REV 1.1<br />
<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />
and the firing rate are controlled by an external control<br />
or by the master boiler.<br />
If using the H-Net protocol, the system setpoint is<br />
sent from the master, along with the modulation value<br />
to control firing rate. It also receives its <strong>com</strong>mand to<br />
start or stop over the H-Net cable.<br />
The member also continuously monitors its supply<br />
temperature against its operating limit. If the supply<br />
temperature approaches the operating limit temperature<br />
(adjustable), the boilers input control rate is limited and<br />
its modulation value decreases to minimize short<br />
cycling. If the operating limit is exceeded, the boiler<br />
shuts off.<br />
If not using the H-Net protocol, the master or an<br />
external boiler control can send a 4-20ma signal along<br />
with a 4-20ma enable signal to control the firing rate.<br />
The boiler may also be treated as a 4-stage boiler or an<br />
ON-OFF boiler using the dedicated T-inputs.<br />