User <strong>Manual</strong><br />
Piccolo Range<br />
5.2.6 Output 2<br />
Output 2 may be fitted with a relay (form A), or a triac or an analogue output depend<strong>in</strong>g on <strong>the</strong> order code. The<br />
function of <strong>the</strong> output may be selected from a list of options <strong>in</strong>clud<strong>in</strong>g heat or cool outputs for <strong>the</strong> control loop, or<br />
alarms or events which may be used for external <strong>in</strong>dication. mA outputs may be used <strong>to</strong> re-transmit setpo<strong>in</strong>t,<br />
measured temperature or output demand.<br />
P12<br />
Select P12 <strong>to</strong> configure Output 2 (OP2).<br />
In P116, output 2 may be Relay, Analogue or Triac depend<strong>in</strong>g on <strong>the</strong> order code.<br />
In P108 and P104, output 2 may be Relay or Triac depend<strong>in</strong>g on <strong>the</strong> order code.<br />
Each output can be used for control, retransmission, alarms or events as listed below:-<br />
nonE<br />
Heat<br />
Output disabled<br />
Heat output<br />
(default)<br />
Output 2 controls <strong>the</strong> heat<strong>in</strong>g power demand. The sense<br />
is set <strong>to</strong> normal – <strong>the</strong> state of <strong>the</strong> output is shown <strong>in</strong> <strong>the</strong><br />
table. This is <strong>the</strong> usual sett<strong>in</strong>g for control outputs.<br />
The code can be checked<br />
aga<strong>in</strong>st <strong>the</strong> label on <strong>the</strong> side of<br />
<strong>the</strong> controller and <strong>the</strong> ‘Order<br />
Code’ <strong>in</strong> section 1.5.<br />
Relay<br />
Logic<br />
OP2 State when heat<strong>in</strong>g<br />
Analogue<br />
Energised<br />
ON<br />
On<br />
CooL<br />
Cool output<br />
Output 2 controls <strong>the</strong> cool<strong>in</strong>g demand. The sense is set<br />
<strong>to</strong> normal – <strong>the</strong> state of <strong>the</strong> output is shown <strong>in</strong> <strong>the</strong> table.<br />
This is <strong>the</strong> usual sett<strong>in</strong>g for control outputs.<br />
OP2 State when cool<strong>in</strong>g<br />
Relay Energised<br />
Logic ON<br />
Analogue On<br />
AL1 Alarm 1<br />
Alarm active<br />
AL2 Alarm 2 Output 2 will operate as shown <strong>in</strong> <strong>the</strong> table if <strong>the</strong> alarm Relay Energised<br />
AL3 Alarm 3<br />
selected is active.<br />
Logic ON<br />
Analogue On<br />
AL1.i Alarm 1 <strong>in</strong>verted.<br />
Output 2 will operate as shown <strong>in</strong> <strong>the</strong> table if <strong>the</strong> selected<br />
Alarm active<br />
AL2.i Alarm 2 <strong>in</strong>verted alarm is active. This is <strong>the</strong> normal sett<strong>in</strong>g for alarms s<strong>in</strong>ce Relay De-energised<br />
AL3.i Alarm 3 <strong>in</strong>verted<br />
if power <strong>to</strong> <strong>the</strong> controller fails an alarm state will be Logic OFF<br />
<strong>in</strong>dicated by a powered external device.<br />
Analogue Off (0mA)<br />
SP.rt<br />
SP re-transmission<br />
If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />
proportional <strong>to</strong> <strong>the</strong> setpo<strong>in</strong>t <strong>to</strong> an external device.<br />
The value is clipped <strong>to</strong> Low<br />
(SP.Lo) and High (SP.Hi)<br />
Setpo<strong>in</strong>t limits set <strong>in</strong> Level 2.<br />
oP.rt<br />
OP retransmission<br />
If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />
proportional <strong>to</strong> <strong>the</strong> output <strong>to</strong> an external device.<br />
The value of <strong>the</strong> analogue<br />
signal is clipped <strong>to</strong> <strong>the</strong> Low<br />
(oP.Lo) and High (oP.Hi)<br />
output limits set <strong>in</strong> Level 2.<br />
Pv.rt<br />
PV re-transmission<br />
If OP2 is mA it can be used <strong>to</strong> transmit an analogue value<br />
proportional <strong>to</strong> <strong>the</strong> process variable <strong>to</strong> an external<br />
device.<br />
The value of <strong>the</strong> analogue<br />
signal is clipped <strong>to</strong> <strong>the</strong> Low and<br />
High scale range set <strong>in</strong> P codes<br />
P3 and P4.<br />
t.End<br />
t.rUn<br />
Timer end status<br />
Timer run status<br />
OP2 can be used <strong>to</strong> operate an external device <strong>to</strong><br />
<strong>in</strong>dicate when <strong>the</strong> timer has timed out. A relay is<br />
energised and a logic output is ON when <strong>the</strong> timer has<br />
timed out.<br />
OP2 can be used <strong>to</strong> operate an external device <strong>to</strong><br />
<strong>in</strong>dicate when <strong>the</strong> timer is runn<strong>in</strong>g. A relay is energised<br />
and a logic output is ON when <strong>the</strong> timer is runn<strong>in</strong>g.<br />
Timer Operation is described <strong>in</strong><br />
section 4.12.<br />
48 Part No HA031260 Issue 1 May -12