Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc.
Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc. Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc.
Engineering Manual From 7 to 20 Tons (60 Hz Data) Modular Floor Mounted Precision Air Conditioners Dual Compressor DX & Chilled Water Systems!
- Page 2 and 3: Stulz Air Technology Systems, Inc.
- Page 4 and 5: 2-1 ModulAiR Advantages ModulAiR A/
- Page 6 and 7: Application Dependent Configuration
- Page 8 and 9: Model Nomenclature Specifications N
- Page 10 and 11: Guide Specifications - Standard Equ
- Page 12 and 13: Evaporator Air Outlet Guide Specifi
- Page 14 and 15: Microprocessor Controls - A-Tech-20
- Page 16 and 17: Microprocessor Controls - A-Tech-20
- Page 18 and 19: Optional Features - Guide Specifica
- Page 20 and 21: Optional Features - Guide Specifica
- Page 22 and 23: Air Cooled - 7 to 20 Ton “MCS”
- Page 24 and 25: Water Cooled - 7 to 20 Ton "MCS" Pe
- Page 26 and 27: Glycol Cooled - 7 to 20 Ton "MCS" P
- Page 28 and 29: Chilled Water - 7 to 20 Ton "MCS" P
- Page 30 and 31: Chilled Water - 42°F EWT, 0% Glyco
- Page 32 and 33: Electrical Data - "ModulAiR" DX Com
- Page 34 and 35: 7 to 10 Ton MCS - "Down-Flow" Air P
- Page 36 and 37: 16 to 20 Ton MCS - "Down-Flow" Air
- Page 38: Air Cooled - Remote Outdoor DX Cond
<strong>Engineering</strong><br />
<strong>Manual</strong><br />
<strong>From</strong> 7 to <strong>20</strong> <strong>To</strong>ns<br />
(60 Hz Data)<br />
Modular Floor Mounted<br />
Precision <strong>Air</strong> Conditioners<br />
Dual Compressor DX &<br />
Chilled Water Systems!
<strong>Stulz</strong> <strong>Air</strong> Technology Systems, <strong>Inc</strong>. (SATS)<br />
Founded in 1947, STULZ acquired <strong>Air</strong> Technology Systems<br />
(ATS) in March <strong>20</strong>01, naming the new company<br />
<strong>Stulz</strong> <strong>Air</strong> Technology Systems, <strong>Inc</strong>. (SATS). SATS is<br />
dedicated to providing innovative solutions for critical<br />
temperature and humidity control needs. SATS designs<br />
and manufactures specialized environmental<br />
control equipment for commercial, industrial and custom<br />
military applications. SATS serves a diverse marketplace<br />
- including telecommunications, information<br />
technology, medical, financial, educational, industrial<br />
process and government contracts - utilizing worldclass<br />
"island" manufacturing processes in a modern,<br />
150,000 ft 2 facility. The addition of SATS to the STULZ<br />
family of companies solidifies STULZ as a global leader<br />
in the precision air conditioning marketplace. SATS<br />
combines a global network of sales and service companies<br />
with an extensive factory engineering staff and<br />
highly flexible manufacturing resources dedicated to<br />
providing world-class quality, innovation and customer<br />
service.<br />
ISO-9001 Quality Registered<br />
SATS operates in an ISO-9001 registered quality control<br />
environment. Each employee of SATS is committed<br />
to satisfying our customer expectations with the<br />
highest level of consistent, measurable and continuous<br />
quality improvement.<br />
CyberAiR - Precision A/C's<br />
SATS CyberAiR air conditioners provide precision temperature<br />
and/or humidity control for computer rooms and<br />
other critical areas where 24/7 continuous operation is required.<br />
With an extensive installation base, SATS has<br />
earned a solid reputation as a quality supplier and leader in<br />
its field.<br />
ModulAiR modular vertical,<br />
floor mounted A/C's are created by<br />
combining quantity two CyberONE<br />
single compressor 3.5, 5, 8 or 10<br />
ton systems to create quantity one<br />
dual compressor 7, 10, 16 or <strong>20</strong><br />
ton system. The result is a large<br />
tonnage system in a very compact<br />
foot-print that solves difficult rigging<br />
applications. ModulAiR systems<br />
are designed for 100% front service access and are<br />
available with a wide range of options to handle a variety of<br />
precision cooling applications. Typical applications include:<br />
INDUSTRIES:<br />
• Telecommunications<br />
• Internet / Web Hosting<br />
• Financial / Banking<br />
• Insurance<br />
• Legal Services<br />
• <strong>Air</strong>lines / Mass Transit<br />
• Entertainment<br />
• Government<br />
• Colleges / Universities<br />
APPLICATIONS:<br />
• Computer / LAN Rooms<br />
• Telecommunications Rooms<br />
• Colocation Centers<br />
• ISP (Internet Service Providers)<br />
• ASP (Applications Service Providers)<br />
• Copier / Fax Rooms<br />
• ATM Bank Centers<br />
• Hospital Operating & Isolation Rooms<br />
• Laboratories<br />
1-1
Table of Contents<br />
SECTION - 1<br />
Introduction to SATS ........................................................... 1-1<br />
Table of Contents ............................................................... 1-2<br />
ModulAiR SYSTEMS:<br />
SECTION - 2<br />
Outstanding Advantages ..................................................... 2-1<br />
User Oriented Features & Options ..................................... 2-2<br />
Available Configurations .................................................. 2-3/4<br />
MODEL NOMENCLATURE:<br />
Model Nomenclature Chart ................................................. 2-4<br />
Model Nomenclature Specifications .................................... 2-5<br />
SECTION - 3<br />
GUIDE SPECIFICATIONS:<br />
Standard Features Index ..................................................... 3-1<br />
Standard Guide Specifications ......................................... 3-2/4<br />
SECTION - 6<br />
DIMENSIONAL / INSTALLATION DRAWINGS:<br />
Standard ModulAiR "MCS" Systems:<br />
7 to 10 <strong>To</strong>n, Up-Flow Systems ........................................... 6-1<br />
7 to 10 <strong>To</strong>n, Down-Flow Systems ...................................... 6-2<br />
16 to <strong>20</strong> <strong>To</strong>n, Up-Flow Systems ......................................... 6-3<br />
16 to <strong>20</strong> <strong>To</strong>n, Down-Flow Systems .................................... 6-4<br />
Remote <strong>Air</strong> Cooled Condensers/Condensing:<br />
Outdoor Remote Condensers ............................................ 6-5<br />
SATS PRODUCTS:<br />
BACK COVER<br />
CeilAiR - Supplemental Ceiling A/C's ................... Back-Cover<br />
FLAiR - Floor Console Precision A/C's ................ Back-Cover<br />
CyberAiR - Vertical Floor Precision A/C's<br />
CyberONE ....................................................... Back-Cover<br />
ModulAiR .......................................................... Back-Cover<br />
CyberTWO ....................................................... Back-Cover<br />
Optional Features Index...................................................... 3-5<br />
A-Tech-<strong>20</strong> Microprocessor Controls Specifications .......... 3-6/9<br />
Optional Features Guide Specifications ....................... 3-10/13<br />
SECTION - 4<br />
PERFORMANCE / CAPACITY SPECIFICATIONS:<br />
DX - <strong>Air</strong> Cooled Systems ................................................. 4-1/2<br />
DX - Water Cooled Systems ........................................... 4-3/4<br />
DX - Glycol Cooled Systems ........................................... 4-5/6<br />
Chilled Water Systems .................................................. 4-7/10<br />
SECTION - 5<br />
ELECTRICAL DATA: (FLA / MCA / MFS)<br />
DX - Compressorized Systems:<br />
<strong>Air</strong> Cooled, Split Systems ................................................... 5-1<br />
Water Cooled Systems ...................................................... 5-1<br />
Glycol Cooled Systems ...................................................... 5-1<br />
Remote <strong>Air</strong> Cooled Condensers:<br />
Indoor & Outdoor Condensers ............................................ 5-1<br />
Chilled Water <strong>Air</strong> Handling Systems:<br />
Chilled Water Systems ....................................................... 5-2<br />
1-2
2-1<br />
ModulAiR Advantages<br />
ModulAiR A/C’s are created by combining quantity<br />
two CyberONE single compressor 3.5, 5, 8 or 10 ton<br />
systems to create quantity one dual compressor 7, 10, 16<br />
or <strong>20</strong> ton system. The result is a large tonnage system in<br />
a very compact foot-print that solves difficult rigging<br />
applications.<br />
Small Elevator? Easy Rigging:<br />
Many service elevators are too small to accomodate the<br />
rigging of typical 1-piece computer room A/C cabinet. As<br />
a result, the historical solution to this rigging problem, has<br />
been to field “cut-down and disassemble”, and then field<br />
“reassemble” the air conditioner. This historical approach<br />
is not only time consuming and costly to the owner, it is<br />
also very risky to the long-term reliable operation of the<br />
air conditioner. ModulAiR units are designed to be the<br />
cost saving, reliable solution to these difficult rigging<br />
problems.<br />
ModulAiR Systems Offer Outstanding Benefits<br />
Flexibility<br />
A wide variety of types are available to meet your unique<br />
requirements.<br />
• DX - <strong>Air</strong> Cooled<br />
• DX - Water Cooled<br />
• DX - Glycol Cooled (w/ Remote Drycoolers &<br />
Pump Packages<br />
• Chilled Water <strong>Air</strong> Handling Units<br />
Versatility<br />
• Plenum Box Spot Cooling & Ducted systems<br />
• Self-Contained & Split systems<br />
• Modular design permits installation and rigging<br />
through small passage ways<br />
100% Front Service Access<br />
Designed for 100% Front Only Access, ModulAiR<br />
systems require minimal floor space and are easily<br />
tucked into a corner or between cabinets.<br />
Wide Size Range<br />
7 to <strong>20</strong> tons capacity in four incremental sizes.<br />
Non-Proprietary Parts<br />
ModulAiR systems incorporate non-proprietary components<br />
where possible. Most major HVAC, refrigeration<br />
and electrical distributors stock an exact model cross<br />
reference or an alternate to most factory provided<br />
components.<br />
Microprocessor Controls<br />
Precision temperature and/or humidity control with<br />
unrivaled, user-friendly A-Tech-<strong>20</strong> series controls, offer a<br />
wide range of functions and alarms.<br />
Complete Temperature & Humidity<br />
Control<br />
• Electrode Canister Steam Humidification<br />
• Dehumidification Mode with Electric Reheat<br />
Capacity Modulation Options<br />
• Hot Gas Bypass Systems<br />
• Multistage Electric Reheat/Heat<br />
• Modulating Chilled Water Valves (Standard)<br />
Code (UL / CSA) Conformance<br />
NRTL<br />
LISTED<br />
C<br />
Listing E11<strong>20</strong>43<br />
R<br />
+<br />
Complies With<br />
UL 1995<br />
CSA C22.2 No. 236<br />
Heating & Cooling Equipment<br />
=<br />
The compact, 100% front-access ModulAiR 16 & <strong>20</strong> ton<br />
systems have a total installed foot-print of 79.12” wide x<br />
34.0” deep. Comparing, the industry’s historical <strong>20</strong>-ton<br />
DX precision air conditioner has a foot-print of 100” wide x<br />
34” deep. For the owner, that means an additional 22 ft 2 of<br />
useable data center floor space!<br />
• BMS Connection<br />
• Multi-Unit Sequencing<br />
• Digital & Analog Output<br />
... and more!<br />
- NYC MEA Approved (MEA-163-88-E)<br />
- CSA Compliance / Chicago Code Approved
