<br />
flame).<br />
When stating information relating <strong>to</strong><br />
guaranteed values, certain conditions for<br />
measurement and evaluation must be<br />
taken in<strong>to</strong> account, such as combustion<br />
chamber loading, test <strong>to</strong>lerances,<br />
temperature, pressure, humidity.<br />
6<br />
10<br />
0<br />
NO x CO NO x CO<br />
<strong>LN</strong> <strong>Version</strong><br />
1<strong>LN</strong> <strong>Version</strong>
<strong>LN</strong> version mixing head<br />
1<strong>LN</strong> version mixing head<br />
7
<strong>LN</strong> version<br />
G<strong>70</strong>/2-A ZM <strong>LN</strong> <strong>gas</strong> burner<br />
Hinged flange for easy access <strong>to</strong> burner mixing chamber<br />
8
Gas burner selection<br />
Models G<strong>30</strong> and G40, <strong>LN</strong> version<br />
[“WC ] Burner model G<strong>30</strong>/2-A, vers. ZM-<strong>LN</strong><br />
Combustion head<br />
G<strong>30</strong>/2 - 3a - 190x60<br />
MBH Natural Gas 1,000 – 6,150<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC ] Burner model G40/1-B, vers. ZM-<strong>LN</strong><br />
Combustion head<br />
G<strong>30</strong>/2 - 3a - 190x60<br />
MBH Natural <strong>gas</strong> 1,365 – 7,1<strong>70</strong><br />
Combustion head “open”<br />
Combustion head “closed”<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong>/LPG<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000<br />
[“WC ] Burner model G40/2-A, vers. ZM-<strong>LN</strong><br />
Combustion head<br />
G<strong>30</strong>/2 - 3a - 210x60<br />
MBH Natural <strong>gas</strong> 1,<strong>70</strong>0 – 9,215<br />
Combustion head “open”<br />
Combustion head “closed”<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000<br />
Burner type <strong>Version</strong><br />
The capacity ranges shown correspond <strong>to</strong> the maximal values<br />
measured on idealized test flame tubes<br />
G<strong>30</strong>/2-A<br />
G40/1-B<br />
G40/2-A<br />
ZM-<strong>LN</strong><br />
ZM-<strong>LN</strong><br />
ZM-<strong>LN</strong><br />
The ratings given for sizes <strong>30</strong> <strong>to</strong> 50/2 are based on fuel with<br />
low calorific value, an air temperature of 68F (20°C) and an<br />
installation altitude of 1,640 ft. (500 m)<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltage from 208 - 600V, 60Hz.<br />
Other voltages and frequencies available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
9
Gas burner selection<br />
Model G50, <strong>LN</strong> version<br />
[“WC] Burner model G50/1-B, vers. ZM-<strong>LN</strong><br />
Combustion head G40/2 - 3a - 210x60<br />
MBH Natural <strong>gas</strong> 1,<strong>70</strong>0 – 10,250<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC] Burner model G50/2-A, vers. ZM-<strong>LN</strong><br />
Combustion head G50/2- 3a - 250x90<br />
MBH Natural <strong>gas</strong> 2,050 – 15,400<br />
Combustion head “open”<br />
Combustion head “closed”<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16.000<br />
Burner type<br />
G50/1-B<br />
G50/2-A<br />
<strong>Version</strong><br />
ZM-<strong>LN</strong><br />
ZM-<strong>LN</strong><br />
The capacity ranges shown correspond <strong>to</strong> the maximal values<br />
measured on idealized test flame tubes<br />
The ratings given for sizes <strong>30</strong> <strong>to</strong> 50/2 are based on fuel with<br />
low calorific value, an air temperature of 68F (20°C) and an<br />
installation altitude of 1,640 ft. (500 m)<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltage from 208 - 600V, 60Hz.<br />
