<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />
AUX FUNCTIONS<br />
COMBUST AIR DAMPER<br />
IN USE? NO If set to YES, then OUTPUT RELAY # can be used<br />
to control a <strong>com</strong>bustion air damper.<br />
OUTPUT RELAY # K5 If K5 is used, There can be no Boiler #3 as a member<br />
address, since the onboard relay is shared by boiler #3<br />
and with the <strong>com</strong>bustion air damper function.<br />
PROOF TIME 2:00 (0 – 4min) This is the proving time in minutes for the<br />
<strong>com</strong>bustion air proof switch. It is sensed at SPARE 1<br />
on J10B. Also Sensor #5 must be set to ON/OFF in<br />
the sensors menu in order to detect the prove switch<br />
being made. If a fault occurs, remove the call for heat to clear.<br />
ALARM SILENCE<br />
IN USE? YES This menu allows the configuration of the Alarm Silence switch.<br />
It can be disabled so that the Alarm Silence switch can not silence<br />
the alarm until the alarm is cleared; ALARM SILENCE = NO. The<br />
default value is to enable the ALARM SILENCE switch.<br />
INPUT = J10B SPARE 2 This setting allows the Alarm Switch to be looked at using another<br />
input. This input should not be changed, but allows for custom<br />
configurations to resolve conflicts.<br />
HEAT EXCHANGER<br />
ALARM TYPE: WARNING This setting determines the way in which the control reacts when the<br />
differential temperature across the heat exchanger exceeds the<br />
specified maximum differential temperature. The default alarm<br />
condition is a WARNING. The WARNING state will allow the<br />
boiler to keep functioning and display a warning message and a<br />
timestamp in the status screen when the maximum differential<br />
temperature is exceeded. If FAULT is selected, the boiler will shut<br />
down and act as if an interlock has tripped.<br />
EXCHR DELTA T 45F per Boiler This is the maximum differential temperature the heat exchanger can<br />
see before the ALARM TYPE is applied. This value can not be<br />
changed and is defined for each boiler size.<br />
LIM-> HALF RATE YES Limit to Half Rate: When set to YES, and the maximum differential<br />
temperature (delta T) has been exceeded, the fire rate called for is cut<br />
in half. In other words: if we are calling for 80% modulation and<br />
have exceeded the delta T, the boiler will only fire at 40%. The delta<br />
T needs to drop 10F below the maximum delta T to reset this<br />
limit. This method helps protect the heat exchanger from damage<br />
due to excessive delta T’s.<br />
SYSTEM CLOCK<br />
TIME<br />
This time needs to be entered at first turn-on and in<br />
DAY OF WEEK the event that power has been lost for more than 3<br />
MONTH<br />
days. The time is only required for an accurate log<br />
DAY<br />
entry time-stamp and fault time stamp.<br />
YEAR<br />
PRESS SEL TO SAVE<br />
The SEL key must be pressed after all time values<br />
have been entered to save all time values at once.<br />
DISTRIBUTED CTRL<br />
<strong>CONTROL</strong> H-Net Two methods of operation: RELAY & H-Net<br />
H-Net MASTER YES Auto detected, based on the HEADER sensor. If the<br />
HEADER sensor is present and is set to TYPEZ or<br />
TE6000, the <strong>FIII</strong>-series control is run as a H-Net<br />
MASTER (YES). If the HEADER sensor is not<br />
TYPEZ or TE6000, H-Net MASTER = NO.<br />
Page 18