7.1.2.12 Pressure compensation<br />
The function pressure compensation foresees to divide the max.<br />
flow rate of the plant in 10 ranges, and into each range it is<br />
assigned a set-point. The ECU changes the set-point according to<br />
the range of flow rate passing through the regulator in that<br />
moment.<br />
The changing of the range has a hysteresis of 50%, i.e. the<br />
change of range in increase is made when exceeding the flow<br />
rates indicated in the example, (100, 200, 300, …Sm³/h) while<br />
when decreasing the change in the previous range is made at<br />
250, 150, 50 Sm³/h).<br />
In the page “Pressure compensation” clicking on “Modify” it is<br />
possible to set, facultative, the period in which the function<br />
activates and a value of default for the periods not activated (or<br />
let it always activated).<br />
The ranges are programmed in the page “Future Compensation”.<br />
Select:<br />
- The maximum flow rate (it calculates automatically the 10<br />
ranges of flow rate).<br />
- The desired set-points matched to each range. Not necessarily<br />
increasing, it is also possible decreasing.<br />
At the end of the insertion of all the set-point, click on “Download”.<br />
Clicking on “Current profile” it is possible to visualize the<br />
programming inserted.<br />
Clicking on “Activation Date” it is possible to choose if to activate<br />
the “Pressure compensation” immediately or at a certain date and<br />
hour.<br />
However, it must always be selected the Modulation mode in<br />
“Pressure Compensation” (see 7.1.2.9).<br />
F.I.O.<br />
User’s Manual<br />
ENGLISH<br />
F.I.O. User Manual – Ed.2. Rev.5 Page 35/ 53<br />
The information contained in this document is confidential and the property of <strong>Pietro</strong> <strong>Fiorentini</strong> S.p.A.<br />
Technical data may undergo changes without notice