Other voltages and frequencies available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
10
Gas burner selection<br />
Models G60 and G<strong>70</strong>, <strong>LN</strong> version<br />
[“WC] Burner model G60/2-A, vers. ZM-<strong>LN</strong><br />
Combustion head G60/2 - 3a - <strong>30</strong>0x100<br />
MBH Natural <strong>gas</strong> 2,1<strong>30</strong> – 19,800<br />
Combustion head “open”<br />
Combustion head “closed”<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000<br />
[“WC] Burner model G<strong>70</strong>/1-B, vers. ZM-<strong>LN</strong><br />
Combustion head G60/2 - 3a - <strong>30</strong>0x100<br />
MBH Natural <strong>gas</strong> 2,390 – 23,900<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC] Burner model G<strong>70</strong>/2-A, vers. ZM-<strong>LN</strong><br />
Combustion head G<strong>70</strong>/2 - 3a - 355x120<br />
MBH Natural Gas 2,7<strong>30</strong> – 29,000<br />
Combustion head “open”<br />
Combustion head “closed”<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 6,000 12,000 18,000 24,000 <strong>30</strong>,000 36,000<br />
Burner type<br />
G60/2-A<br />
G<strong>70</strong>/1-B<br />
G<strong>70</strong>/2-A<br />
<strong>Version</strong><br />
ZM-<strong>LN</strong><br />
ZM-<strong>LN</strong><br />
ZM-<strong>LN</strong><br />
The capacity ranges shown correspond <strong>to</strong> the maximal values<br />
measured on idealized test flame tubes<br />
The ratings given for sizes 60 and <strong>70</strong> are based on fuel with<br />
low calorific value, an air temperature of 68F (20°C) and an<br />
installation altitude of 0 ft. (0 m)<br />
Depending on the altitude of the installation, a reduction in<br />
capacity of approximately 1% for every 328 ft (100 m) above<br />
sea level should be taken in<strong>to</strong> account.<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltage from 208 - 600V, 60Hz.<br />
Other voltages and frequencies available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
11
1<strong>LN</strong> version<br />
G<strong>70</strong>/2-A ZM 1<strong>LN</strong> <strong>gas</strong> burner<br />
Burner with integrated Control and Display Unit<br />
12
Gas burner selection<br />
Models G<strong>30</strong> and G40, 1<strong>LN</strong> version<br />
[“WC ] Burner model G<strong>30</strong>/2-A, vers. ZM-1<strong>LN</strong><br />
Combustion head<br />
G<strong>30</strong>/2-<strong>LN</strong> 190x35<br />
MBH Natural Gas 1,000 – 6,400<br />
Propane 1,000 – 6,400<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC ] Burner model G40/1-B, vers. ZM-1<strong>LN</strong><br />
Combustion head<br />
G<strong>30</strong>/2-<strong>LN</strong> 190x35<br />
MBH Natural <strong>gas</strong> 1,5<strong>30</strong> – 7,500<br />
Propane 1,5<strong>30</strong> – 7,500<br />
Combustion head “open”<br />
Combustion head “closed”<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong>/LPG<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong>/LPG<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000<br />
[“WC ] Burner model G40/2-A, vers. ZM-1<strong>LN</strong><br />
Combustion head<br />
G40/2-<strong>LN</strong> 217x35<br />
MBH Natural <strong>gas</strong> 1,<strong>70</strong>0 – 10,500<br />
Propane 1,<strong>70</strong>0 – 10,500<br />
Combustion head “open”<br />
Combustion head “closed”<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong>/LPG<br />
-1<br />
[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000<br />
Burner type<br />
G<strong>30</strong>/2-A<br />
