REV 1.1<br />

<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />

AUX FUNCTIONS<br />

COMBUST AIR DAMPER<br />

IN USE? NO If set to YES, then OUTPUT RELAY # can be used<br />

to control a <strong>com</strong>bustion air damper.<br />

OUTPUT RELAY # K5 If K5 is used, There can be no Boiler #3 as a member<br />

address, since the onboard relay is shared by boiler #3<br />

and with the <strong>com</strong>bustion air damper function.<br />

PROOF TIME 2:00 (0 – 4min) This is the proving time in minutes for the<br />

<strong>com</strong>bustion air proof switch. It is sensed at SPARE 1<br />

on J10B. Also Sensor #5 must be set to ON/OFF in<br />

the sensors menu in order to detect the prove switch<br />

being made. If a fault occurs, remove the call for heat to clear.<br />

ALARM SILENCE<br />

IN USE? YES This menu allows the configuration of the Alarm Silence switch.<br />

It can be disabled so that the Alarm Silence switch can not silence<br />

the alarm until the alarm is cleared; ALARM SILENCE = NO. The<br />

default value is to enable the ALARM SILENCE switch.<br />

INPUT = J10B SPARE 2 This setting allows the Alarm Switch to be looked at using another<br />

input. This input should not be changed, but allows for custom<br />

configurations to resolve conflicts.<br />

HEAT EXCHANGER<br />

ALARM TYPE: WARNING This setting determines the way in which the control reacts when the<br />

differential temperature across the heat exchanger exceeds the<br />

specified maximum differential temperature. The default alarm<br />

condition is a WARNING. The WARNING state will allow the<br />

boiler to keep functioning and display a warning message and a<br />

timestamp in the status screen when the maximum differential<br />

temperature is exceeded. If FAULT is selected, the boiler will shut<br />

down and act as if an interlock has tripped.<br />

EXCHR DELTA T 45F per Boiler This is the maximum differential temperature the heat exchanger can<br />

see before the ALARM TYPE is applied. This value can not be<br />

changed and is defined for each boiler size.<br />

LIM-> HALF RATE YES Limit to Half Rate: When set to YES, and the maximum differential<br />

temperature (delta T) has been exceeded, the fire rate called for is cut<br />

in half. In other words: if we are calling for 80% modulation and<br />

have exceeded the delta T, the boiler will only fire at 40%. The delta<br />

T needs to drop 10F below the maximum delta T to reset this<br />

limit. This method helps protect the heat exchanger from damage<br />

due to excessive delta T’s.<br />

SYSTEM CLOCK<br />

TIME<br />

This time needs to be entered at first turn-on and in<br />

DAY OF WEEK the event that power has been lost for more than 3<br />

MONTH<br />

days. The time is only required for an accurate log<br />

DAY<br />

entry time-stamp and fault time stamp.<br />

YEAR<br />

PRESS SEL TO SAVE<br />

The SEL key must be pressed after all time values<br />

have been entered to save all time values at once.<br />

DISTRIBUTED CTRL<br />

<strong>CONTROL</strong> H-Net Two methods of operation: RELAY & H-Net<br />

H-Net MASTER YES Auto detected, based on the HEADER sensor. If the<br />

HEADER sensor is present and is set to TYPEZ or<br />

TE6000, the <strong>FIII</strong>-series control is run as a H-Net<br />

MASTER (YES). If the HEADER sensor is not<br />

TYPEZ or TE6000, H-Net MASTER = NO.<br />

Page 18