IQ204/ADL Autodialling Controller Data Sheet - Trend
IQ204/ADL Autodialling Controller Data Sheet - Trend
IQ204/ADL Autodialling Controller Data Sheet - Trend
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Data</strong> <strong>Sheet</strong><br />
<strong>IQ204</strong>/<strong>ADL</strong><br />
HARDWARE (Continued)<br />
Auxiliary output supply: An auxiliary output supply of 24 Vdc at<br />
200 mA is available at terminals on the input and output rails.<br />
This is in addition to the full complement of inputs, outputs, NDP<br />
or GDP+, and an external 2-line display panel. If the modem is<br />
in use, it consumes the equivalent of 20 mA maximum (reduces<br />
auxiliary output supply to 180 mA).<br />
If more current is required from the auxiliary output supply, it can<br />
be compensated for by reducing input consumption.<br />
The auxiliary output supply is part of a 24 Vdc supply protected<br />
by a 500 mA self-resetting thermal device (effectively 380 mA at<br />
maximum temperature, 45 °C, 113 °F). This protected supply<br />
powers the inputs and the auxiliary output supply.<br />
# )<br />
I A @ = HO F H JA JE <br />
E F K JI<br />
= K N EE= HO I K F F O<br />
@ A ) <br />
The current consumed by these items is shown in the table:<br />
Area<br />
Inputs<br />
Analogue<br />
Digital<br />
Modem<br />
V<br />
oltage<br />
Load<br />
Item<br />
Current<br />
(IQ powered)<br />
Current<br />
(externally powered)<br />
Thermistor<br />
Auxiliary<br />
Supply<br />
24 Vdc Current<br />
P er Channel<br />
Total (maximum)<br />
0 mA<br />
20<br />
mA<br />
160 mA<br />
0 mA<br />
0 mA<br />
2 mA<br />
16 mA<br />
total<br />
20 mA<br />
180 mA<br />
376 mA<br />
For example:<br />
If an <strong>IQ204</strong>/<strong>ADL</strong> with modem connected has 8 digital inputs, 4<br />
voltage and 4 current (IQ supplied) inputs, what current can be<br />
taken from the auxiliary output supply<br />
ignore voltage inputs<br />
digital inputs (8 x 2)<br />
16 mA<br />
analogue current inputs (4 x 20) 80 mA<br />
modem<br />
20 mA<br />
Available for auxiliary output supply = 380 -16- 80 - 20 = 264mA<br />
I/O Channels: the <strong>IQ204</strong> is supplied with 8 digital inputs, 8 analogue inputs and 8 analogue outputs (voltage only).<br />
Digital inputs (Channels D1 to D8)<br />
Analogue voltage outputs (Channels B1 to B8)<br />
, <br />
<br />
" 8<br />
! !<br />
" 8<br />
" 8<br />
8<br />
4<br />
4<br />
2 <br />
Analogue inputs (Channels A1 to A8)<br />
The channels can be linked for thermistor (T), current (I), or<br />
voltage (V).<br />
8<br />
8<br />
<br />
# 8<br />
) <br />
" 4<br />
& <br />
1<br />
8 6<br />
8<br />
<br />
8<br />
" 8<br />
8<br />
" 8<br />
6 1 8<br />
The current sensor, I, is IQ powered. For an externally powered<br />
current sensor, the channel should be linked for I, and connected<br />
as a voltage input, V.<br />
<strong>IQ204</strong>/<strong>ADL</strong> Autodailling <strong>Controller</strong> <strong>Data</strong> <strong>Sheet</strong> TA200489 Issue 1/E 01/11/06<br />