7.1.2.12 Pressure compensation<br />

The function pressure compensation foresees to divide the max.<br />

flow rate of the plant in 10 ranges, and into each range it is<br />

assigned a set-point. The ECU changes the set-point according to<br />

the range of flow rate passing through the regulator in that<br />

moment.<br />

The changing of the range has a hysteresis of 50%, i.e. the<br />

change of range in increase is made when exceeding the flow<br />

rates indicated in the example, (100, 200, 300, …Sm³/h) while<br />

when decreasing the change in the previous range is made at<br />

250, 150, 50 Sm³/h).<br />

In the page “Pressure compensation” clicking on “Modify” it is<br />

possible to set, facultative, the period in which the function<br />

activates and a value of default for the periods not activated (or<br />

let it always activated).<br />

The ranges are programmed in the page “Future Compensation”.<br />

Select:<br />

- The maximum flow rate (it calculates automatically the 10<br />

ranges of flow rate).<br />

- The desired set-points matched to each range. Not necessarily<br />

increasing, it is also possible decreasing.<br />

At the end of the insertion of all the set-point, click on “Download”.<br />

Clicking on “Current profile” it is possible to visualize the<br />

programming inserted.<br />

Clicking on “Activation Date” it is possible to choose if to activate<br />

the “Pressure compensation” immediately or at a certain date and<br />

hour.<br />

However, it must always be selected the Modulation mode in<br />

“Pressure Compensation” (see 7.1.2.9).<br />

F.I.O.<br />

User’s Manual<br />

ENGLISH<br />

F.I.O. User Manual – Ed.2. Rev.5 Page 35/ 53<br />

The information contained in this document is confidential and the property of <strong>Pietro</strong> <strong>Fiorentini</strong> S.p.A.<br />

Technical data may undergo changes without notice

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!