REV 1.1<br />
<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />
Modbus Input (Read Only) Registers<br />
Address Data Type Description Valid Values/Range<br />
0 Unsigned Boilers Running 0 – 16<br />
1 Modulation (% BTU Load) 0 – 100<br />
2 Header / System Temperature 32 – 250 °F<br />
3 Supply Temperature 32 – 250 °F<br />
4 Return Temperature 32 – 250 °F<br />
5 Outside Air Temperature -40 – 250 °F<br />
6 Signed Spare Input 1 -32768 to 32767<br />
7 Signed Spare Input 2 -32768 to 32767<br />
8 Unsigned Clock – Month 0 – 11<br />
9 Unsigned Clock – Day 1 – 31<br />
10 Unsigned Clock – Year 0 – 99<br />
11 Unsigned Clock – Hours 0 – 23<br />
12 Unsigned Clock – Minutes 0 – 59<br />
13 Unsigned Clock – Seconds 0 – 59<br />
14 Unsigned Clock – Day of Week 1 – Monday<br />
7 – Sunday<br />
15 – 46 Unsigned Boilers 1 – 16 status flag (32-bit) registers. The upper<br />
16-bits of each 32-bit register is stored at odd<br />
numbered addresses 15 – 45. The lower 16-bits of each<br />
32-bit register is stored at even numbered addresses 16<br />
– 46.<br />
See the Boiler Status<br />
Flags Table Below<br />
47 – 78 Unsigned Boilers 1 – 16 runtime (32-bit) registers. The upper<br />
16-bits of each 32-bit register is stored at odd<br />
numbered addresses 47 – 77. The lower 16-bits of each<br />
32-bit register is stored at even numbered addresses 48<br />
– 78.<br />
0 – 4294967295<br />
seconds<br />
When the upper and lower registers are <strong>com</strong>bined they<br />
form a 32-bit unsigned integer that is the number of<br />
seconds that the boiler has been running. For instance:<br />
(((Register 29) * 65536) + Register 30) = Boiler 1<br />
runtime in seconds.<br />
Boiler 1 is the master boiler. Boilers 2 – 16 are<br />
member boilers.<br />
Page 22