LON – Network 3065<br />

Page 14<br />

5.2.2 Assembly Instructions<br />

The LPI-10 is intended<br />

for installation in<br />

distribution boxes with<br />

DIN rails. You will also<br />

need an outlet for the<br />

plug-in power supply<br />

of the LPI-10. Depending<br />

on the structural<br />

situation and number<br />

of groups, you can<br />

also put several power<br />

supplies and routers in<br />

one distribution box.<br />

Connect the network cable<br />

(twisted pair) here. You can<br />

also lay a network cable to<br />

the router (if there is one).<br />

Connect the cable to<br />

terminals 17 and 18 there. An<br />

additional network cable goes<br />

from the router to the Lock-<br />

Nodes.<br />

Connect the plug-in<br />

power supply to these<br />

terminals. Make sure<br />

that the polarity (+/-) is<br />

correct. This is printed<br />

on the connecting<br />

terminals. Ground the<br />

LPI-10 on the middle<br />

terminal.<br />

<br />

<br />

<br />

<br />

<br />

Build the LPI-10 into the separate segments in such a way that there is voltage<br />

of at least 35V DC on each LockNode.<br />

Consequently, the installation location depends on the number and particular<br />

distribution of the LockNodes in the corresponding segment.<br />

If it is not possible to guarantee voltage of 35 VDC at each LockNode with one<br />

LPI-10, you must install a repeater (including power supply) and an additional<br />

LPI-10 (including power supply) in the segment.<br />

The LPI-10, as it comes from the factory, does not have any over voltage<br />

protection. For this reason, this protection should be already provided for by<br />

the customer.<br />

When commissioning the LPI-10 and the network, you must make sure that<br />

the line voltage that is applied is 230V~ (+/- 10%). Higher or lower line voltage<br />

input to the LPI-10 can lead to disturbances in the network.