User Oriented Features & Options<br />
Scroll Compressors<br />
ModulAiR DX A/C's incorporate<br />
Scroll Compressor Technology.<br />
Scroll Compressors provide higher<br />
efficiency, higher reliability and<br />
lower sound power than other<br />
compressor technologies.<br />
24/7 Year Round Operation<br />
Option offerings available with ModulAiR A/C's allow for<br />
year-round, 24 hrs-a-day A/C operation in any environment<br />
in the world:<br />
Low Ambient Control (DX - <strong>Air</strong> Cooled)<br />
• -<strong>20</strong>°F Variable Fan Speed<br />
• -30°F Flooded Head Pressure<br />
Modular Motor Controllers<br />
ModulAiR systems incorporate<br />
modular motor controllers with<br />
motor circuit breakers in lieu of<br />
inconvenient replaceable fuses,<br />
eliminating the need for ANY<br />
motor fusing.<br />
Quiet Operation<br />
Low sound power Scroll compressors coupled with low<br />
RPM blowers, acoustically lined cabinets and low velocity<br />
grilles provide the optimum in quiet operation.<br />
Warranty<br />
- 1 Year Parts Standard<br />
- Optional 5 Year Compressor<br />
100% Front Access<br />
(Saves a Minimum 18 ft 2 Floor Space)<br />
Selected Standard Features:<br />
• Main Power Non-Fused Disconnect Switch<br />
• Modular Motor Controllers (w/ motor circuit breakers)<br />
• Acoustical / Thermal Insulation<br />
• Aluminum Finned / Copper Tube Coils<br />
• Thermal Expansion Valve<br />
• Refrigerant Sight Glass<br />
• Filter / Drier Strainer<br />
• Liquid Refrigerant Reclaim Valves<br />
• Non-Corroding Stainless Steel or Polymer Drain Pan<br />
• High / Low Pressure Switches<br />
Other Available Options:<br />
ModulAiR<br />
(Model MCS-240-DAR-D Shown)<br />
- 2 & 3-way Grilled Plenum Boxes<br />
- Floor Stands (with & without turning vanes, seismic)<br />
- Condensate Pumps<br />
- Firestats<br />
- Smoke Detectors<br />
- Water Leak Detectors<br />
- High Static Belt-Drive Blowers<br />
- Special High Efficiency Filtration<br />
(2" & 4" Filters up-to 60% Dust Spot)<br />
- High Pressure DX - Water/Glycol Cooled<br />
Condenser Regulating Valves<br />
- Drycoolers & Pump Packages<br />
- Many more options available (see page 3-5)!<br />
2-2
Application Dependent Configuration Choices<br />
ModulAiR<br />
Configurations<br />
+<br />
=<br />
AIR COOLED SYSTEMS<br />
SPLIT AIR COOLED<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
WATER COOLED SYSTEMS<br />
SELF-CONTAINED<br />
WATER COOLED SYSTEMS<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
HES-( )-DL()A<br />
(Remote Outdoor<br />
Propeller Condenser)<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Remote Water Source<br />
(supplied by others)<br />
MCS-084 thru 240-DAR-( )<br />
(ModulAiR, Split Evaporator)<br />
(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />
MCS-084 thru 240-DW-( )<br />
(ModulAiR, Self-Contained)<br />
(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />
GLYCOL COOLED SYSTEMS<br />
SELF-CONTAINED<br />
GLYCOL COOLED SYSTEMS<br />
CHILLED WATER SYSTEMS<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
HES-()-LGA / GPS-( )<br />
(Outdoor Propeller Drycooler & Pump Package)<br />
Remote Liquid Chiller<br />
(supplied by others)<br />
MCS-084 thru 240-DW-( )<br />
(ModulAiR, Self-Contained)<br />
(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />
MCS-084 thru 240-C-( )<br />
(ModulAiR, Self-Contained, <strong>Air</strong> Handler)<br />
(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />
2-3
Flexible <strong>Air</strong> Pattern Configuration Choices<br />
Down-Flow Systems:<br />
<strong>To</strong>p "Free" Return with:<br />
<strong>To</strong>p "Ducted" Return with:<br />
1 2<br />
Bottom Discharge<br />
Into Raised Floor<br />
Up-Flow Systems:<br />
<strong>To</strong>p Discharge Through 2 or 3-<br />
Way Grilled Plenum Box with:<br />
Floor Stand<br />
(Optional)<br />
Bottom Discharge<br />
Into Raised Floor<br />
<strong>To</strong>p "Ducted" Discharge with:<br />
3 4<br />
Front "Free" Return<br />
Front "Free" Return<br />
Model Nomenclature<br />
MCS-240-DG-U<br />
D = Down-Flow <strong>Air</strong> Pattern<br />
U = Up-Flow <strong>Air</strong> Pattern<br />
MCS= Modular Cyber System<br />
HES = Heat Exchanger System<br />
GPS = Glycol Pump System<br />
Nominal Capacity in 1,000's of BTU/H<br />
AR = Remote (Split) <strong>Air</strong> Cooled<br />
C = Chilled Water System<br />
CAA = Indoor Centrifugal Condenser<br />
D( ) = Dual (Two) Circuit or Pump System<br />
G = Glycol Cooled<br />
LSA = Outdoor Propeller Condenser for -<strong>20</strong>°F<br />
LFA = Outdoor Propeller Condenser for -30°F<br />
LGA = Outdoor Propeller Glycol Drycooler<br />
S = Single Pump<br />
W = Water Cooled<br />
2-4
Model Nomenclature Specifications<br />
Nomenclature - ModulAiR System Model Specifications<br />
"ModulAiR"<br />
Model Nomenclature<br />
Guide Specifications<br />
DX - EVAPORATOR SECTIONS<br />
<strong>Air</strong> Cooled Remote Evaporator<br />
(Models MCS-( )-DAR)<br />
The system shall be a remote (split)<br />
air cooled, floor mounted precision air<br />
conditioner evaporator. The evaporator<br />
section shall house, as a minimum,<br />
the evaporator coil, expansion valve,<br />
compressor, evaporator blower/motor<br />
and associated electrical and refrigeration<br />
components.<br />
The MCS-( )-DAR evaporator section<br />
shall be located at some distance from<br />
its corresponding SATS model HES-(<br />
)-DHCA/DVCA indoor or HES-( )-<br />
DL()A outdoor air cooled condenser.<br />
The evaporator system shall require<br />
only single point main power supply<br />
connection; and the system shall ship<br />
from the SATS factory with a dry<br />
nitrogen holding charge ready for field<br />
refrigerant (R-22) charging.<br />
DX - AIR COOLED CONDENSERS<br />
Remote Indoor Centrifugal<br />
(Models HES-( )-DHCA / DVCA)<br />
The system shall be a remote indoor<br />
ceiling mounted air cooled condenser<br />
with centrifugal blower. The condenser<br />
cabinet shall house the<br />
condenser coil, blower and blower<br />
motor, receivers (if applicable) and<br />
condenser motor control / enabling<br />
box. The compressor(s) shall be<br />
located with the MCS-( )-DAR<br />
evaporator section.<br />
The condenser shall be sized to<br />
provide the total heat of rejection of<br />
the system at a 95°F DB ambient<br />
temperature for the corresponding<br />
ModulAiR model MCS-( )-DAR<br />
evaporator.<br />
Remote Outdoor Propeller<br />
(Models HES-( )-DL()A)<br />
The system shall be a remote outdoor<br />
air cooled condenser with directdriven<br />
propeller fan(s). The condenser<br />
cabinet shall house the<br />
condenser coil, fan(s) and fan<br />
motor(s) and Nema 3R condenser<br />
motor control / enabling box. The<br />
compressor(s) shall be located with<br />
the MCS-( )-DAR evaporator section.<br />
The condenser shall be sized to<br />
provide the total heat of rejection of<br />
the system at a 95°F DB ambient<br />
temperature for the corresponding<br />
ModulAiR model MCS-( )-DAR<br />
evaporator.<br />
Note: The outdoor propeller condensers<br />
are model designated as follows:<br />
HES-( )-DLSA:<br />
Low Ambient Head Pressure Control down<br />
to a minimum ambient temperature of -<br />
<strong>20</strong>°F via Variable Fan Speed Head<br />
Pressure Control.<br />
HES-( )-DLFA:<br />
Low Ambient Head Pressure Control down<br />
to a minimum ambient temperature of -<br />
30°F via Flooded Head Pressure<br />
Control.<br />
DX - WATER COOLED SYSTEMS<br />
Integral Self-Contained<br />
(Models MCS-( )-DW)<br />
The system shall be a self-contained,<br />
floor mounted precision air conditioner<br />
to include integral water cooled,<br />
condenser with factory installed head<br />
pressure water regulating control<br />
valve(s). Condenser (source) water<br />
shall be provided by a cooling tower or<br />
some other remote water source.<br />
The system shall require only single<br />
point supply power connection and<br />
shall ship from the SATS factory with<br />
a full operating refrigerant (R-22)<br />
charge.<br />
Water Regulating Valves:<br />
Head pressure shall be automatically<br />
controlled by a factory installed 2-way<br />
water regulating valve rated for 150<br />
psig w.w.p.<br />
(Note: 3-way and high pressure valves<br />
are optionally available, page 3-11.)<br />
DX - GLYCOL COOLED SYSTEMS<br />
Integral Self-Contained<br />
(Models MCS-( )-DG)<br />
The system shall be a self-contained,<br />
floor mounted precision air conditioner<br />
to include integral glycol cooled,<br />
condenser with factory installed head<br />
pressure glycol regulating control<br />
valve(s). Condenser (source) glycol<br />
solution shall be provided via a SATS<br />
model GPS-( )-( ) / HES-( )-LGA<br />
remote glycol pump package and<br />
drycooler system.<br />
The system shall require only single<br />
point supply power connection and<br />
shall ship from the SATS factory with<br />
a full operating refrigerant (R-22)<br />
charge.<br />
Glycol Regulating Valves:<br />
Head pressure shall be automatically<br />
controlled by a factory installed 2-way<br />
glycol regulating valve rated for 150<br />
psig w.w.p.<br />
(Note: 3-way and high pressure valves<br />
are optionally available, page 3-11.)<br />
CHILLED WATER AIR HANDLERS<br />
CHILLED WATER SYSTEM<br />
(Models MCS-( )-C)<br />
The system shall be a floor mounted<br />
chilled water precision air conditioner<br />
to include chilled water cooling coil,<br />
evaporator blower and motor and<br />
chilled water control valve. Chilled<br />
water shall be provided by a remote<br />
liquid chiller system.<br />
Chilled Water Control Valve:<br />
Cooling capacity shall be controlled<br />
with a factory installed 3-way modulating<br />
(0-10 Vdc) control valve rated for<br />
400 psig.<br />
(Note: 2-way modulating valves are<br />
optionally available, page 3-11.)<br />
2-5
Selected Standard Features - "MCS" Series<br />
"MCS" Model MCS-084/1<strong>20</strong>-( ) MCS-192/240-( )<br />
SELECTED STANDARD FEATURES:<br />
TEMPERATURE CONTROL<br />
• 2-Stage Cooling Mode Standard Standard<br />
• 1-Stage Electric Reheating / Heating Standard Standard<br />
• 2-Stage Electric Reheating / Heating Optional Optional<br />
• Cooling &/or Heating Only (No Humidity Control) Optional Optional<br />
HUMIDITY CONTROL<br />
• Electrode Canister Steam Humidifier Standard Standard<br />
• Dehumidification Mode with 1-Stage Electric Reheat Standard Standard<br />
CONTROLS<br />
• A-Tech-<strong>20</strong> Advanced Micropressor w/ Alarms Standard Standard<br />
CABINET<br />
• Powder Coat Painted Galvanneal Steel Standard Standard<br />
• Insulated Stainless Steel or Polymer Condensate Drain Pan Standard Standard<br />
• 2 lb Density Thermal & Sound Insulation Standard Standard<br />
• Floor Stand (Adjustable, turning vanes optional) Optional Optional<br />
FILTERS / PLENUMS<br />
• 2", 30% Dust Spot Eff. Pleated Filters Standard N/A<br />
• 4", 30% Dust Spot Eff. Pleated Filters Optional Standard<br />
• 2 or 3-way Plenum Box (Up-Flow Units) Optional Optional<br />
DX-REFRIGERATION CIRCUIT<br />
• CFC-Free R22 Refrigerant Standard Standard<br />
• Scroll Compressors w/ Rotolock Service Valves Standard Standard<br />
• High Efficiency, Aluminum Fin / Copper Tube Coils Standard Standard<br />
• Thermal Expansion Valves Standard Standard<br />
• Refrigerant Sight Glasses & Filter/Drier Strainers Standard Standard<br />
