01.12.2014 Views

MODEL FIII-SERIES CONTROL INSTALLATION ... - Agencespl.com

MODEL FIII-SERIES CONTROL INSTALLATION ... - Agencespl.com

MODEL FIII-SERIES CONTROL INSTALLATION ... - Agencespl.com

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

ohm method (type 4). The relay contacts on the MASTER<br />

will then be connected to the associated 4-20ma<br />

REMOTE ENABLE inputs on the associated boiler(s).<br />

NOTE<br />

The minimum setting of the boiler is calibrated so<br />

that the minimum PWM signal to control the Blower<br />

motor is 20%. The VFD to blower motor operates<br />

with a control signal from 20% - 80% Pulse Width<br />

Modulation. This PWM signal to the VFD can be<br />

measured using a multimeter. It is a 0–10volt square<br />

wave signal at 110 Hertz. A 20% modulation signal<br />

will read 2.0 VDC, and an 80% modulation signal<br />

will read 8.0 VDC on an RMS multimeter.<br />

Circulator Pump Options<br />

The circulator pump options are intended for the boilers<br />

local circulator pump. The circulator pump is supported<br />

by (3) modes.<br />

1. The first mode will allow the circulator<br />

pump to remain on, unless the control’s<br />

outside high air temperature setting has been<br />

met when using OUTDOOR AIR RESET.<br />

2. The second mode will allow the circulator<br />

pump to be turned on whenever there is a<br />

call for heat (any control input). This mode<br />

will stop the circulator pump when the call<br />

for heat is lost and the pump post purge time<br />

has been satisfied.<br />

3. The third mode allows the inlet sensor<br />

(RETURN) to be used with the outlet sensor<br />

(SUPPLY) to keep the pump on until a delta<br />

(difference) temperature is met. The return<br />

temperature sensor is required for this mode,<br />

since the delta temperature (SUPPLY –<br />

RETURN) measured is across the boiler. In<br />

this mode, the post purge time is also used,<br />

and after the delta temp has been met, the<br />

post purge time needs to expire before the<br />

pump is turned off.<br />

If a flow switch is connected to the WTR FLW<br />

interlock, the <strong>FIII</strong> control will wait up to 10 seconds to<br />

prove flow. If flow is interrupted after it has been<br />

established, an error will be displayed and the boiler<br />

will cycle OFF. As long as there is a call for heat,<br />

every 10 minutes the circulator pump will try to reestablish<br />

flow and start the boiler again.<br />

REV 1.1<br />

<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />

temperature. In the case of a single boiler system, the<br />

boiler’s outlet (SUPPLY) sensor will only be needed<br />

(Local Control).<br />

Auxiliary Function Options<br />

If less than 3 boilers are used in a stand-alone (no<br />

external control) configuration, the third boiler relay<br />

contact can be used to control a <strong>com</strong>bustion air damper.<br />

A proof time of up to 4 minutes can be set before the<br />

boiler can start or an alarm condition will occur. If the<br />

boiler configuration is for a single boiler, either the<br />

second or third boiler relays can be used for this option.<br />

Sensors<br />

The <strong>FIII</strong> control supports a standard 10K thermistor.<br />

These sensors can be calibrated to the control by<br />

entering the sensor menu and placing a precision 10k<br />

resistor on an input.<br />

Security<br />

A password can be used to lock out control and setup<br />

features. It can be enabled, but is shipped in the<br />

disabled state.<br />

Diagnostics<br />

The <strong>FIII</strong> control can display and identify faults in a<br />

meaningful way. If an interlock trips, it will be<br />

indicated in the main screen display, along with an<br />

audible alarm and a set of relay contacts will close. A<br />

record of this, with a time stamp, will also be entered<br />

into the log as an aide in the diagnosis of the event. The<br />

log can be downloaded and a histogram used to display<br />

the data TBD.<br />

Open and shorted sensors are checked continuously, so<br />

that in the event of a sensor failure, the system shuts<br />

down and the alarm relay is closed.<br />

Communications<br />

The <strong>FIII</strong> control has the ability to <strong>com</strong>municate using the<br />

MODBUS protocol with a building management system.<br />

Most registers and functions are available through<br />

MODBUS access. Access is allowed using the RS485<br />

CONSOLE connecter on the <strong>com</strong>munication board.<br />

PID Control Algorithm Options<br />

The control algorithm can be used with an outdoor reset<br />

ratio, and can regulate water temperature from the loop<br />

(header temperature), or from the boiler’s outlet<br />

Page 9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!