G40/1-B<br />
G40/2-A<br />
<strong>Version</strong><br />
ZM-1<strong>LN</strong><br />
ZM-1<strong>LN</strong><br />
ZM-1<strong>LN</strong><br />
The capacity ranges shown correspond <strong>to</strong> the maximal values<br />
measured on idealized test flame tubes<br />
The ratings given are based on fuel with low calorific value<br />
and an installation altitude of 0 ft. (0 m)<br />
Depending on the altitude of the installation, a reduction in<br />
capacity of approximately 1% for every 328 ft. (100 m) above<br />
sea level should be taken in<strong>to</strong> account.<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltage from 208 - 600V, 60Hz.<br />
Other voltages and frequencies available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
13
Gas burner selection<br />
Models G50 and G<strong>70</strong>, 1<strong>LN</strong> version<br />
[“WC] Burner model G50/1-B, vers. ZM-1<strong>LN</strong><br />
Combustion head G40/2-<strong>LN</strong> 217x35<br />
MBH Natural <strong>gas</strong> 1,<strong>70</strong>0 – 11,600<br />
Propane 1,<strong>70</strong>0 – 11,600<br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC] Burner model G<strong>70</strong>/1-B, vers. ZM-1<strong>LN</strong><br />
Combustion head G60/2- 1<strong>LN</strong> <strong>30</strong>0x75<br />
MBH Natural <strong>gas</strong> 2,7<strong>30</strong> – 24,915<br />
Propane 3,410 – 24,915<br />
Combustion head “open”<br />
Combustion head “closed”<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong>/LPG<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000<br />
Nat <strong>gas</strong><br />
Propane<br />
[“WC ] Burner model G50/2-A, vers. ZM-1<strong>LN</strong><br />
Combustion head G50/2-<strong>LN</strong> 260x40<br />
MBH Natural Gas 2,050 – 16,7<strong>30</strong><br />
Propane 2,7<strong>30</strong> – 16,7<strong>30</strong><br />
Combustion head “open”<br />
Combustion head “closed”<br />
[“WC] Burner model G<strong>70</strong>/2-A, vers. ZM-1<strong>LN</strong><br />
Combustion head G<strong>70</strong>/2-1<strong>LN</strong> 365x85<br />
MBH Natural Gas 3,400 – 34,1<strong>30</strong><br />
Propane 4,750 – 34,1<strong>30</strong><br />
Combustion head “open”<br />
Combustion head “closed”<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Nat <strong>gas</strong><br />
Propane<br />
-1<br />
[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
-1<br />
[MBH] 0 6,000 12,000 18,000 24,000 <strong>30</strong>,000 36,000<br />
Nat <strong>gas</strong><br />
Propane<br />
Burner type<br />
G50/1-B<br />
G50/2-A<br />
G<strong>70</strong>/1-B<br />
G<strong>70</strong>/2-A<br />
<strong>Version</strong><br />
ZM-1<strong>LN</strong><br />
ZM-1<strong>LN</strong><br />
ZM-1<strong>LN</strong><br />
ZM-1<strong>LN</strong><br />
The capacity ranges shown correspond <strong>to</strong> the maximal values<br />
measured on idealized test flame tubes<br />
The ratings given are based on fuel with low calorific value<br />
and an installation altitude of 0 ft. (0 m)<br />
Depending on the altitude of the installation, a reduction in<br />
capacity of approximately 1% for every 328 ft. (100 m) above<br />
sea level should be taken in<strong>to</strong> account.<br />
Voltages and frequencies:<br />
As standard, the <strong>burners</strong> are suitable for three phase alternating<br />
current available with various voltage from 208 - 600V, 60Hz.<br />
Other voltages and frequencies available on request.<br />
Standard burner mo<strong>to</strong>r:<br />
Isolation class F, IP 54 protection<br />
14
Scope of delivery<br />
