User <strong>Manual</strong><br />

Piccolo Range<br />

5.2.6 Output 2<br />

Output 2 may be fitted with a relay (form A), or a triac or an analogue output depend<strong>in</strong>g on <strong>the</strong> order code. The<br />

function of <strong>the</strong> output may be selected from a list of options <strong>in</strong>clud<strong>in</strong>g heat or cool outputs for <strong>the</strong> control loop, or<br />

alarms or events which may be used for external <strong>in</strong>dication. mA outputs may be used <strong>to</strong> re-transmit setpo<strong>in</strong>t,<br />

measured temperature or output demand.<br />

P12<br />

Select P12 <strong>to</strong> configure Output 2 (OP2).<br />

In P116, output 2 may be Relay, Analogue or Triac depend<strong>in</strong>g on <strong>the</strong> order code.<br />

In P108 and P104, output 2 may be Relay or Triac depend<strong>in</strong>g on <strong>the</strong> order code.<br />

Each output can be used for control, retransmission, alarms or events as listed below:-<br />

nonE<br />

Heat<br />

Output disabled<br />

Heat output<br />

(default)<br />

Output 2 controls <strong>the</strong> heat<strong>in</strong>g power demand. The sense<br />

is set <strong>to</strong> normal – <strong>the</strong> state of <strong>the</strong> output is shown <strong>in</strong> <strong>the</strong><br />

table. This is <strong>the</strong> usual sett<strong>in</strong>g for control outputs.<br />

The code can be checked<br />

aga<strong>in</strong>st <strong>the</strong> label on <strong>the</strong> side of<br />

<strong>the</strong> controller and <strong>the</strong> ‘Order<br />

Code’ <strong>in</strong> section 1.5.<br />

Relay<br />

Logic<br />

OP2 State when heat<strong>in</strong>g<br />

Analogue<br />

Energised<br />

ON<br />

On<br />

CooL<br />

Cool output<br />

Output 2 controls <strong>the</strong> cool<strong>in</strong>g demand. The sense is set<br />

<strong>to</strong> normal – <strong>the</strong> state of <strong>the</strong> output is shown <strong>in</strong> <strong>the</strong> table.<br />

This is <strong>the</strong> usual sett<strong>in</strong>g for control outputs.<br />

OP2 State when cool<strong>in</strong>g<br />

Relay Energised<br />

Logic ON<br />

Analogue On<br />

AL1 Alarm 1<br />

Alarm active<br />

AL2 Alarm 2 Output 2 will operate as shown <strong>in</strong> <strong>the</strong> table if <strong>the</strong> alarm Relay Energised<br />

AL3 Alarm 3<br />

selected is active.<br />

Logic ON<br />

Analogue On<br />

AL1.i Alarm 1 <strong>in</strong>verted.<br />

Output 2 will operate as shown <strong>in</strong> <strong>the</strong> table if <strong>the</strong> selected<br />

Alarm active<br />

AL2.i Alarm 2 <strong>in</strong>verted alarm is active. This is <strong>the</strong> normal sett<strong>in</strong>g for alarms s<strong>in</strong>ce Relay De-energised<br />

AL3.i Alarm 3 <strong>in</strong>verted<br />

if power <strong>to</strong> <strong>the</strong> controller fails an alarm state will be Logic OFF<br />

<strong>in</strong>dicated by a powered external device.<br />

Analogue Off (0mA)<br />

SP.rt<br />

SP re-transmission<br />

If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />

proportional <strong>to</strong> <strong>the</strong> setpo<strong>in</strong>t <strong>to</strong> an external device.<br />

The value is clipped <strong>to</strong> Low<br />

(SP.Lo) and High (SP.Hi)<br />

Setpo<strong>in</strong>t limits set <strong>in</strong> Level 2.<br />

oP.rt<br />

OP retransmission<br />

If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />

proportional <strong>to</strong> <strong>the</strong> output <strong>to</strong> an external device.<br />

The value of <strong>the</strong> analogue<br />

signal is clipped <strong>to</strong> <strong>the</strong> Low<br />

(oP.Lo) and High (oP.Hi)<br />

output limits set <strong>in</strong> Level 2.<br />

Pv.rt<br />

PV re-transmission<br />

If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />

proportional <strong>to</strong> <strong>the</strong> process variable <strong>to</strong> an external<br />

device.<br />

The value of <strong>the</strong> analogue<br />

signal is clipped <strong>to</strong> <strong>the</strong> Low and<br />

High scale range set <strong>in</strong> P codes<br />

P3 and P4.<br />

t.End<br />

t.rUn<br />

Timer end status<br />

Timer run status<br />

OP2 can be used <strong>to</strong> operate an external device <strong>to</strong><br />

<strong>in</strong>dicate when <strong>the</strong> timer has timed out. A relay is<br />

energised and a logic output is ON when <strong>the</strong> timer has<br />

timed out.<br />

OP2 can be used <strong>to</strong> operate an external device <strong>to</strong><br />

<strong>in</strong>dicate when <strong>the</strong> timer is runn<strong>in</strong>g. A relay is energised<br />

and a logic output is ON when <strong>the</strong> timer is runn<strong>in</strong>g.<br />

Timer Operation is described <strong>in</strong><br />

section 4.12.<br />

48 Part No HA031260 Issue 1 May -12