• Refrigerant Service Valves Standard Standard<br />
BLOWERS / MOTORS<br />
• Belt-Drive Evaporator Blower / Motor Standard Standard<br />
ELECTRICAL<br />
• 3-Phase Power Supply - - - See Electrical Tables Section 5 - - -<br />
• Multi-Voltage Control Transformer (24V Class 2) Standard Standard<br />
• Modular Motor Controllers with Integral Circuit Breakers Standard Standard<br />
SAFETY FEATURES<br />
• A-Tech-<strong>20</strong> Audible/Visual Local & Remote Alarms Standard Standard<br />
• Main Power Non-Fused Disconnect, unit mounted Standard Standard<br />
• High / Low Refrigerant Pressure Switches (DX units) Standard Standard<br />
• Motor Overload Protection Standard Standard<br />
SPECIFIC MODEL STANDARD FEATURES:<br />
AIR COOLED<br />
• Low Ambient Head Pressure Control - - - - Two types -<strong>20</strong>°F or -30°F - - - -<br />
• Remote <strong>Air</strong> Cooled Condenser Standard Standard<br />
WATER / GLYCOL COOLED<br />
• 2-way, 150 psig Water/Glycol Regulating Valves Standard Standard<br />
• High Pressure &/or 3-way Valves Optional Optional<br />
• Coaxial, Tube-in-Tube Heat Exchanger Standard N/A<br />
• Stainless Steel Brazed Plate Heat Exchanger N/A Standard<br />
ALL SPLIT DX SYSTEMS<br />
• Liquid Line Solenoid Valve to Prevent Liquid Slugging Standard Standard<br />
CHILLED WATER SYSTEMS<br />
• 3-way, 300 psig Modulating (0-10 Vdc) Valve Standard N/A<br />
• 3-way, 400 psig Modulating (0-10 Vdc) Valve Optional Standard<br />
• 2-way, Modulating (0-10 Vdc) Valve Optional Optional<br />
Guide Specifications - Standard Features "Quick-Reference" Table<br />
CODE CONFORMANCE<br />
• NRTL Conformance Compliance to UL 1995 Standard Standard Standard<br />
• CSA / NYC MEA-163-88-E / Chicago Code Approval Standard Standard<br />
3-1
Guide Specifications - Standard Equipment<br />
Guide Specifications - Standard Equipment<br />
QUALITY ASSURANCE<br />
(ISO-9001 Registered)<br />
SATS operates in an ISO-9001<br />
registered quality control environment.<br />
Each SATS employee is<br />
committed to satisfying his or her<br />
customer expectations with the<br />
highest level of consistent, measurable<br />
and continuous quality<br />
improvement.<br />
GENERAL GUIDE<br />
SPECIFICATION<br />
General Description<br />
+<br />
=<br />
The system shall be a floor mounted<br />
air conditioner designed and built to<br />
provide precision temperature and<br />
humidity control. The system shall<br />
be complete and factory run-tested<br />
before shipment. The system shall<br />
be MET Laboratory (an NRTL) listed<br />
and labeled in compliance with UL<br />
1995 and CSA C22.2 No. 236. The<br />
system shall be MEA NYC approved<br />
(MEA-163-88-E).<br />
The system shall be manufactured<br />
by <strong>Stulz</strong> <strong>Air</strong> Technology Systems,<br />
<strong>Inc</strong>. in Frederick, Maryland, USA.<br />
100% Front Access<br />
The air conditioner shall require front<br />
only access for all routinely<br />
maintenanced components. No<br />
allowance for side service access<br />
shall be required, however, removable<br />
side access shall be provided<br />
for additional access.<br />
Cabinet Construction<br />
The cabinet and access panels shall<br />
be fabricated from heavy gauge<br />
galvannealed steel and powder-coat<br />
paint processed for decor matching<br />
and corrosion protection. The<br />
panels shall be lined with 2 lb/ft 2 high<br />
density sound and thermal insulation<br />
and sealed with self-extinguishing<br />
gasketing conforming to NFPA 90A<br />
and 90B.<br />
Electrical System<br />
Modular Motor Controllers<br />
The system shall incorporate modular<br />
motor controllers utilizing motor<br />
start protectors and circuit breakers<br />
eliminating the need for fusing, as<br />
well as providing:<br />
• Motor branch circuit short circuit<br />
protection<br />
• Motor load switching controllers<br />
(contactors)<br />
• Motor overload protection<br />
The system shall incorporate overcurrent<br />
and overload protection in<br />
accordance with UL 1995 requirements.<br />
Each blower motor, compressor,<br />
electric heater stage and<br />
humidifier (if applicable) shall be<br />
provided with a factory mounted and<br />
wired starter / contactor.<br />
The control circuit shall be a 24 VAC<br />
Class 2 low voltage circuit including<br />
a circuit breaker for protection. Low<br />
voltage, high voltage and grounding<br />
wires shall be color coded and shall<br />
be individually numbered at each<br />
end for ease of service tracing. All<br />
wiring shall be in accordance with<br />
the National Electric Code (NEC).<br />
Main Power - Electric<br />
Non-Fused Service Switch<br />
As a factory standard, a unit<br />
mounted main power service switch<br />
shall be provided. The service<br />
switch shall be a dust-proof, nonfused<br />
type with lockable handle.<br />
Evaporator Coils<br />
Evaporator systems shall be configured<br />
for a draw-thru air pattern to<br />
provide uniform air distribution over<br />
the evaporator coil face. The coils<br />
shall be seamless drawn copper<br />
tubes, mechanically bonded to<br />
tempered aluminum fins with fin<br />
pattern designed for maximum heat<br />
transfer. Coil end plates shall be hot<br />
dipped galvanized.<br />
The evaporator coil shall be mounted<br />
in an insulated polymeric or<br />
stainless steel condensate drain pan,<br />
depending on unit model size.<br />
DX-Refrigeration System<br />
Thermal Expansion<br />
Valves<br />
Filter Drier/<br />
Strainers<br />
Sight Glasses<br />
All refrigeration piping shall be<br />
refrigerant grade tubing. Each<br />
refrigerant circuit shall include, as a<br />
minimum, refrigerant drier/strainer,<br />
sight glass with moisture detector,<br />
3-2
Guide Specifications - Standard Equipment<br />
thermal expansion valve with rapid<br />
bleed port feature and external<br />
equalizer, evaporator coil, compressor,<br />
high pressure switch with<br />
manual reset and a low pressure<br />
switch with automatic reset.<br />
Split / Remote systems shall have a<br />
liquid line solenoid for refrigerant<br />
isolation to prevent liquid slugging. All<br />
high pressure joints shall be brazed,<br />
and the entire system shall be<br />
pressure tested at the factory with<br />
dry nitrogen, evacuated to at least 50<br />
microns and fully charged with<br />
refrigerant.<br />
Note: All split / remote DX systems<br />
ship with a dry nitrogen holding charge.<br />
All self-contained DX systems ship with a<br />
full refrigerant (R-22) operating charge.<br />
Scroll Compressors<br />
Each compressor shall be a high<br />
efficiency, high reliability and low<br />
sound Scroll Compressor.<br />
The compressor shall be complete<br />
with charging and service schraeder<br />
ports, internal vibration isolation,<br />
internal thermal overloads, internal<br />
pressure relief valve, internal discharge<br />
gas vibration eliminator and<br />
external vibration mounting isolation.<br />
Chilled Water System<br />
(Models MCS-( )-C)<br />
Cooling Coil:<br />
The chilled water coil shall be<br />
constructed of seamless drawn<br />
copper tubes, mechanically bonded<br />
to tempered aluminum fins for<br />
maximum heat transfer. Coil end<br />
plates shall be hot dipped galvanized.<br />
The cooling coil shall be mounted in<br />
an insulated stainless steel condensate<br />
drain pan.<br />
CW Control Valve:<br />
Cooling capacity shall be controlled<br />
by a factory installed 3-way, modulating<br />
(0-10 Vdc) control valve rated<br />
for a maximum 300 psig w.w.p. (7 to<br />
10 <strong>To</strong>n) and 400 psig w.w.p. (16 to<br />
<strong>20</strong> <strong>To</strong>n).<br />
Note: 2-way valves are optionally<br />
available, page 3-11.<br />
Blowers / Motors<br />
Belt Driven Systems<br />
The blower(s) shall be belt driven<br />
with double width, double inlet<br />
housing and forward curved blades<br />
and permanently lubricated ball<br />
bearings sized for an average<br />
100,000 hours of service life. The<br />
blowers shall be dynamically and<br />
statically balanced to minimize<br />
vibration and operate in the Class I<br />
range.<br />
The blower(s) shall have an adjustable<br />
base for belt tensioning and a<br />
locking system to prevent the motors<br />
from moving. The motors’ drive<br />
sheaves shall have an adjustable<br />
pitch to change the speed of the<br />
blowers. The motor(s) shall be 1725<br />
RPM and shall have overload protection<br />
and a minimum NEMA service<br />
factor of 1.15.<br />
Temp & Humid Control<br />
The standard ModulAiR floor A/C<br />
includes the A-Tech-<strong>20</strong> Advanced<br />
Microprocessor Controller, Canister<br />
Steam Humidifier and Dehumidification<br />
Mode with Electric Reheat/Heat<br />
providing precision temperature and<br />
humidity control.<br />
A-TECH-<strong>20</strong><br />
(Microprocessor Controller w/ Alarms)<br />
Control shall be provided by SATS'<br />
Advanced A-Tech-<strong>20</strong> Microprocessor<br />
temperature and humidity controller with<br />
alarms. The user friendly A-Tech-<strong>20</strong><br />
shall provide both local & remote alarm<br />
indication, if applicable, for:<br />
• High Temperature • Loss of <strong>Air</strong> Flow<br />
• Low Temperature • Loss of Power<br />
• High Humidity • Dirty Filter<br />
• Low Humidity • Leak Detection<br />
• High Head Press • Smoke Detection<br />
• Low Suction Press • Firestat<br />
Electrode Canister Steam<br />
Humidifier<br />
The humidifier shall<br />
be an electrode<br />
steam canister type.<br />
<strong>Manual</strong>ly adjustable<br />
ON/OFF steam<br />
output shall be<br />
standard.<br />
Dehumidification Mode<br />
A Dehumidification<br />
mode with<br />
Electric Reheat/<br />
Heat shall be<br />
incorporated as<br />
standard.<br />
(Note: Please refer to pages 3-5 thru 3-10<br />
of this brochure for more specification<br />
details on all ModulAiR Temperature and<br />
Humidity Control Options.)<br />
Guide Specifications - Standard Equipment<br />
3-3
Evaporator<br />
<strong>Air</strong> Outlet<br />
Guide Specifications - Standard Equipment<br />
Guide Specifications - Standard Equipment<br />
Evaporator <strong>Air</strong> Patterns<br />
DOWN-FLOW:<br />
(MCS-( )-( )-D)<br />
The air conditioner shall be configured<br />
for a down-flow air pattern with<br />
free evaporator return air to the top<br />
and conditioned supply air discharge<br />
through bottom of the A/C into the<br />
raised floor. (Floor Stands are<br />
optionally available, page 3-11.)<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Down-Flow<br />
<strong>Air</strong> Pattern<br />
(A top 1" flanged return air duct connection<br />
is optionally available.)<br />
UP-FLOW:<br />
(MCS-( )-( )-U)<br />
The air conditioner shall be configured<br />
for an up-flow air pattern with<br />
free evaporator return air through<br />
front filtered grille and conditioned<br />
supply air through the top of the unit.<br />
Up-Flow<br />
<strong>Air</strong> Pattern<br />
DX - Heat Rejection<br />
AIR COOLED<br />
(Note: Please refer to page 3-11, for<br />
specification details of ModulAiR air<br />
cooled condenser "Low Ambient Control"<br />
options: -<strong>20</strong>°F & -30°F)<br />
Outdoor - Remote Condensers<br />
(Models HES-( )-DL()A Evaporator)<br />
The system shall be a remote<br />