Gas train layout<br />
Description G<strong>30</strong> G40 G50 G60 G<strong>70</strong><br />
<strong>LN</strong> 1<strong>LN</strong> <strong>LN</strong> 1<strong>LN</strong> <strong>LN</strong> 1<strong>LN</strong> <strong>LN</strong> <strong>LN</strong> 1<strong>LN</strong><br />
Burner housing, hinged flange, housing cover, <strong>Weishaupt</strong> ● ● ● ● ● ● ● ● ●<br />
burner mo<strong>to</strong>r, air regulation housing, fan wheel, combustion<br />
head, ignition unit, ignition cable, ignition electrodes,<br />
combustion manager with control unit, flame sensor, flange<br />
<strong>gas</strong>ket, limit switch on hinged flange, fixing bolts<br />
W-FM 100 combustion manager ● ● ● ● ● ● ● ● ●<br />
Double main <strong>gas</strong> valves ● ● ● ● ● ● ● ● ●<br />
1<strong>LN</strong> version: separate pilot <strong>gas</strong> connection ● ● ● ●<br />
Gas butterfly valve ● ● ● ● ● ● ● ● ●<br />
Valve connection piece ● ● ● ● ● ● ● ● ●<br />
Air pressure switch ● ● ● ● ● ● ● ● ●<br />
Gas pressure switch ● ● ● ● ● ● ● ● ●<br />
Adjustable regulating sleeve in the mixing head ● ● ●<br />
Adjustable flame tube in the mixing head ● ● ● ● ● ●<br />
Servomo<strong>to</strong>r for fuel/air ratio<br />
regulation via W-FM 100<br />
Servomo<strong>to</strong>r for air damper ● ● ● ● ● ● ● ● ●<br />
Servomo<strong>to</strong>r for <strong>gas</strong> butterfly ● ● ● ● ● ● ● ● ●<br />
<strong>LN</strong> version:<br />
6<br />
7<br />
4b<br />
4b<br />
9<br />
Legend<br />
1<strong>LN</strong> version:<br />
6<br />
7<br />
4b<br />
4b<br />
9<br />
P<br />
P<br />
1 Isolating valve<br />
2 Main <strong>gas</strong> pressure regula<strong>to</strong>r<br />
3 Low <strong>gas</strong> pressure switch<br />
4 Double main <strong>gas</strong> valves<br />
4b Double pilot <strong>gas</strong> valves<br />
5 High <strong>gas</strong> pressure switch<br />
6 Isolating valve (pilot)<br />
7 Pilot <strong>gas</strong> pressure regula<strong>to</strong>r<br />
8 Gas butterfly valve<br />
9 Burner<br />
P<br />
P<br />
2<br />
3 4<br />
1<br />
5<br />
8<br />
2<br />
3 4<br />
1<br />
5<br />
8<br />
15
Special equipment<br />
Technical data<br />
Special equipment versions <strong>LN</strong> and 1<strong>LN</strong> Size <strong>30</strong> Size 40 Size 50 Size 60 1 Size <strong>70</strong><br />
Vertically firing burner version standard standard standard standard standard<br />
Air intake flange for connection of an air duct 280 003 47 280 001 68 280 000 92 280 000 38 280 000 13<br />
Combustion head extension by 6” (150 mm), types ../1-B – 290 003 22 290 006 <strong>30</strong> – 290 007 <strong>70</strong><br />
<strong>Version</strong> <strong>LN</strong> by 12” (<strong>30</strong>0 mm), types ../1-B – 290 003 23 290 006 31 – 290 007 71<br />
by 6” (150 mm), types ../2-A 290 003 22 290 006 <strong>30</strong> 290 007 08 290 007 <strong>70</strong> 290 007 88<br />
by 12” (<strong>30</strong>0 mm), types ../2-A 290 003 23 290 006 31 290 007 09 290 007 71 290 007 89<br />
Combustion head extension by 6” (150 mm), types ../1-B – * * – 290 010 76<br />
<strong>Version</strong> 1<strong>LN</strong> by 12” (<strong>30</strong>0 mm), types ../1-B – * * – 290 010 77<br />
by 6” (150 mm), types ../2-A 290 011 10 * 290 009 38 – 290 010 95<br />
by 12” (<strong>30</strong>0 mm), types ../2-A – * * – *<br />
W-FM 100 with internal modulating controller 290 010 60 290 010 60 290 010 60 290 010 60 290 010 60<br />
Burner controller<br />
Mechanical linkage with LFL in lieu of W-FM 100 -price reduction- 290 011 02 290 011 02 290 011 02 290 011 02 290 011 02<br />
