<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />

Modbus Input (Read Only) Registers<br />

Address Data Type Description Valid Values/Range<br />

0 Unsigned Boilers Running 0 – 16<br />

1 Modulation (% BTU Load) 0 – 100<br />

2 Header / System Temperature 32 – 250 °F<br />

3 Supply Temperature 32 – 250 °F<br />

4 Return Temperature 32 – 250 °F<br />

5 Outside Air Temperature -40 – 250 °F<br />

6 Signed Spare Input 1 -32768 to 32767<br />

7 Signed Spare Input 2 -32768 to 32767<br />

8 Unsigned Clock – Month 0 – 11<br />

9 Unsigned Clock – Day 1 – 31<br />

10 Unsigned Clock – Year 0 – 99<br />

11 Unsigned Clock – Hours 0 – 23<br />

12 Unsigned Clock – Minutes 0 – 59<br />

13 Unsigned Clock – Seconds 0 – 59<br />

14 Unsigned Clock – Day of Week 1 – Monday<br />

7 – Sunday<br />

15 – 46 Unsigned Boilers 1 – 16 status flag (32-bit) registers. The upper<br />

16-bits of each 32-bit register is stored at odd<br />

numbered addresses 15 – 45. The lower 16-bits of each<br />

32-bit register is stored at even numbered addresses 16<br />

– 46.<br />

See the Boiler Status<br />

Flags Table Below<br />

47 – 78 Unsigned Boilers 1 – 16 runtime (32-bit) registers. The upper<br />

16-bits of each 32-bit register is stored at odd<br />

numbered addresses 47 – 77. The lower 16-bits of each<br />

32-bit register is stored at even numbered addresses 48<br />

– 78.<br />

0 – 4294967295<br />

seconds<br />

When the upper and lower registers are <strong>com</strong>bined they<br />

form a 32-bit unsigned integer that is the number of<br />

seconds that the boiler has been running. For instance:<br />

(((Register 29) * 65536) + Register 30) = Boiler 1<br />

runtime in seconds.<br />

Boiler 1 is the master boiler. Boilers 2 – 16 are<br />

member boilers.<br />

Page 22