outdoor air cooled condenser with<br />
direct-driven propeller fan(s). The<br />
condenser shall be sized to provide<br />
the total heat of rejection of the<br />
system at a 95°F DB ambient<br />
temperature for the corresponding<br />
model MCS-( )-DAR DX evaporator.<br />
Indoor - Remote Condensers<br />
(Models HES-( )-DHCA / DVCA)<br />
The system shall be a remote indoor<br />
ceiling mounted air cooled condenser<br />
with centrifugal blower. The<br />
condenser shall be sized to provide<br />
the total heat of rejection of the<br />
system at a 95°F DB ambient<br />
temperature for the corresponding<br />
model MCS-( )-DAR DX evaporator.<br />
SS Brazed-Plated:<br />
(Models MCS-192/240-DW/DG)<br />
Each evaporator refrigerant circuit<br />
shall be provided with a factory<br />
installed single pass, counterflow<br />
configured brazed plate heat<br />
exchanger, with integral subcooler,<br />
constructed of type 316 stainless<br />
steel; designed and tested for a 450<br />
psig. w.w.p.<br />
2-Way, 150 psig Regulating Valve<br />
(Standard on all MCS-( )-DW/G)<br />
Each refrigerant circuit's head<br />
pressure shall be controlled by a<br />
factory installed 2-way water / glycol<br />
regulating valve rated for 150 psig.<br />
w.w.p.<br />
(Note: 3-way and high pressure water/<br />
glycol regulating valves are optionally<br />
available, page 3-11.)<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
WATER / GLYCOL COOLED<br />
(A top 1" flanged duct connection shall be<br />
provided as a standard. 2 & 3-way top<br />
discharge plenum boxes are optionally<br />
available, page 3-12.)<br />
<strong>Air</strong> Filtration<br />
The A/C shall have slide out, ___"<br />
deep, class 2 (per U.L. Standard<br />
900) filters. The filters shall be<br />
easily accessed through a front<br />
access door. The filters shall have<br />
an efficiency rating of at least, 30%<br />
dust-spot as measured by ASHRAE<br />
Standard 52-76 test method.<br />
Water/Glycol Cooled<br />
Condensers<br />
Coaxial Tube-In-Tube:<br />
(Models MCS-084/1<strong>20</strong>-DW/DG)<br />
Each evaporator refrigerant circuit<br />
shall be provided with a factory<br />
installed single pass, counterflow<br />
configured, tube-in-tube coaxial<br />
condenser; designed and tested for<br />
a 450 psig. w.w.p.<br />
3-4
Optional Features - Guide Specifications<br />
Optional Features Index<br />
OPTION ................................................... page<br />
Microprocessor Controls<br />
• A-Tech-<strong>20</strong> Microprocessor (standard) ............... 3-6/9<br />
• CyberLAN Networking Options ......................... 3-8/9<br />
- Multi-Unit "N+1" Sequencing.............................. 3-8/9<br />
- Multi-Unit Capacity Assist-Mode ........................... 3-9<br />
- Remote BMS Communications ............................. 3-9<br />
Humidity Control Options<br />
• Steam Humidifier (standard) ................................ 3-10<br />
• Dehumidification Cycle<br />
- Electric Reheat / Heat (standard) ....................... 3-10<br />
High Static Pressure Blowers<br />
• High Static Belt-Drive Blower Upgrade ................... 3-10<br />
(Up to 2.0" ext. static pressure)<br />
High Efficiency Filtration (IAQ)<br />
• IAQ High Efficiency Filters .................................... 3-10<br />
Head Pressure Control Options<br />
DX - Capacity Modulation<br />
• Snap-Acting, Hot Gas Bypass ............................ 3-11<br />
Chilled Water Modulating Control Valves<br />
• 3-way, 300 & 400 psig, 0-10 Vdc (standard) ....... 3-11<br />
• 2-way, 300 & 400 psig, 0-10 Vdc ........................ 3-11<br />
ACCESSORIES<br />
• Floor Stands<br />
- Turning Vanes .................................................... 3-11<br />
- Seismic Floor Stand ........................................... 3-12<br />
• 2 or 3-Way Plenum Discharge Box .................... 3-12<br />
• Condensate Pump ............................................... 3-12<br />
• Smoke Detector ................................................... 3-12<br />
• Firestat ................................................................. 3-12<br />
• Remote Water Detector:<br />
- Qty. One, Spot Type ........................................... 3-12<br />
- Qty. Two, Spot Type ............................................ 3-12<br />
- 40 Ft. - Strip/Cable Type..................................... 3-12<br />
- Water Detector Auxiliary Contact ........................ 3-12<br />
• Acoustical Compressor Sound Jackets ........ 3-12/13<br />
Optional Features - Index<br />
<strong>Air</strong> Cooled - Low Ambient Control<br />
• -<strong>20</strong>°F Ambient .................................................... 3-11<br />
• -30°F Ambient .................................................... 3-11<br />
Water/Glycol Cooled - Regulating Valves<br />
• 2-way, 150 psig (standard) ................................. 3-11<br />
• 2-way, 350 psig .................................................. 3-11<br />
• 2-way, 450 psig .................................................. 3-11<br />
• 3-way, 150 psig .................................................. 3-11<br />
• 3-way, 350 psig .................................................. 3-11<br />
• 3-way, 450 psig .................................................. 3-11<br />
Glycol Pump Packages & Drycoolers<br />
• Glycol Pump Packages:<br />
- Single Pump Packages ...................................... 3-13<br />
- Dual Pump Packages ......................................... 3-13<br />
• Remote Drycoolers.............................................. 3-13<br />
3-5
Microprocessor Controls - A-Tech-<strong>20</strong><br />
Guide Specifications - Microprocessor Control Options<br />
A-Tech-<strong>20</strong> Series Controls:<br />
Advanced Microprocessor<br />
Temperature & Humidity<br />
Controller with Alarms<br />
The ModulAiR floor mounted air<br />
conditioner shall be provided with<br />
SATS' A-Tech-<strong>20</strong> Advanced Microprocessor<br />
based Temperature and<br />
Humidity controller with Alarms. The<br />
controller shall incorporate a "userfriendly"<br />
operating environment, to<br />
allow easy system setup and operation.<br />
DISPLAY / KEYPAD:<br />
Featuring an easy to read, 4 x <strong>20</strong><br />
character liquid-crystal alphanumerical<br />
display, the attractive unit<br />
mounted (standard) or remote<br />
mounted (optional) keypad/display,<br />
allows the operator to visually monitor<br />
and customize unit functions and<br />
settings. Self-explanatory, keypad<br />
nomenclature makes for easy<br />
location of system programming<br />
features.<br />
Performing simple functions such<br />
as adjusting the Temperature or<br />
Humidity set point are made obvious:<br />
Press TEMP SETPT or HUMID<br />
SETPT, ARROW UP or DOWN to<br />
adjust & press ENTER to accept.<br />
FIELD CONFIGURABLE:<br />
The A-Tech-<strong>20</strong> controller is field<br />
program configurable and capable of<br />
matching the unique needs of any<br />
data center, telecommunication or<br />
other critical area.<br />
Display/Sensor Options:<br />
Display Location Options:<br />
As a standard, the A-Tech-<strong>20</strong><br />
controller display is factory unit<br />
mounted to the front of the ModulAiR<br />
unit.<br />
Optionally, the A-Tech-<strong>20</strong> keypad/<br />
display can be shipped loose for<br />
remote wall mounting.<br />
Remote Display Cable Options:<br />
• 30 ft. cable length (standard option)<br />
• 75 ft. cable length<br />
• 150 ft. cable length<br />
Sensor Location Options:<br />
As a standard, the A-Tech-<strong>20</strong><br />
temperature and humidity sensor is<br />
factory unit mounted in the return air<br />
stream of the ModulAiR unit, after<br />
the filter(s).<br />
Optionally, the A-Tech-<strong>20</strong> temperature<br />
and humidity sensor can be<br />
shipped loose for remote wall<br />
mounting.<br />
Remote Sensor Cable Options:<br />
• 75 ft. cable length (standard option)<br />
• 150 ft. cable length<br />
Dual-Sensor Selection: (Optional)<br />
Through a menu selection option<br />
screen within the A-Tech-<strong>20</strong> controller,<br />
an automatic or a manual selection is<br />
available for local T/H sensor control or<br />
remote T/H sensor control. Typically,<br />
the local (standard) T/H sensor is<br />
factory unit mounted within the return<br />
air stream of the ModulAiR unit, while<br />
the remote (optional) T/H sensor is<br />
remote wall (or "sensor-tree")<br />
mounted.<br />
During automatic dual-sensor<br />
selection mode, A-Tech-<strong>20</strong> control<br />
logic shall compare T/H sensor input<br />
readings. The sensor reading that is<br />
the greater from setpoint will be used<br />
to control the unit's temperature and/<br />
or humidity output control devices.<br />
During manual dual-sensor selection<br />
mode, the user can manually select<br />
which sensor controls the unit.<br />
Remote Sensor Cable Options:<br />
The cable shall be type NEC CMP 2<br />
shielded twisted paired and comply<br />
with NEC Article 600 (UL: 150°C,<br />
300V) and c(UL)PCC FT 6 .<br />
• 75 ft. cable length (standard option)<br />
• 150 ft. cable length<br />
SYSTEM SETUP & ADJUSTMENTS:<br />
The A-Tech-<strong>20</strong> is completely factory<br />
preprogrammed, and therefore, most<br />
applications will require no field setup.<br />
However, the “default” set points and<br />
their ranges are easily adjusted from<br />
A-Tech-<strong>20</strong> kepad/display.<br />
The system is supplied with the<br />
following factory preprogrammed<br />
and field adjustable default settings:<br />
Temp/Humid Control:<br />
Temp Set Point<br />
72°F DB<br />
Humidity Set Point<br />
50% RH<br />
Heat/Cool Dead-Band 2°F DB<br />
Humid/Dehumid Dead-Band 5% RH<br />
Inter-stage Differential 1°F DB<br />
Alarms:<br />
High Temp Alarm<br />
Low Temp Alarm<br />
High Humid Alarm<br />
Low Humid Alarm<br />
Compressor Short Cycle:<br />
Cold-Start Time Delay<br />
Minimum ON Time<br />
Minimum OFF Time<br />
80°F DB<br />
60°F DB<br />
70% RH<br />
30% RH<br />
3 min<br />
2 min<br />
4 min<br />
3-6
Microprocessor Controls - A-Tech-<strong>20</strong><br />
UNIT STATUS DISPLAY:<br />
The A-Tech-<strong>20</strong> displays current unit<br />
functions and room status:<br />
• Current Dry Bulb Temp Set Point<br />
• Current Relative Humidity Set Point<br />
Current Unit Status: (if applicable)<br />
• System ON/OFF • Free Cooling<br />
• Cooling<br />
• AWS Cooling<br />
• Heating<br />
• Compr. Lock-Out<br />
• Humidifying • Capacity Assist<br />
• Dehumidifying • Standby Mode<br />
• Reheating • <strong>Manual</strong> Mode<br />
• Actual Room DB Temperature<br />
• Actual Room Relative Humidity<br />
Run Times<br />
The historical run-time in hours of<br />
the following major components is<br />
available directly from the A-Tech-<strong>20</strong><br />
keypad/display: (if applicable)<br />
• Evaporator Blower Motor<br />
• Compressor<br />
• Humidifier<br />
• Chilled Water Valve<br />
• Free-Cooling Valve<br />
• Alternate Water Source Valve<br />
ALARM CONDITIONS:<br />
Alarm conditions activate an audible<br />
and visual indicator, as well as, close<br />
a summary alarm dry contact<br />
connection. An alarm is acknowledged<br />
through the Alarm and Alarm<br />
Mute buttons located on the keypad<br />
display.<br />
The A-Tech-<strong>20</strong> alerts to the following<br />
