Airtight gas convectors<br />
3.5 Gas line connection<br />
SYSTEMA S.p.A.<br />
The gas line connection must be made with respect to the regulations in force.<br />
a) The device cannot withstand pressures of higher than 40 mbar (0,04 bar) without risking<br />
the breakage of the gas valve membrane.<br />
b) Always use ball valves and flexible joints for gas when connecting the devices.<br />
c) Gas supply line pressure adjustment: all the devices are tested and calibrated at the<br />
Manufacturer’s factory for their respective operating pressures (see the data provided in<br />
the table).<br />
In order to check burner pressure (Methane gas), use the pressure tap (4) at the valve outlet<br />
point (See Draw ) after first removing the closing screw; whenever the burner pressure<br />
values do not correspond, calibration must be performed (with the burner in operation) by<br />
using the pressure adjustment screw (9) until the nominal value is reached.<br />
For LPG gas (Butane-Propane), the gas valve pressure regulator must be disabled by<br />
screwing the pressure adjustment screw (9) all the way down. The gas supply pressure can<br />
be checked by using the pressure tap (5) at the valve inlet point (with the burner in operation);<br />
whenever the gas supply pressure values do not correspond, calibration must be performed<br />
(with the burner in operation) by using the pressure regulator positioned upstream from the<br />
device.<br />
After these pressure adjustment operations have been completed, remember to close the<br />
pressure taps located on the gas safety valve using the respective screws.<br />