LON – Network 3065<br />

Page 17<br />

Build the LPI-10 into the separate segments in such a way that there is voltage of at<br />

least 35V DC at each LockNode.<br />

Consequently, the installation location depends on the number and particular<br />

distribution of the LockNodes in the corresponding segment.<br />

If it is not possible to guarantee voltage of 35 VDC at each LockNode with one<br />

LPI-10, you must install a repeater (including power supply) and an additional LPI-10<br />

(including power supply) in the segment.<br />

The LPI-10, as it comes from the factory, does not have any over voltage protection.<br />

For this reason, this protection should be already provided for by the customer.<br />

6.0 Router<br />

6.1 Method of Operation<br />

Routers are needed in order to separate individual segments, such as floors or<br />

buildings, from one another in large networks. From the entire data stream that<br />

arrives at one side, they are able to filter out the data that is intended for the segment<br />

lying behind them (data segmentation). Because the routers receive a Group ID, they<br />

must be configured by <strong>SimonsVoss</strong>.<br />

Example:<br />

One segment can have a maximum of 62 LockNodes. As soon as this number is<br />

exceeded, you must open a new segment with a router and an additional LPI-10<br />

module + plug-in power supply. A network can have a maximum of 63 segments. In<br />

large networks, you should choose the segments to fit the structural conditions, for<br />

example, one segment per building or floor.