alarm conditions (if applicable):<br />
• High Temperature • Dirty Filter<br />
• Low Temperature • Smoke Detection<br />
• High Humidity • Firestat<br />
• Low Humidity • Leak Detection<br />
• High Head Press • GC Pump Failure<br />
• Low Suction Press • Sensor Failure<br />
• Loss of <strong>Air</strong> Flow • Comm. Failure<br />
• Loss of Power<br />
The operator may select which<br />
alarms are active or inactive.<br />
Summary Alarm Contacts:<br />
• A user-configurable summary<br />
alarm dry-contact (n/o) connection<br />
is available for remote<br />
annunciation of an alarm condition.<br />
• An additional user-configurable<br />
custom alarm dry-contact is also<br />
available on most system configurations.<br />
Alarm History:<br />
The A-Tech-<strong>20</strong> controller provides<br />
users with a recorded history of the<br />
last 25 alarms, including the time and<br />
date of the alarm.<br />
CONTROL INPUTS / OUTPUTS:<br />
The A-Tech-<strong>20</strong> is capable of both<br />
digital (on/off) and analog (proportional<br />
integral, PI) input and output<br />
device control. Prior to shipment,<br />
each ModulAiR unit's A-Tech-<strong>20</strong> is<br />
factory program configured to match<br />
the unit's system operational requirements:<br />
Digital (On/Off) Outputs:<br />
• 2 (two) Cool (if applicable)<br />
• 2 (two) Reheat/Heat<br />
• 1 (one) Humidification<br />
Analog (0-10 Vdc) Outputs:<br />
• 1 (one) Cool<br />
• 1 (one) Reheating/Heat (opt.)<br />
• 1 (one) Humidification (opt.)<br />
Temperature Anticipation:<br />
The A-Tech-<strong>20</strong> incorporates a selfcalibrating<br />
and self-adjusting control<br />
logic that adjusts the response of the<br />
SATS air conditioner to changes in<br />
temperature and humidity. The<br />
system provides premium setpoint<br />
accuracy while controlling the room<br />
conditions rate of change, minimizing<br />
the equipment energy consumption<br />
and maximizing the system’s<br />
operating life and reliability.<br />
Remote Stop / Start:<br />
<strong>Inc</strong>luded in the system's electrical<br />
control circuit shall be a 2-pin<br />
terminal connection for remote stop /<br />
start of the ModulAiR air conditioner<br />
by a remote source.<br />
POWER LOSS RESTART:<br />
In the event of a loss of power to the<br />
system, the A-Tech-<strong>20</strong> can be<br />
configured for Automatic or <strong>Manual</strong><br />
Restart. The A-Tech-<strong>20</strong>'s nonvolatile<br />
memory enables the system<br />
to restart when power is restored,<br />
without the loss of the "last" stored<br />
set points and other system configuration<br />
settings.<br />
Sequential Load Activation:<br />
<strong>To</strong> minimize the total in-rush current<br />
loads during system start-up/restart,<br />
the A-Tech-<strong>20</strong> controller can be<br />
configured for time-delay sequence<br />
start-up. The user can designate<br />
specific unit restart time-delays, as<br />
well as, each unit's respective<br />
compressor, electric heater and/or<br />
humidifier. Unit restart delay can be<br />
adjusted from 0 to 10 minutes. Unit<br />
compressor, electric heater and/or<br />
humidifier restart delay can be<br />
adjusted from 0 to 60 seconds.<br />
Recovery Delay:<br />
After a power loss, the A-Tech-<strong>20</strong>'s<br />
Recovery Delay feature allows the<br />
ModulAiR A/C to operate without<br />
initiating any high or low temperature<br />
or humidity alarms for a delayed<br />
period. This feature allows the A/C<br />
time (15 to 60 minutes adj.) to "pulldown"<br />
the conditioned space's load<br />
without nuisance alarms during initial<br />
start-up or power loss restart.<br />
COMPRESSOR OPERATIONS:<br />
Short cycle protection:<br />
Each compressor is protected from<br />
frequent compressor cycling through<br />
the A-Tech-<strong>20</strong>'s minimum compressor<br />
ON and minimum compressor<br />
OFF short cycle timers.<br />
Cold Start Time Delay:<br />
Each compressor of a DX Split<br />
system is protected from liquid<br />
slugging through the A-Tech-<strong>20</strong>'s<br />
Cold Start compressor time delay.<br />
The Cold Start timer delays, and<br />
therefore, overrides the system's<br />
refrigerant low suction pressure<br />
Guide Specifications - Microprocessor Control Options<br />
3-7
Microprocessor Controls - A-Tech-<strong>20</strong><br />
Guide Specifications - Microprocessor Control Options<br />
switch during system start-up. This<br />
allows the system time to build<br />
sufficient discharge pressure during<br />
cold weather start-up.<br />
Pump-Down Cycle:<br />
The A-Tech-<strong>20</strong> is pre-programmed<br />
for a one-time refrigerant system<br />
pump-down cycle upon compressor<br />
shutdown on all split DX systems.<br />
This assists in the prevention of<br />
liquid slugging at start-up/restart.<br />
SECURITY:<br />
Multiple security levels prevent<br />
unauthorized adjustment of critical<br />
system parameters. The user may<br />
select a four-digit password for<br />
setpoint and configuration changes.<br />
Keypad Lockout:<br />
The A-Tech-<strong>20</strong> includes a selectable<br />
Keypad Lock-Out feature that<br />
prevents unauthorized users from<br />
making changes to system setpoints<br />
and settings available directly from<br />
the multi-function keypad/display.<br />
Keypad Lock-Out eliminates the<br />
need for stat-guards.<br />
DIAGNOSTICS & SERVICE MODE<br />
The A-Tech-<strong>20</strong> incorporates a<br />
unique self-diagnostics algorithm that<br />
continually tests system functions<br />
and hardware operation. In the<br />
event of such a failure, the user will<br />
be alerted to the condition via a<br />
visual and audible alarm.<br />
Control Board:<br />
Initiates a self-test of the control<br />
system.<br />
Input diagnostics:<br />
All system inputs and input devices<br />
are continuously monitored for<br />
proper operation.<br />
Output diagnostics:<br />
(Service Mode)<br />
Major component functionality can<br />
be tested by manually turning<br />
components ON and OFF from the<br />
A-Tech-<strong>20</strong> control panel. Select<br />
output devices that can be manually<br />
tested include (if applicable):<br />
• Compressor 1 or 2 • CW Valve<br />
• Blower Motor • HW Valve<br />
• Humidifier • FC Valve<br />
• Heat 1, 2 or 3 stgs • AWS Valve<br />
• Summary Alarm • Liq-Line Solenoid<br />
• Custom Alarm 1 • GC Pump Enable<br />
TIME CLOCK & NIGHT SET-BACK<br />
The A-Tech-<strong>20</strong> includes both Time<br />
Clock and Night Set-Back occupied/<br />
non-occupied energy saving modes.<br />
These features enable the user to<br />
customize each unit's daily 5-day/<br />
weekly and 2-day/weekend operational<br />
schedule.<br />
Time-Clock Feature:<br />
The Time-Clock feature enables the<br />
user to create an automatic time<br />
schedule for the unit to be allowed<br />
ON. The Time-Clock 5-2 day<br />
schedule allows the user to limit unit<br />
operation to occupied periods only.<br />
Night Set-Back Feature:<br />
The Night Set-Back feature enables<br />
the user to create a schedule for<br />
automatic relaxing of the unit's<br />
temperature and humidity control set<br />
points. For example, during the<br />
space occupied periods of 7am to<br />
6pm, the unit operates at a temperature<br />
setpoint of 72°F. Then, during<br />
the space unoccupied periods of<br />
6pm to 7am the next morning, the<br />
temperature setpoint automatically<br />
"relaxes" to 77°F. The Set-Back<br />
schedule resets again after 7am that<br />
morning where the temperature<br />
setpoint changes back to 72°F for<br />
Day Time Operation.<br />
Override Feature:<br />
During the unoccupied time cycles,<br />
the user can temporarily "override"<br />
the Time-Clock and/or Set-Back<br />
features. The user can override<br />
these functions for a time duration of<br />
1 to 6 hours.<br />
CyberLAN<br />
Networking Options<br />
MULTI-UNIT "N+1"<br />
SEQUENCING<br />
(Optional)<br />
AC-1 AC-2 AC-3<br />
(Master)<br />
AC-4 AC-5 AC-6<br />
(Standby)<br />
Critical control applications can<br />
incorporate the A-Tech-<strong>20</strong>'s Cyber-<br />
LAN multi-unit sequencing program<br />
logic, where under an A/C failure<br />
condition, the A-Tech-<strong>20</strong> will automatically<br />
initiate the unit operation of<br />
a designated standby/backup unit.<br />
Multi-Unit Sequencing:<br />
Multiple CyberAiR air conditioners<br />
incorporating A-Tech-<strong>20</strong> controls can<br />
be configured in groups of up to 6<br />
(six) units to allow for "N+1" redundancy/backup<br />
critical application<br />
operation.<br />
The "N" in N+1, represents the<br />
number of concurrent units in an On-<br />
Line Operational Mode with 1(one)<br />
unit in a standby mode. The value of<br />
"N" can range from 1 unit to a<br />
maximum of 5 units with a minimum<br />
and maximum of quantity 1 unit in<br />
standby mode.<br />
3-8
Microprocessor Controls - A-Tech-<strong>20</strong><br />
<strong>To</strong> allow for equal unit runtime and/or<br />
to ensure unit operation, the A-Tech-<br />
<strong>20</strong> can be configured for automatic<br />
timed and/or manual lead-lag of<br />
standby unit operation.<br />
The CyberLAN Multi-Unit Sequencing<br />
control logic shall automatically<br />
initiate the current standby unit upon<br />
a user selectable system failure<br />
alarm condition.<br />
The A-Tech-<strong>20</strong> is programmed to<br />
automatically change from current<br />
primary unit operation to secondary<br />
standby unit operation via three<br />
methods:<br />
1) <strong>Manual</strong> ChangeOver<br />
2) Automatic Timed (1-30 days)<br />
3) Automatic ChangeOver on Unit<br />
Failure (if applicable):<br />
• High Temperature<br />
• Low Temperature<br />
• High Humidity<br />
• Low Humidity<br />
• High Head Press<br />
• Low Suction Press<br />
• Sensor Failure<br />
• Loss of <strong>Air</strong> Flow<br />
• Dirty Filter<br />
• Leak Detection<br />
• Smoke Detection<br />
• Firestat<br />
• GC Pump Failure<br />
• Comm. Failure<br />
Factory defaults set a "logical" active/<br />
inactive state for the alarms. This is<br />
to limit "nuisance" type alarms that<br />
may occur because of conditions<br />
inherent to a particular application or<br />
system and that are not critical to the<br />
operation of the system.<br />
(For example: If Low Humidity is not<br />
critical to a particular application, and<br />
therefore, the A/C unit is not equipped<br />
with a Humidifier, the Low Humidity Alarm<br />
can be set to an inactive state.)<br />
Multi-Unit Network Grouping<br />
Interconnect Cable Options:<br />
• 75 ft. cable length (standard option)<br />
• 150 ft. cable length<br />
Capacity Assist-Mode:<br />
(Additionally Optional)<br />
In addition to switchover via manual,<br />
automatic timed or failure, the<br />
CyberLAN Multi-Unit Sequencing<br />
“Capacity Assist-Mode” can initiate<br />
switchover to standby unit operation<br />
to assist in the temperature and/or<br />
humidity control of the space.<br />
Remote Wall Mounted<br />
Capacity Assist T/H Sensor<br />
Sequence of Operation:<br />
The optional Capacity Assist Mode<br />
includes quantity one remote wall<br />
mounted Capacity Assist-Mode T/H<br />
Sensor with interconnect cable. This<br />
single capacity assist remote T/H<br />
sensor controls all N+1 units in the<br />
