REV 1.1 FIII SERIES CONTROL FIGURE 4: Control: 1-4 stage boiler, MASTER/MEMBER Close this contact to run boiler at High Fire Stage Control Inputs: Stage 1, Stage 2, Stage 3, Stage 4 AA 1 2 3 4 FIGURE 5: Control: PID, MASTER/MEMBER Slave: Close to run at Local Setpoint Master: Close to control all boilers & run at System Setpoint. Close this contact to override the Outdoor Reset slope and run at the Local/System Setpoint. Page 12

REV 1.1 FIII SERIES CONTROL FIGURE 6: Control: Relay Mode MASTER 4-20ma Transmitter 4-20ma - Output 4-20ma + Output Connect to boilers 2 and 3 Relay Mode: Enables boiler 2, wire to Boiler 2 Remote Enable. All Modes: Alarm Contacts close during a fault condition. Relay Mode: Enables Combustion Air Damper or boiler 3, wire to Boiler 3 Remote Enable or to power Combustion Air Damper. All Modes: Enables local boiler Circulator pump . FIGURE 7: Control: H-NET, MASTER/MEMBER NOTE: J4 can be used instead of J1. If RJ45 cables/ends are not available, use shielded wire. Computer or Management System USB to Computer To next Boiler H-Link Termination: Master: always has (2) termination jumpers enabled(Termination) J21,J23. MEMBER: (farthest) boiler has (2) jumpers enabled(Termination). J21,J23 MODBUS Always A MEMBER: Terminate last using J3 & J6 (Termination enabled) H-NET Termination: Enabled Disabled J6 J3 J23 J21 Straight Pins From a Boiler Right Angle Pins NO Termination Termination H-NET MODBUS Page 13

REV 1.1<br />

<strong>FIII</strong> <strong>SERIES</strong> <strong>CONTROL</strong><br />

FIGURE 4:<br />

Control: 1-4 stage boiler, MASTER/MEMBER<br />

Close this contact to run<br />

boiler at High Fire<br />

Stage Control Inputs:<br />

Stage 1, Stage 2,<br />

Stage 3, Stage 4<br />

AA<br />

1 2 3 4<br />

FIGURE 5:<br />

Control: PID, MASTER/MEMBER<br />

Slave: Close to run at Local Setpoint<br />

Master: Close to control all boilers & run<br />

at System Setpoint.<br />

Close this contact to override the<br />

Outdoor Reset slope and run at<br />

the Local/System Setpoint.<br />

Page 12