Mechanical linkage with LGK in lieu of W-FM 100 -price reduction- 290 011 09 290 011 09 290 011 09 290 011 09 290 011 09<br />
Solenoid valve for air pressure switch test<br />
for continuous run fan or post purge 290 004 29 290 004 29 290 000 31 290 000 31 290 000 31<br />
* Additional price on request<br />
Technical data G<strong>30</strong>/2-A G40/1-B G40/2-A G50/1-B<br />
Burner mo<strong>to</strong>r Model D112/110-2 D112/140-2 D112/140-2 D132/1<strong>70</strong>-2a<br />
Mo<strong>to</strong>r rating HP (kW) 6.7 (5.0) 10.5 (7.8) 10.5 (7.8) 14 (10.5)<br />
Full Load Amps (FLA) at 460 V A 8.2 11.5 11.5 17.2<br />
Speed (60 Hz) rpm 3510 3450 3450 3500<br />
Fan wheel colour / Ø red / 248 x 100 red / 275 x 100 red / 275 x 100 red / 3<strong>30</strong> x 100<br />
Ignition unit Model W-ZG 02/2 W-ZG 02/2 W-ZG 02/2 W-ZG 02/2<br />
Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100<br />
Servomo<strong>to</strong>r Model SQM 45 SQM 45 SQM 45 SQM 45<br />
Weight lbs (kg) 265 (120) 287 (1<strong>30</strong>) 287 (1<strong>30</strong>) 4<strong>30</strong> (195)<br />
Technical data G50/2-A G60/2-A 1 G<strong>70</strong>/1-B G<strong>70</strong>/2-A<br />
Burner mo<strong>to</strong>r Model D132/1<strong>70</strong>-2 D132/1<strong>70</strong>-2 D160/215-2a 2 D160/215-2<br />
Mo<strong>to</strong>r rating HP (kW) 20 (15) 20 (15) 21.5 (16) 29.5 (22)<br />
Full Load Amps (FLA) at 460 V A 23.2 23.2 29 36<br />
Speed (60 Hz) rpm 3500 3500 3520 3500<br />
Fan wheel colour / Ø red / 3<strong>30</strong> x 100 red / 465 x 103 green / 5<strong>30</strong> x120 green / 5<strong>30</strong> x 120<br />
Ignition unit Model W-ZG 02/2 W-ZG 02/2 W-ZG 02/2 W-ZG 02/2<br />
Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100<br />
Servomo<strong>to</strong>r Model SQM 45 SQM 45 SQM 45 SQM 45<br />
Weight lbs (kg) 440 (200) 640 (290) 860 (390) 860 (390)<br />
1 <strong>LN</strong> version only<br />
2 1<strong>LN</strong> version is equipped with burner mo<strong>to</strong>r: D160/215-2B, 25HP (19kW), FLA: 32.2A at 460V and 3400 rpm<br />
16
Burner dimensions<br />
sizes <strong>30</strong> <strong>to</strong> 50, <strong>LN</strong> version<br />
Flange connection<br />
Drilling dimensions of<br />
the burner plate<br />
Size<br />
<strong>30</strong>/2-A<br />
40/1-B<br />
40/2-A<br />
50/1-B<br />
50/2-A<br />
Dimensions in inches (mm)<br />
l1 l2 l3 l5 l6 l7 l8 l9 l10 b1 b2 b3 b4 b5<br />
42.6 9.6 10.1 0.3 13.9 11.8 2.3 9.4 4.8 27.6 14.6 8.2 16.5 13.0<br />
(1083) (245) (257) (8) (354) (<strong>30</strong>0) (58) (238) (123) (<strong>70</strong>0) (371) (208) (418) ( 3<strong>30</strong>)<br />
44.4 10.6 10.1 0.3 16.3 12.6 2.3 9.4 4.8 29.7 15.8 9.5 18.2 13.0<br />
(1128) (2<strong>70</strong>) (257) (8) (414) (320) (58) (238) (123) (755) (401) (242) (462) ( 3<strong>30</strong>)<br />
45.2 10.6 14.4 0.3 16.3 13.4 2.6 10.2 5.2 29.7 15.8 9.5 18.2 14.6<br />
(1148) (2<strong>70</strong>) (367) (8) (414) (340) (67) (258) (133) (755) (401) (242) (462) ( 3<strong>70</strong>)<br />
47.0 12.4 14.4 0.3 16.6 14.3 2.6 10.2 5.2 32.3 17.3 10.9 21.7 14.6<br />
(1195) (315) (367) (8) (422) (363) (67) (258) (133) (820) (440) (277) (550) ( 3<strong>70</strong>)<br />
49.0 12.4 15.2 0.3 16.6 16.3 2.8 12.1 6.2 33.9 18.3 10.9 21.7 16.9<br />
(1245) (315) (387) (8) (422) (413) (72) (<strong>30</strong>8) (158) (860) (465) (277) (550) ( 4<strong>30</strong>)<br />
<strong>30</strong>/2-A<br />
40/1-B<br />
40/2-A<br />
50/1-B<br />
h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8 r1 r2<br />