respective CyberLAN Group. <strong>To</strong><br />
establish a single point of control<br />
reference, the CyberLAN Group’s<br />
temperature and humidity set point is<br />
determined by the Master Unit’s<br />
(U1’s) A-Tech-<strong>20</strong> setpoints. Therefore,<br />
each of the current on-line units<br />
of the CyberLAN Group operate and<br />
control space temperature and/or<br />
humidity based on the Master Unit’s<br />
(U1’s) TEMP and HUMID SETPT in<br />
respect to their individual deadband.<br />
Capacity Assist Sensor Cable Options:<br />
• 75 ft. cable length (standard option)<br />
• 150 ft. cable length<br />
The current standby unit is enabled<br />
when the actual space temperature<br />
or humidity rises or falls to a condition<br />
equal to the Master Unit’s (U1’s)<br />
setpoint plus dead-band plus stage<br />
differential (if appl.) plus Capacity<br />
Assist Differential.<br />
(Note: As standard, each unit of a<br />
CyberLAN Group incorporating Capacity<br />
Assist Mode additionally includes its own<br />
standard unit mounted return air T/H<br />
sensor. If the Capacity Assist Sensor or its<br />
communications cable were to fail, Multi-<br />
Unit & Capacity Assist Mode operations will<br />
be automatically disabled, and the N+1<br />
Units will perform as stand-alone systems.<br />
CyberLAN - REMOTE<br />
COMMUNICATIONS<br />
(Optional)<br />
REMOTE BMS CONNECTION<br />
(ModBus Gateway)<br />
A-Tech-<strong>20</strong> Inputs & Outputs can be<br />
remotely monitored (address readable)<br />
and remotely controlled<br />
(address writable) via any building<br />
management system (BMS) / local<br />
area network (LAN) control system<br />
that can communicate via a ModBus<br />
protocol. Each A-Tech-<strong>20</strong> configured<br />
for BMS communication shall<br />
incorporate an optional Serial<br />
Communication Port that is field<br />
wired to a factory provided wall<br />
mounted ModBus Gateway.<br />
(Note: A list of the addressable I/Os are<br />
available upon request from your local<br />
SATS Sales Representative.)<br />
16 Units Per CyberLAN ModBus:<br />
Each ModBus Gateway can accommodate<br />
up to 16 (sixteen) A/C units<br />
in a group.<br />
The total number of Gateways<br />
required for a given application may<br />
not depend only on the number of<br />
maximum (16) units each Gateway<br />
can accommodate, but also the<br />
facility layout.<br />
(Note: The units of a CyberLAN<br />
Networking Group must be connected to<br />
each other and then to the ModBus<br />
Gateway via shielded serial twisted-pair<br />
cabling. This cabling is not included in<br />
SATS' CyberLAN Remote Communications<br />
/ ModBus Gateway option, as a<br />
standard. This cabling is typically<br />
provided by the installing contractor.)<br />
Guide Specifications - Microprocessor Control Options<br />
3-9
Optional Features - Guide Specifications<br />
Optional Features - Guide Specifications<br />
3-10<br />
SELECTED OPTIONS<br />
Humidity Control<br />
ModulAiR floor systems include<br />
the A-Tech-<strong>20</strong> Microprocessor<br />
Controller, Electrode Canister<br />
Steam Humidifier and Dehumidification<br />
Mode with Electric Reheat/<br />
Heat for total temperature and<br />
humidity control, as a standard.<br />
However, these standard features<br />
can be deleted and/or substituted<br />
with alternate features to allow you<br />
the flexibility to select the configuration<br />
best suited for your unique<br />
application.<br />
Canister Steam Humidification:<br />
(standard)<br />
The humidifier shall be an electrode<br />
steam canister type and shall have<br />
an adjustable humidity output setting<br />
from 25 to 100% of the full rated<br />
humidifier capacity. The humidifier<br />
shall incorporate an automatic flush<br />
cycle that senses the current consumption<br />
of the humidifier and<br />
controls mineral concentration of the<br />
water. A “Change Cylinder” light shall<br />
notify service personnel when the<br />
humidification output is below rated<br />
requirements and when maintenance<br />
is due.<br />
Dehumidification Cycle: (standard)<br />
The floor A/C shall be provided with a<br />
refrigeration based dehumidification<br />
mode. Moisture is condensed on the<br />
cooling coil and discharged through<br />
the condensate drain. Electric reheat<br />
shall be provided to offset sensible<br />
cooling during the dehumidification<br />
cycle.<br />
Electric Heat/Reheat: (standard)<br />
A factory mounted and wired electric<br />
resistance heater shall be included to<br />
provide automatic sensible reheating<br />
mode during the dehumidification cycle<br />
and automatic heating mode as<br />
required. Electric heaters shall be<br />
provided with thermal / magnetic circuit<br />
breakers which shall protect each<br />
conductor. <strong>Inc</strong>luded shall be one<br />
automatic resetting and one manual<br />
resettable over-temperature safety<br />
device (pilot duty).<br />
Heater elements shall be of a safe lowwatt<br />
density, plated fin-tubular design.<br />
High Static Pressure<br />
Belt-Drive Blowers<br />
The ModulAiR vertical floor air<br />
conditioner shall be provided with a<br />
high static pressure belt-driven<br />
evaporator blower to provide standard<br />
unit CFM @ ____ " e.s.p.<br />
(Note: Due to the probable change in<br />
standard unit blower motor horsepower for<br />
the High Static Belt-Drive Blower option,<br />
please consult your local SATS sales<br />
representative for the following unit<br />
specification changes:<br />
• Blower Motor Horsepower<br />
• Net Cooling Capacity<br />
• Electrical Data<br />
• Discharge Blower Data<br />
Unit AIr Flow Rate (CFM) will match the<br />
standard data as shown in Section 4 of this<br />
manual for each respective unit model.<br />
Filtration<br />
ModulAiR vertical floor A/C's are<br />
available with the following standard<br />
and optional high efficiency IAQ<br />
conscious filtration:<br />
F1: 2", 30% Eff. Filters (std 084/1<strong>20</strong>)<br />
F2: 4", 30% Eff. Filters (std 192/240)<br />
F3: 4", 60% Eff. Filters<br />
F4: 2", 30% Pre / 4", 60% Eff. Final Filters<br />
<strong>Air</strong> Pattern Type Filters Avail.<br />
MCS-084/1<strong>20</strong>-( )-U:<br />
w/ free-front return: F1<br />
w/ ducted rear return: F1, F2, F3, F4<br />
MCS-084/1<strong>20</strong>-( )-D:<br />
w/ top return: F1, F2, F3, F4<br />
MCS-192/240-( )-U:<br />
w/ free-front return: F2, F3<br />
w/ ducted rear return: F2, F3, F4<br />
MCS-192/240-( )-D:<br />
w/ top return: F2, F3, F4<br />
Filter ratings are based on dust spot<br />
efficiency ratings per ASHRAE Test<br />
Standard 52-76.<br />
(Note: Optional filters create additional<br />
static pressure and may require the High<br />
Static Pressure Belt-Drive Option. Please<br />
consult your local SATS sales representative<br />
for details.)
HP<br />
LP<br />
Optional Features - Guide Specifications<br />
Head Pressure Control<br />
AIR COOLED - Low Ambient<br />
-<strong>20</strong>°F, Variable Speed Control<br />
(Model HES-( )-LSA Condensers)<br />
The air cooled system shall incorporate<br />
a low ambient variable speed fan<br />
head pressure control for year-round<br />
system operation down to -<strong>20</strong>°F DB<br />
minimum ambient air temperature.<br />
-30°F, Flooded Control<br />
Remote <strong>Air</strong><br />
Cooled Condenser<br />
Flooded<br />
Head Pressure<br />
Control Valve<br />
Relief<br />
Valve<br />
Liquid Refrigerant<br />
Receiver<br />
Scroll<br />
Compressor<br />
Evaporator<br />
Cooling Coil<br />
High<br />
Low<br />
Feeler<br />
Pressure<br />
Pressure<br />
Bulb<br />
Switch<br />
Switch<br />
Liquid Line<br />
Sight<br />
Solenoid Valve<br />
Glass<br />
Refrigerant<br />
Refrigerant Drier / Strainer Thermal Expansion<br />
Reclaim Port<br />
Valve<br />
Equalizer<br />
Line<br />
The air cooled system shall incorporate<br />
a low ambient flooded head<br />
pressure control for year-round<br />
system operation down to -30°F DB<br />
minimum ambient air temperature.<br />
This option shall include a factory<br />
installed crankcase heater, cold-start<br />
relay, liquid refrigerant receiver with<br />
receiver liquid level sight glass and<br />
head pressure regulating valve for<br />
flooded condenser operation.<br />
Each refrigerant circuit's head<br />
pressure shall be controlled by a<br />
factory installed ____-way water /<br />
glycol regulating valve rated for ____<br />
psig. w.w.p.<br />
DX - Capacity Modulation<br />
/ Free-Protecion<br />
SNAP-ACTING, Hot Gas Bypass<br />
(Models MCS-()-DAR, DW & DG only)<br />
The ModulAiR floor A/C shall incorporate<br />
a snap acting hot gas bypass<br />
system to provide modulation of the<br />
unit’s cooling capacity and evaporator<br />
coil freeze protection under low load<br />
conditions.<br />
Remote <strong>Air</strong><br />
Cooled Condenser<br />
Flooded<br />
Head Pressure<br />
Control Valve<br />
Relief<br />
Valve<br />
Liquid Refrigerant<br />
Receiver<br />
Refrigerant<br />
Reclaim Port<br />
High<br />
Pressure<br />
Switch<br />
HP<br />
Scroll<br />
Compressor<br />
Refrigerant<br />
Drier / Strainer<br />
Low<br />
Pressure<br />
LP Switch<br />
Hot Gas<br />
Regulator Valve<br />
(Optional)<br />
Liquid Line<br />
Sight<br />
Solenoid Valve<br />
Glass<br />
Equalizer<br />
Line<br />
Thermal Expansion<br />
Valve<br />
Chilled Water<br />
Control Valves<br />
Feeler<br />
Bulb<br />
Evaporator<br />
Cooling Coil<br />
Standard (0-10 Vdc) Valve Control:<br />
A ____-way modulating CW or AWS<br />
cooling control valve rated for a<br />
maximum ____ psig w.w.p. shall be<br />
factory installed. Precision cooling<br />
control shall be accomplished via a 0-<br />
10 Vdc A-Tech-<strong>20</strong> analog control<br />
signal to the proportionally actuating<br />
control valve.<br />
ACCESSORIES<br />
Adjustable Floor Stand:<br />
A _____ " high adjustable floor stand<br />
shall be provided to allow for ease of<br />
installation of the ModulAiR A/C onto<br />
a raised floor. The floor stand shall be<br />
field installed.<br />
Floor Stand<br />
Nominal Height<br />
Dimensional<br />
Data -<br />
"A" Dimension<br />
Floor Stand Heights<br />
Adjustable Height<br />
Minimum<br />
Maximum<br />
Turning Vane<br />
Availability<br />
4 .0" ( Upflow Units Only)<br />
3 .5"<br />
4.5"<br />
Not Availabl e<br />
6 .0"<br />
5 .0"<br />
7.0"<br />
Not Availabl e<br />
Optional Features - Guide Specifications<br />
WATER / GLYCOL COOLED<br />
12.0"<br />
11.0"<br />
15.0"<br />
Optional<br />
15.0"<br />
14.0"<br />
18.0"<br />
Optional<br />
18.0"<br />
17.0"<br />
21.0"<br />
Optional<br />
24.0"<br />
23.0"<br />
26.0"<br />
Optional<br />
DX Water Cooled and Glycol Cooled<br />
systems are available with following<br />
standard (V1) and optional (V2-V6)<br />
head pressure regulating control<br />
valves:<br />
V1: 2-way, 150 psig (standard)<br />
V2: 2-way, 350 psig<br />
V3: 2-way, 450 psig<br />
V4: 3-way, 150 psig<br />
V5: 3-way, 350 psig<br />
V6: 3-way, 450 psig<br />
Chilled Water and Alternate Water<br />
Source cooling shall be controlled by<br />
the following standard and optional<br />
control valves:<br />
Models MCS-084/1<strong>20</strong>-C:<br />
V1: 3-way, 300 psig (standard)<br />
V2: 3-way, 400 psig<br />
V3: 2-way, 300 psig<br />
V4: 2-way, 400 psig<br />
Models MCS-192/240-C:<br />
