5. Basic configurations on ECU<br />
PROCEDURE STEP 4:<br />
F.I.O.<br />
User’s Manual<br />
After the electrical devices and connections have been verified, the first configuration has to be done on ECU.<br />
ENGLISH<br />
- In case of direct measurement of the flow rate, set the parameters for the calculation. Refer to the following instructions.<br />
- In case of indirect measurement of the flow rate, set the full scale (100%) and the zero (0%) of the regulator. Refer to the following<br />
instructions.<br />
IMPORTANT: After the first modification made directly via keypad, the ECU goes in “Maintenance” status. In this status the ECU<br />
stops all the modulation activities, so remember to bring back the ECU in “Normal working status” (see Enclosure A at the end of<br />
manual).<br />
At the end of the configuration of flow rate measurement parameters:<br />
- Pressurize the upstream line if it has not been done yet (depending from the case with the spring of the P-kit completely<br />
free and opening slowly the upstream ball or butterfly valve. Leave the downstream valve closed.<br />
- Screw the setting screw of P-kit keeping a small flow rate from the downstream side to the atmosphere through the vent<br />
valve. Increase the downstream pressure and set the spring of P-kit at the pneumatic setting agreed with the customer.<br />
When possible, latch the SSV if present.<br />
Note: if one of these units is not provided, don’t consider the corresponding chapter.<br />
5.1 Instruction for the navigation through ECU menus<br />
For the visualization/modification of variables from the keypad:<br />
-pressing ENTER is possible to go inside the next sub-menu<br />
-pressing ESC is possible to go back to the higher menu<br />
-pressing the arrows “▲” or “▼” is possible to move inside the menu<br />
For the modifications of the parameters related to the direct measurement of flow rate in menu “Settings” from the keypad:<br />
1- Press the “PROGRAM ENABLE” botton on the board of ECU. If this operation is forgotten,<br />
the message “Access denied remove seals” appear<br />
2- Press ENTER on the page where there is the value to modify (the value moves to the left)<br />
3- Write with the keypad the new value<br />
4- Press ENTER<br />
5- When all the selected values in that menu has been updated, press ESC<br />
6- Press ENTER to save the modifications<br />
For the modifications of the other parameters in menu “Settings” and “F.I.O. Five in One \ Maintenance” from the keypad:<br />
7- Press ENTER on the page where there is the value to modify<br />
8- Type the requirred password (default 0000)<br />
9- Press ENTER<br />
10- Press ENTER again (the value moves to the left)<br />
11- Write with the keypad the new value<br />
12- Press ENTER<br />
13- When all the selected values in that menu has been updated, press ESC<br />
14- Press ENTER to save the modifications<br />