22.5 8.1 16.0 8.1 13.0 11.0 10.2 – 8.6 M12 14.2 11.2 DN50 33.1 35.0<br />
(572) (207) (407) (207) ( 3<strong>30</strong>) (280) (260) – (218) M12 (360) (285) DN50 (840) (890)<br />
23.9 8.3 16.6 8.1 13.0 11.0 10.2 – 8.6 M12 14.2 11.2 DN50 35.2 38.2<br />
(607) (211) (422) (207) ( 3<strong>30</strong>) (280) (260) – (218) M12 (360) (285) DN50 (895) (9<strong>70</strong>)<br />
23.9 8.3 16.6 8.9 14.6 12.6 11.7 – 8.6 M12 15.7 12.8 DN65 35.2 38.2<br />
(607) (211) (422) (227) ( 3<strong>70</strong>) (320) (296) – (218) M12 (400) (325) DN65 (895) (9<strong>70</strong>)<br />
28.7 10.4 20.2 8.9 14.6 12.6 11.7 – 10.2 M12 15.7 12.8 DN65 41.7 39.4<br />
(7<strong>30</strong>) (263) (513) (227) ( 3<strong>70</strong>) (320) (296) – (258) M12 (400) (325) DN65 (1060) (1000)<br />
28.7 10.4 20.2 10.1 16.9 15.0 13.8 – 10.2 M16 18.9 15.4 DN80 41.7 40.4<br />
50/2-A<br />
(7<strong>30</strong>) (263) (513) (257) ( 4<strong>30</strong>) (380) (350) – (258) M16 (480) (390) DN80 (1060) (1025)<br />
All measurements are approximate. <strong>Weishaupt</strong> reserves the right <strong>to</strong> make alterations in light of future developments.<br />
17
Burner dimensions<br />
sizes 60 and <strong>70</strong>, <strong>LN</strong> version<br />
Flange connection<br />
Drilling dimensions of<br />
the burner plate<br />
Size<br />
60/2-A<br />
<strong>70</strong>/1-B<br />
<strong>70</strong>/2-A<br />
60/2-A<br />
<strong>70</strong>/1-B<br />
<strong>70</strong>/2-A<br />
Dimensions in inches (mm)<br />
l1 l2 l3 l5 l6 l7 l8 l9 l10 b1 b2 b3 b4 b5<br />
58.2 15.9 17.0 0.3 20.0 17.3 3.5 13.7 7.0 38.6 19.2 11.0 26.4 20.5<br />
(1478) (405) (432) (8) (508) (440) (89) (348) (178) (980) (487) (280) (6<strong>70</strong>) ( 520)<br />
64.9 19.0 17.0 0.3 24.2 20.1 3.5 13.7 7.0 44.3 21.9 13.4 29.9 20.5<br />
(1648) (483) (432) (8) (614) (510) (89) (348) (178) (1125) (557) (340) (760) ( 520)<br />
65.7 19.0 17.2 0.3 24.2 20.9 4.0 14.5 7.4 46.1 23.7 13.4 29.9 23.6<br />
(1668) (483) (437) (8) (614) (5<strong>30</strong>) (102) (368) (188) (11<strong>70</strong>) (602) (340) (760) ( 600)<br />
h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8 r1 r2<br />
36.6 14.2 26.4 11.9 20.5 17.0 16.0 – 10.2 M16 18.5 17.1 DN100 49.2 44.9<br />
(9<strong>30</strong>) (360) (6<strong>70</strong>) (<strong>30</strong>2) ( 520) (432) (406) – (258) M16 (4<strong>70</strong>) (435) DN100 (1250) (1140)<br />
42.3 16.5 <strong>30</strong>.5 11.9 20.5 17.0 16.0 – 12.2 M16 18.5 17.1 DN100 56.7 51.6<br />
(1075) (420) (775) (<strong>30</strong>2) ( 520) (432) (406) – (310) M16 (4<strong>70</strong>) (435) DN100 (1440) (1310)<br />
42.3 16.5 <strong>30</strong>.5 12.4 23.6 18.5 – 18.9 12.2 M16 21.7 19.7 DN100 56.7 51.6<br />
(1075) (420) (775) (315) ( 600) (4<strong>70</strong>) – (480) (310) M16 (550) (500) DN100 (1440) (1310)<br />
All measurements are approximate. <strong>Weishaupt</strong> reserves the right <strong>to</strong> make alterations in light of future developments.<br />
18
Burner dimensions<br />
sizes <strong>30</strong> <strong>to</strong> 50, 1<strong>LN</strong> version<br />
Flange connection<br />
Drilling dimensions of<br />
the burner plate<br />
Size<br />
<strong>30</strong>/2-A<br />
40/1-B<br />
40/2-A<br />
50/1-B<br />
50/2-A<br />
Dimensions in inches (mm)<br />
l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5<br />
42.6 9.6 10.7 0.3 13.9 11.8 2.3 9.4 4.8 1.3 27.6 14.6 8.2 16.5 13.0<br />
(1083) (245) (272) (8) (354) (<strong>30</strong>0) (58) (238) (123) (32) (<strong>70</strong>0) (371) (208) (418) ( 3<strong>30</strong>)<br />
