WORKING HEAD OF THE PUMPING MODULE MP AM STD AND MP SS STD<br />
400<br />
350<br />
300<br />
250<br />
200<br />
150<br />
100<br />
50<br />
0<br />
The graph below illustrates for the evaporator the water pressure drop values in kPa depending on the flow rate in liters/second. The<br />
operating range is delimited by the minimum and maximum values given in the next table.<br />
560.6<br />
440.6<br />
350.5<br />
630.6<br />
390.6<br />
490.6<br />
6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0<br />
Water flow rate (l/s) (l/s)<br />
Operating range<br />
Unit size 350.5 390.6 440.6 490.6 560.6 630.6 UM NOTE<br />
Lower limit value Q 7.20 7.20 8.98 8.98 11.76 11.78 l/s<br />
Q= Water flow rate<br />
Upper limit value Q 24.7 24.7 28.2 28.2 38.4 38.4 l/s<br />
Water pressure drop (kPa)<br />
(kPa)<br />
37