REV 1.1<br />

<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />

and the firing rate are controlled by an external control<br />

or by the master boiler.<br />

If using the H-Net protocol, the system setpoint is<br />

sent from the master, along with the modulation value<br />

to control firing rate. It also receives its <strong>com</strong>mand to<br />

start or stop over the H-Net cable.<br />

The member also continuously monitors its supply<br />

temperature against its operating limit. If the supply<br />

temperature approaches the operating limit temperature<br />

(adjustable), the boilers input control rate is limited and<br />

its modulation value decreases to minimize short<br />

cycling. If the operating limit is exceeded, the boiler<br />

shuts off.<br />

If not using the H-Net protocol, the master or an<br />

external boiler control can send a 4-20ma signal along<br />

with a 4-20ma enable signal to control the firing rate.<br />

The boiler may also be treated as a 4-stage boiler or an<br />

ON-OFF boiler using the dedicated T-inputs.<br />

Page 3