ACCESSORIES AND OPTIONAL EQUIPMENT<br />

Electrical accessories<br />

TP - Low and High pressure transducers (M). Allow the display of the suction and discharge pressures of compressors. Their presence<br />

activates an advanced defrost and condensation control logic and the ATC (Advanced Temperature Control) to prevent high pressure alarm<br />

due to high external air temperature.<br />

RAG- Storage tank electrical heater (F). Keeps water in storage tank above freezing point to avoid risk of icing during winter stops it is<br />

activated together with plate heat exchanger electrical heater.<br />

TAT- High Temperature Thermostat (M). Two thermostats in series on compressors outlet pipes preserve operation not allowing temperature<br />

to rise up than a specified non adjustable value.<br />

CR- Remote control panel (F). Replies every control and visualization of the onboard control panel.<br />

INT- Serial interface (M). Allows serial communication on RS485 by MODBUS protocol.<br />

MTC - Magnetothermic switch (M). Magnetothermic switch on all loads place of fuses.<br />

SS - Soft Starter (M). Soft starter on compressors allow to reduce to about a 60% nominal inrush current.<br />

FLS - Flow switch (F). Paddle flow switch on the water circuit to avoid the risk of freezing if the water flow is shut off for some reason.<br />

RIF - Capacitors for power factor corrections (M). Capacitors for power factor corrections increase power factor cos φ (> 0.91) and reduce<br />

power input.<br />

CSF - Voltage monitor and sequence meter (M). The device enables control of the correct sequence of power phases and the lack of any<br />

phases.<br />

KOP - Programmer clock (M). Allows the unit to be turned on and off depending on the programmed time setting (up to 14 switching actions<br />

can be programmed as required throughout the 7 days of the week).<br />

DCC - Head pressure control (M). (as standard for Low Noise unit AS and for eXtra Low Noise unit AX).<br />

The device is made by 2 electrical drivers that, by means of phase cutting, control the fans speed rotation, with the scope of mantaining the<br />

condensation pressure inside the correct operating limits.<br />

Mechanical options<br />

Special finned heat exchangers<br />

• Coils with copper fins<br />

• Coils with tin-coated copper fins<br />

• Coils with aluminium fins with acrylic, epoxy or hydrofilic coating.<br />

Electrical options<br />

Other power source voltage rating (contact our technical department).<br />