44.4 10.6 10.7 0.3 16.3 12.6 2.3 9.4 4.8 1.3 29.7 15.8 9.5 18.2 13.0<br />
(1128) (2<strong>70</strong>) (272) (8) (414) (320) (58) (238) (123) (32) (755) (401) (242) (462) ( 3<strong>30</strong>)<br />
45.2 10.6 13.1 0.3 16.3 13.4 2.6 10.2 5.2 1.7 29.7 15.8 9.5 18.2 14.6<br />
(1148) (2<strong>70</strong>) (332) (8) (414) (340) (67) (258) (133) (42) (755) (401) (242) (462) ( 3<strong>70</strong>)<br />
47.0 12.4 13.1 0.3 16.6 14.3 2.6 10.2 5.2 1.7 32.3 17.3 10.9 21.7 14.6<br />
(1195) (315) (332) (8) (422) (363) (67) (258) (133) (42) (820) (440) (277) (550) ( 3<strong>70</strong>)<br />
49.0 12.4 17.6 0.3 16.6 16.3 2.8 12.1 6.2 2.6 33.9 18.3 10.9 21.7 16.9<br />
(1245) (315) (447) (8) (422) (413) (72) (<strong>30</strong>8) (158) (65) (860) (465) (277) (550) ( 4<strong>30</strong>)<br />
<strong>30</strong>/2-A<br />
40/1-B<br />
40/2-A<br />
50/1-B<br />
h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8 r1 r2<br />
22.5 8.1 16.0 8.1 13.0 11.0 9.8 – 8.6 M12 14.2 11.2 DN50 33.1 35.0<br />
(572) (207) (407) (207) ( 3<strong>30</strong>) (280) (250) – (218) M12 (360) (285) DN50 (840) (890)<br />
23.9 8.3 16.6 8.1 13.0 11.0 9.8 – 8.6 M12 14.2 11.2 DN50 35.2 38.2<br />
(607) (211) (422) (207) ( 3<strong>30</strong>) (280) (250) – (218) M12 (360) (285) DN50 (895) (9<strong>70</strong>)<br />
23.9 8.3 16.6 8.9 14.6 12.6 11.4 – 8.6 M12 15.7 12.8 DN65 35.2 38.2<br />
(607) (211) (422) (227) ( 3<strong>70</strong>) (320) (290) – (218) M12 (400) (325) DN65 (895) (9<strong>70</strong>)<br />
28.7 10.4 20.2 8.9 14.6 12.6 11.4 – 10.2 M12 15.7 12.8 DN65 41.7 39.4<br />
(7<strong>30</strong>) (263) (513) (227) ( 3<strong>70</strong>) (320) (290) – (258) M12 (400) (325) DN65 (1060) (1000)<br />
28.7 10.4 20.2 10.1 16.9 15.0 13.8 – 10.2 M16 18.9 15.4 DN80 41.7 40.4<br />
50/2-A<br />
(7<strong>30</strong>) (263) (513) (257) ( 4<strong>30</strong>) (380) (350) – (258) M16 (480) (390) DN80 (1060) (1025)<br />
All measurements are approximate. <strong>Weishaupt</strong> reserves the right <strong>to</strong> make alterations in light of future developments.<br />
19
Burner dimensions<br />
size <strong>70</strong>, 1<strong>LN</strong> version<br />
Flange connection<br />
Drilling dimensions of<br />
the burner plate<br />
Size<br />
<strong>70</strong>/1-B<br />
<strong>70</strong>/2-A<br />
<strong>70</strong>/1-B<br />
<strong>70</strong>/2-A<br />
Dimensions in inches (mm)<br />
l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5<br />
64.9 19.0 16.5 0.3 24.2 20.1 3.5 13.7 7.0 3.4 44.3 23.7 13.4 29.9 20.5<br />
(1648) (483) (419) (8) (614) (510) (89) (348) (178) (87) (1125) (602) (340) (760) ( 520)<br />
65.7 19.0 17.6 0.3 24.2 20.9 4.0 14.5 7.4 3.4 46.1 23.7 13.4 29.9 23.6<br />
(1668) (483) (447) (8) (614) (5<strong>30</strong>) (102) (368) (188) (87) (11<strong>70</strong>) (602) (340) (760) ( 600)<br />
h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 d8 r1 r2<br />
42.3 16.5 <strong>30</strong>.5 11.9 20.5 17.0 16.0 – 12.2 M16 18.5 17.1 DN100 56.7 51.6<br />
(1075) (420) (775) (<strong>30</strong>2) ( 520) (432) (406) – (310) M16 (4<strong>70</strong>) (435) DN100 (1440) (1310)<br />
42.3 16.5 <strong>30</strong>.5 12.4 23.6 18.5 – 18.9 12.2 M16 21.7 19.7 DN100 56.7 51.6<br />
(1075) (420) (775) (315) ( 600) (4<strong>70</strong>) – (480) (310) M16 (550) (500) DN100 (1440) (1310)<br />
All measurements are approximate. <strong>Weishaupt</strong> reserves the right <strong>to</strong> make alterations in light of future developments.<br />
20
The patented technology has been well<br />
and extensively tested<br />
