Troubleshooting Tips<br />
USING MANUAL DIAGNOSTICS<br />
WARNING<br />
Be sure to discharge any system pressure before performing any manual<br />
diagnostics.<br />
This unit’s manual diagnostics mode is easily accessible through the keypad.<br />
1. Press SHIFT/RESET and ENTER at the same time. The display should be<br />
blank except for the decimal point.<br />
2. Press the following keys to perform these functions:<br />
Press 1 — Starts the vacuum pump to begin evacuation. Press 1 again (or<br />
SHIFT/RESET) to turn off the pump.<br />
Press 2 — Begins the transfer of refrigerant. The “ADD” message displays<br />
momentarily, then the display shows the amount of refrigerant transferred.<br />
Press HOLD/CONT at any time to interrupt the transfer and again to resume<br />
operation.<br />
Press 3 — Displays the total amount of refrigerant recovered. Each time<br />
recovery is completed, that amount is added to the existing total. To clear the<br />
internal counter, press SHIFT/RESET and ENTER at the same time while<br />
the total is being displayed. The maximum amount recorded is 9,999 pounds<br />
(or 99 kilograms) of refrigerant.<br />
Press 4 — Automatic charge after the vacuum cycle. The display will show<br />
"AUTOMATIC", "VACUUM," and either "00" or "11." "00" indicates a<br />
disabled auto-charge and "11" indicates an enabled auto-charge. Press<br />
ENTER to shift between enabled and disabled auto-charge. Press SHIFT/<br />
RESET to lock in mode choice to memory.<br />
Press 5 — All display segments light up. Press 5 again to turn off.<br />
Press 6 — Displays the approximate weight on the scale.<br />
See CHECKING THE SCALE ACCURACY for diagnostic procedures.<br />
Press 7 — Displays the weight of refrigerant contained in the tank.<br />
3. Press SHIFT/RESET to return to the PROGRAM mode.<br />
Series 17700A/17701A/34700/34701/34704 Enviro-Charge Units<br />
35