Water pressure drop EVAPORATOR<br />

150<br />

140<br />

130<br />

120<br />

110<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

The graph below illustrates for the evaporator the water pressure drop values in kPa depending on the flow rate in liters/second. The<br />

operating range is delimited by the minimum and maximum values given in the next table.<br />

390.6<br />

350.5<br />

490.6<br />

440.6<br />

630.6<br />

560.6<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0 38.0 40.0 42.0 44.0 46.0<br />

Water flow (l/s) rate (l/s)<br />

Operating range<br />

Unit size 350.5 390.6 440.6 490.6 560.6 630.6 UM NOTES<br />

Q 7.20 7.20 8.98 8.98 11.76 11.78 l/s<br />

Lower limit value<br />

∆p 10 kPa<br />

Upper limit value<br />

Q 21.4 21.4 26.4 26.3 34.7 34.7 l/s<br />

∆p 150 kPa<br />

Q= Water flow rate<br />

∆P= Water pressure<br />

drop<br />

Water pressure drop (kPa)<br />

(kPa)<br />