Low NOx is a good subject for practical<br />
research and development work. The excellent<br />
emmission levels were not reached and<br />
measured under labora<strong>to</strong>ry conditions, but<br />
during hard, practical operation.<br />
Meanwhile, the <strong>Weishaupt</strong> Research and<br />
Development Centre can look back on many<br />
years of experiences with low NOx <strong>burners</strong><br />
on large combustion plants in Germany and<br />
Switzerland, the countries with the most stringent<br />
emission limits in Europe.<br />
Overall, the technology has shown itself <strong>to</strong> be<br />
extremely reliable, efficient and problem free<br />
in operation.<br />
21
Company overview<br />
The company <strong>Weishaupt</strong> was established in 1932. Today the<br />
company has grown <strong>to</strong> be one of the worlds largest<br />
manufacturers of <strong>burners</strong>, employing more than 3,000 people<br />
worldwide. Burner models range in size between 43,000 and<br />
63,000,000 BTU/h and can burn <strong>gas</strong>, oil or a combination of<br />
fuels.<br />
The <strong>Weishaupt</strong> Research & Development Institute was<br />
established in 1962 with the aim <strong>to</strong> develop exceptional<br />
products in terms of quality and performance.<br />
This commitment was made at a time when the concepts of<br />
“energy savings” and “environmental protection” were not yet<br />
considered issues of social or political importance. Today the<br />
commitment continues and is clearly seen in the quality and performance<br />
of every <strong>Weishaupt</strong> product.<br />
Annually more than 150,000 <strong>burners</strong> are sold by <strong>Weishaupt</strong>, all<br />
of which are manufactured <strong>to</strong> the highest quality standards. Up<br />
<strong>to</strong> now over 4.5 millions <strong>burners</strong> have been sold worldwide.<br />
<strong>Weishaupt</strong> is certified <strong>to</strong> ISO 9001. (Certification from 1992)<br />
Combustion test at R&D department<br />
High tech manufacturing facility<br />
22
<strong>Weishaupt</strong> manufacturing plant<br />
Aerial view of <strong>Weishaupt</strong> head quarter in Schwendi, Germany<br />
<strong>Weishaupt</strong> North America in Mississauga, ON, Canada<br />
23
Product and cus<strong>to</strong>mer service<br />
the complete <strong>Weishaupt</strong> range<br />
<strong>Weishaupt</strong> Corporation<br />
6280 Danville Road<br />
Mississauga, ON L5T 2H7<br />
Ph.: (905) 564 0946, Fax.: (905) 564 0949<br />
www.weishaupt-corp.com<br />
Print No. 8<strong>30</strong>17816, July 2006<br />
Printed in Germany. All rights reserved.<br />
Regular maintenance reduces heating<br />
costs and environmental pollution. Only a<br />
properly adjusted burner can save energy<br />
and be environmentally friendly. Behind<br />
each <strong>Weishaupt</strong> burner stands the whole<br />
<strong>Weishaupt</strong> cus<strong>to</strong>mer service organization.<br />
The outstanding efforts made in<br />
maintenance and service justify the<br />
enormous trust placed in <strong>Weishaupt</strong>’s<br />
<strong>burners</strong>, for at <strong>Weishaupt</strong> product and<br />
cus<strong>to</strong>mer service belong <strong>to</strong>gether.<br />
<strong>Weishaupt</strong> cus<strong>to</strong>mer service is there for<br />
you all year round. Whenever you need<br />
help, be it the supply of spare parts,<br />
technical advice or a site visit. We are<br />
there when you need us.