V5: 3-way, 400 psig (standard)<br />
V6: 2-way, 400 psig<br />
Note: For additional floor stand heights,<br />
please contact your local SATS sales<br />
representative.<br />
Additional Floor Stand Options:<br />
Turning Vanes:<br />
Turning vanes shall be factory<br />
provided for field installation to each<br />
unit's floor stand.<br />
3-11
Optional Features - Guide Specifications<br />
Optional Features - Guide Specifications<br />
Seismic Zone-4 Rate:<br />
The adjustable floor stand shall be<br />
certified rated for seismic zone-4<br />
installation.<br />
<strong>To</strong>p Discharge Plenum Box:<br />
(Up-Flow units only)<br />
A 2 or 3-way (please specify) plenum<br />
discharge box shall be provided. The<br />
plenum box shall include doubledeflecting,<br />
adjustable grilles. The<br />
plenum box shall ship separately for<br />
rigging purposes.<br />
Condensate Pump<br />
(Factory Mounting Available)<br />
A condensate pump shall be factory<br />
installed within the ModulAiR system<br />
for automatic removal of condensate<br />
and humidifier flush water (if applicable).<br />
The condensate pump shall include an<br />
internal overflow safety float switch<br />
which, when wired to the A/C's remote<br />
stop/start terminals, shall open the A/<br />
C's control circuit, thereby shutting the<br />
A/C down in the event of a condensate<br />
overflow.<br />
The condensate pump shall be<br />
specifically designed to operate with<br />
the higher condensate temperatures<br />
caused by the flush and drain cycle of<br />
the electrode canister humidifiers.<br />
Smoke Detector<br />
A photo-electric smoke detector shall<br />
be factory installed in the ModulAiR<br />
evaporator section on the suction side<br />
of the evaporator blower.<br />
The smoke detector shall be rated for<br />
high air velocity applications, and shall<br />
shut down the air conditioner upon<br />
sensing smoke in the return air<br />
stream.<br />
Optional Auxiliary Contact:<br />
An auxiliary dry-contact (n/o) terminal<br />
connection shall be provided for<br />
remote notification of a smoke<br />
detection alarm.<br />
Firestat<br />
The air conditioner shall be provided<br />
with a factory wired and mounted<br />
firestat. The firestat shall shut down<br />
the air conditioner upon sensing a<br />
high return air temperature.<br />
Remote Water Detectors<br />
Single (one) - Spot Type Detector:<br />
Quantity 1(one) remote spot type<br />
water/leak detector per A/C unit shall<br />
be factory provided for remote field<br />
installation. Upon sensing a water<br />
leak, the normally closed water<br />
detector control circuit shall open,<br />
thereby shutting down the air<br />
conditioner's water producing operations.<br />
Dual (two) - Spot Type Detectors:<br />
Quantity 2(two) remote spot type<br />
water/leak detectors per A/C unit shall<br />
be factory provided for remote field<br />
installation. Upon sensing a water<br />
leak, the normally closed water<br />
detector control circuit shall open,<br />
thereby shutting down the air<br />
conditioner's water producing operations.<br />
40 Ft. - Strip/Cable Type Detector:<br />
A 40 Ft. in length remote strip/cable<br />
type water/leak detector shall be<br />
factory provided for remote field<br />
installation. In addition to the 40 Ft.<br />
cable, a 24V water detector power<br />
module shall require field mounting<br />
and wiring to factory provided terminal<br />
connection. Upon sensing a water<br />
leak, the normally closed water<br />
detector control circuit shall open,<br />
thereby shutting down the air<br />
conditioner's water producing operations.<br />
Optional Auxiliary Contact:<br />
An auxiliary dry-contact (n/o) terminal<br />
connection shall be provided for<br />
remote notification of a water detection<br />
alarm.<br />
Compressor Sound Jackets<br />
(MCS-( )-DW/DG-() Only!)<br />
Each compressor shall be provided<br />
with a factory installed acoustical<br />
3-12
Optional Features - Guide Specifications<br />
sound jacket. Each sound jacket shall<br />
have a snap closure system for ease<br />
of removing and reinstallation during<br />
maintenance. Each sound jacket shall<br />
have a Noise Reduction Coefficient<br />
NRC of 85 per ASTM C-423 and a<br />
Sound Transmission Loss STC of 11<br />
per ASTM E-90.<br />
Glycol Pump Packages<br />
Single Pump Packages<br />
(Models GPS-( )-S)<br />
The system shall be a single pump<br />
package designed to provide the total<br />
required glycol condenser coolant<br />
flow rate at the total rated system<br />
pressure drop.<br />
(Dual Pump Packages)<br />
(Models GPS-( )-D)<br />
The system shall be a dual (two),<br />
redundant, pump package designed to<br />
provide the total required glycol<br />
condenser coolant flow rate at the total<br />
rated system pressure drop. A field<br />
installed coolant sensing flow switch<br />
shall be provided for automatic<br />
switchover from primary to backup<br />
pump operation in the event of a loss of<br />
coolant flow.<br />
<strong>To</strong> allow for equal pump run-time<br />
and/or to ensure pump operation, a<br />
manual lead-lag toggle switch shall<br />
be factory included with the Dual<br />
Pump Package controls.<br />
Single & Dual Pump Packages:<br />
Each pump shall be mounted on a<br />
galvanized steel chassis and protected<br />
by a removable galvanized<br />
steel cover. The pump controls shall<br />
consist of individual pumps controls<br />
mounted in a NEMA-3R enclosure at<br />
the end of each pump package. The<br />
glycol pump package shall be<br />
electrically interfaced with each<br />
drycooler and indoor evaporator via<br />
a 24-Vac low voltage connection.<br />
The pump package controls shall<br />
include, but not be limited to:<br />
• Pump starter(s)/contactor(s) with<br />
fusing per NEC;<br />
• Main Power Non-Fused Disconnect<br />
Switch with lockable handle;<br />
• Powered Pump Package with 24<br />
Volt Control Transformer;<br />
• Main Power Distribution Block with<br />
grounding lug;<br />
The pump shall be sized to<br />
provide:<br />
____<br />
____<br />
____<br />
or<br />
____<br />
GPM (total system flow rate)<br />
ft. w.g. (total system press drop)<br />
% Ethylene Glycol Solution<br />
% Propylene Glycol Solution<br />
Remote Drycoolers<br />
(MODELS HES-( )-LGA)<br />
Remote Drycooler<br />
(Models HES-( )-LGA)<br />
The system shall be a remote<br />
outdoor air cooled glycol drycooler<br />
(fluid-cooler) sized to provide the<br />
total heat of rejection of the system<br />
glycol condenser source solution at<br />
a ___°F DB ambient temperature.<br />
Drycooler casings shall be fabricated<br />
from heavy gauge aluminum for<br />
corrosion protection and appearance.<br />
Structural components shall be<br />
fabricated from galvanized steel for<br />
support.<br />
The drycooler shall incorporate<br />
direct-driven propeller fan(s). Each<br />
fan shall be provided with a low RPM,<br />
non-overloading direct driven motor.<br />
The fan blades shall be made from<br />
aluminum and have zinc plated hubs<br />
for strength and corrosion protection.<br />
Multiple fan drycoolers shall<br />
have internal air baffles to prevent air<br />
bypass from one fan section to<br />
another and to maximize air through<br />
each coil section.<br />
Each drycooler shall be provided<br />
with a field installed 15 gallon<br />
expansion tank and airtrol fitting.<br />
Drycooler - Fan Cycling Controls:<br />
The drycooler control box shall<br />
include, but not be limited to:<br />
• Weather Rated Enclosure<br />
• Fan Motor starter(s)/contactor(s)<br />
with fusing per NEC;<br />
• Aquastat(s) to sense and maintain<br />
proper coolant temperature in DX<br />
mode;<br />
• Main Power Non-Fused Disconnect<br />
Switch;<br />
• Main Power Distribution Block with<br />
grounding lug.<br />
Optional Features - Guide Specifications<br />
3-13
<strong>Air</strong> Cooled - 7 to <strong>20</strong> <strong>To</strong>n “MCS”<br />
Performance Data - <strong>Air</strong> Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
"MCS" Model MCS-084-DAR MCS-1<strong>20</strong>-DAR MCS-192-DAR MCS-240-DAR<br />
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />
75°FDB/62.5°FWB, 50% RH<br />
<strong>To</strong>tal 94,150 119,8<strong>20</strong> 189,560 244,510<br />
Sensible 78,580 100,440 168,080 <strong>20</strong>3,400<br />
72°FDB/60°FWB, 50% RH<br />
<strong>To</strong>tal 89,700 114,070 180,3<strong>20</strong> 233,150<br />
Sensible 77,0<strong>20</strong> 98,4<strong>20</strong> 164,580 199,500<br />
70°FDB/58.5°FWB, 50% RH<br />
<strong>To</strong>tal 87,110 110,750 174,940 226,580<br />
Sensible 75,340 96,2<strong>20</strong> 160,680 195,180<br />
75°FDB/61°FWB, 45% RH<br />
<strong>To</strong>tal 91,480 116,060 184,180 237,080<br />
Sensible 83,990 107,580 179,610 217,810<br />
72°FDB/58.5°FWB, 45% RH<br />
<strong>To</strong>tal 87,190 110,430 175,010 225,880<br />
Sensible 82,400 105,390 172,590 213,730<br />
70°FDB/57°FWB, 45% RH<br />
<strong>To</strong>tal 84,680 107,180 170,040 219,440<br />
Sensible 80,680 103,100 167,980 <strong>20</strong>9,290<br />
Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />
ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />
@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />
<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />
Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />
Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />
Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />
Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />
Standard Control Cycling Cycling Cycling Cycling<br />
Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />
Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />
CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />
Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />
Qty. of Blowers two two two two<br />
Evaporator Coils - Aluminum Fin, Copper Tube<br />
Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />
Face Velocity, fpm 338 469 434 495<br />
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />
Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />
Watts Input 7,696 9,918 15,582 <strong>20</strong>,878<br />
<strong>To</strong>t. Heat of Rej. (BTU/H) 1<strong>20</strong>,4<strong>20</strong> 153,670 242,740 315,770<br />
Connection Sizes - Copper, (Please refer to ModulAiR IOM <strong>Manual</strong> for proper interconnecting refrigerant line sizing.)<br />
Refrigerant:<br />
Liquid Line, (Qty.) 1/2" OD, (2) 1/2" OD, (2) 7/8" OD, (2) 7/8" OD (2)<br />
Hot Gas Line, (Qty.) 7/8" OD, (2) 7/8" OD, (2) 7/8" OD, (2) 1-1/8" OD (2)<br />
Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />
Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />
4-1
<strong>Air</strong> Cooled - Remote Condenser Data (7 to <strong>20</strong> <strong>To</strong>n “MCS”)<br />
"MCS" Model MCS-084-DAR MCS-1<strong>20</strong>-DAR MCS-192-DAR MCS-240-DAR<br />
Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />
Up-Flow:<br />
Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />
(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />
Down-Flow:<br />
Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />
Physical Data<br />
Approx. Weight 500 lbs x 2 500 lbs x 2 725 lbs x 2 735 lbs x 2<br />
Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />
MCS-( )-DAR-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />
MCS-( )-DAR-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />
><br />
Remote <strong>Air</strong> Cooled Condenser Data:<br />
HES-( )-DL()A - (Remote Outdoor Propeller Fan, <strong>Air</strong> Cooled Condenser for Model MCS-( )-DAR Evaporator Section)<br />
Cond. Model @ 95°F Amb. HES-1<strong>20</strong>-DL()A HES-168-DL()A HES-252-DL()A HES-339-DL()A<br />
Condenser Fan Data<br />
CFM @ free discharge 10,100 13,700 <strong>20</strong>,500 23,000<br />
Motor Hp, (Qty.) 1/3 Hp, (2) 1/3 Hp, (2) 1/3 Hp, (3) 1.5 Hp, (2)<br />
Fan RPM 1,140 1,140 1,140 1,140<br />
Drive Method Direct Driven Direct Driven Direct Driven Direct Driven<br />
Condenser Coil<br />
Rows/Face Area (ft 2 ) 3/ 16.7 3/ 22.2 3/ 32.1 2/ 32.3<br />
Refrigerant Connections<br />
Liquid Line, (Qty.) 7/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 1-3/8" OD, (2)<br />
Hot Gas Line, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-3/8" OD, (2)<br />
Compressors are located with the model MCS-( )-DAR Evaporator Section<br />
HES-( )-DL()A - (Remote Outdoor Propeller Fan(s), <strong>Air</strong> Cooled Condenser for Model MCS-( )-DAR Evaporator Section)<br />
Cond. Model @ 105°F Amb. HES-168-DL()A HES-192-DL()A HES-399-DL()A HES-525-DL()A<br />
Condenser Fan Data<br />
CFM @ free discharge 13,700 12,900 23,<strong>20</strong>0 <strong>20</strong>,700<br />
Motor Hp, (Qty.) 1/3 Hp, (2) 1/3 Hp, (2) 1.5 Hp, (2) 1.5 Hp, (2)<br />
Fan RPM 1,140 1,140 1,140 1,140<br />
Drive Method Direct Driven Direct Driven Direct Driven Direct Driven<br />
Condenser Coil<br />
Rows/Face Area (ft 2 ) 3/ 22.2 4/ 22.2 3/ 32.3 4/ 32.3<br />
Refrigerant Connections<br />
Liquid Line, (Qty.) 7/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />
Hot Gas Line, (Qty.) 1-1/8" OD, (2) 1-3/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />
Compressors are located with the model MCS-( )-DAR Evaporator Section<br />
Low Ambient Control<br />
Std Minimum Op. Amb. -<strong>20</strong>°F -<strong>20</strong>°F -<strong>20</strong>°F -<strong>20</strong>°F<br />
Head Press. Method Variable Speed Variable Speed Variable Speed Variable Speed<br />
Optional Min. Oper. Method -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded)<br />
Performance Data - <strong>Air</strong> Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
4-2
Water Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />
Performance Data - Water Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
"MCS" Model MCS-084-DW MCS-1<strong>20</strong>-DW MCS-192-DW MCS-240-DW<br />
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />
75°FDB/62.5°FWB, 50% RH<br />
<strong>To</strong>tal 100,980 128,540 <strong>20</strong>2,540 261,7<strong>20</strong><br />
Sensible 81,190 103,540 173,0<strong>20</strong> <strong>20</strong>9,8<strong>20</strong><br />
72°FDB/60°FWB, 50% RH<br />
<strong>To</strong>tal 96,260 122,460 192,900 249,110<br />
Sensible 79,470 101,370 169,610 <strong>20</strong>6,580<br />
70°FDB/58.5°FWB, 50% RH<br />
<strong>To</strong>tal 93,380 118,980 187,300 242,180<br />
Sensible 77,900 99,190 165,770 <strong>20</strong>2,280<br />
75°FDB/61°FWB, 45% RH<br />
<strong>To</strong>tal 97,780 124,<strong>20</strong>0 196,7<strong>20</strong> 253,3<strong>20</strong><br />
Sensible 86,580 110,840 185,600 224,300<br />
72°FDB/58.5°FWB, 45% RH<br />
<strong>To</strong>tal 93,240 118,300 187,430 241,580<br />
Sensible 85,060 108,830 181,580 2<strong>20</strong>,4<strong>20</strong><br />
70°FDB/57°FWB, 45% RH<br />
<strong>To</strong>tal 90,590 114,860 182,0<strong>20</strong> 234,760<br />
Sensible 83,400 106,630 177,480 216,100<br />
Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />
ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />
@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />
<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />
Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />
Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />
Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />
Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />
Standard Control Cycling Cycling Cycling Cycling<br />
Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />
Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />
CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />
Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />
Qty. of Blowers two two two two<br />
Evaporator Coils - Aluminum Fin, Copper Tube<br />
Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />
Face Velocity, fpm 338 469 434 495<br />
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />
Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />
Watts Input 5.946 7,734 12,568 17,070<br />
Water Cooled Condenser Data - Based on 0% Glycol Solution<br />
<strong>To</strong>t Heat of Reject. 121,280 Btu/h 154,940 Btu/h 245,440 Btu/h 319,980 Btu/h<br />
GPM @ 85°F EWT / 95°F LWT 24.2 GPM 31.0 GPM 29.0 GPM 64.0 GPM<br />
Press. Drop (Ft. of H 2<br />
O) 15.3 Ft. 26.0 Ft. 18.1 Ft. 27.9 Ft.<br />
Condenser Type Coaxial Brazed-Plate Brazed-Plate Brazed-Plate<br />
Std Head Pressure Control - - - - 2-way, 150 psig DX Water Source Regulating Valve - factory installed - - - -<br />
4-3
Water Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />
"MCS" Model MCS-084-DW MCS-1<strong>20</strong>-DW MCS-192-DW MCS-240-DW<br />
Connection Sizes - Copper<br />
Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />
Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />
Water Source In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-3/8 " OD, (2) 1-3/8 " OD, (2)<br />
Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />
Up-Flow:<br />
Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />
(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />
Down-Flow:<br />
Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />
Physical Data<br />
Approx. Weight 530 lbs x 2 530 lbs x 2 800 lbs x 2 810 lbs x 2<br />
Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />
MCS-( )-DW-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />
MCS-( )-DW-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />
><br />
Performance Data - Water Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
4-4
Glycol Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />
Performance Data - Glycol Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
"MCS" Model MCS-084-DG MCS-1<strong>20</strong>-DG MCS-192-DG MCS-240-DG<br />
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />
75°FDB/62.5°FWB, 50% RH<br />
<strong>To</strong>tal 89,770 113,640 179,800 232,600<br />
Sensible 76,800 98,000 164,450 198,600<br />
72°FDB/60°FWB, 50% RH<br />
<strong>To</strong>tal 85,460 108,040 170,880 221,6<strong>20</strong><br />
Sensible 75,280 96,010 160,710 194,8<strong>20</strong><br />
70°FDB/58.5°FWB, 50% RH<br />
<strong>To</strong>tal 82,960 104,8<strong>20</strong> 165,690 215,270<br />
Sensible 73,600 93,780 156,700 190,480<br />
75°FDB/61°FWB, 45% RH<br />
<strong>To</strong>tal 87,2<strong>20</strong> 110,000 174,640 225,350<br />
Sensible 82,230 105,030 171,860 213,1<strong>20</strong><br />
72°FDB/58.5°FWB, 45% RH<br />
<strong>To</strong>tal 83,1<strong>20</strong> 104,600 166,960 214,580<br />
Sensible 80,460 102,380 165,310 <strong>20</strong>8,500<br />
70°FDB/57°FWB, 45% RH<br />
<strong>To</strong>tal 80,7<strong>20</strong> 101,470 162,080 <strong>20</strong>8,400<br />
Sensible 78,660 99,880 160,740 <strong>20</strong>3,760<br />
Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />
ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />
@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />
<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />
Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />
Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />
Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />
Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />
Standard Control Cycling Cycling Cycling Cycling<br />
Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />
Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />
CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />
Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />
Qty. of Blowers two two two two<br />
Evaporator Coils - Aluminum Fin, Copper Tube<br />
Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />
Face Velocity, fpm 338 469 434 495<br />
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />
Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />
Watts Input 8.<strong>20</strong>6 10,580 16,482 21,998<br />
Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution<br />
<strong>To</strong>t. Heat of Reject. 117,780 Btu/h 149,750 Btu/h 236,060 Btu/h 307,680 Btu/h<br />
GPM @ 110°F EGT / 1<strong>20</strong>°F LGT 26.0 GPM 33.2 GPM 52.2 GPM 68.0 GPM<br />
Press. Drop (Ft. of H 2<br />
O) 16.6 Ft. 28.1 Ft. 19.9 Ft. 30.1 Ft.<br />
Condenser Type Coaxial Coaxial Brazed-Plate Brazed-Plate<br />
Std Head Pressure Control - - - - 2-way, 150 psig DX Glycol Source Regulating Valve - factory installed - - - -<br />
4-5
Glycol Cooled - Condenser Data (7 to <strong>20</strong> <strong>To</strong>n "MCS")<br />
"MCS" Model MCS-084-DG MCS-1<strong>20</strong>-DG MCS-192-DG MCS-240-DG<br />
Connection Sizes - Copper<br />
Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />
Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />
Water Source In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-3/8 " OD, (2) 1-3/8 " OD, (2)<br />
Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />
Up-Flow:<br />
Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />
(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />
Down-Flow:<br />
Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />
Physical Data<br />
Approx. Weight 530 lbs x 2 530 lbs x 2 800 lbs x 2 810 lbs x 2<br />
Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />
MCS-( )-DG-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />
MCS-( )-DG-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />
><br />
Drycooler / Pump Package<br />
Selection @ 95°F HES-1<strong>20</strong>-LGA HES-168-LGA HES-252-LGA HES-447-LGA<br />
GPM @ 1<strong>20</strong>°F EGT/110°F LGT 26.0 GPM 33.2 GPM 52.2 GPM 68.0 GPM<br />
Press. Drop (Ft. of H 2<br />
O) 6.7 Ft. 13.2 Ft. 6.4 Ft. 14.1 Ft.<br />
No. of Circuits 24 24 48 21<br />
Epansion Tank 15 Gal 15 Gal 15 Gal 15 Gal<br />
Pipe Connection (In/Out) 2-1/8" OD 2-1/8" OD 2-5/8" OD 2-5/8" OD<br />
105°F Amb. Selections Optional - Please refer to Glycol Pump / Drycooler <strong>Engineering</strong> <strong>Manual</strong><br />
Standard Pump GPS-015-S GPS-015-S GPS-0<strong>20</strong>-S GPS-030-S<br />
Quantity 1(one) 1(one) 1(one) 1(one)<br />
Horsepower 1.5 Hp 1.5 Hp 2.0 Hp 3.0Hp<br />
<strong>To</strong>tal Hd Press. (ft. w.g.) Ft. Ft. Ft. Ft.<br />
Dual Pump Packages Optional - Please refer to Glycol Pump / Drycooler <strong>Engineering</strong> <strong>Manual</strong><br />
Performance Data - Glycol Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
4-6
Chilled Water - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />
Performance Data - Chilled Water (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
"MCS" Model MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
NET COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings)<br />
75°FDB/62.5°FWB, 50% RH<br />
High Flow <strong>To</strong>tal 108,4<strong>20</strong> 139,660 2<strong>20</strong>,280 244,0<strong>20</strong><br />
(8°F ∆T w<br />
) Sensible 88,340 116,440 190,600 213,160<br />
GPM / (pd. Ft.) 27.2 / (11.7) 34.8 / (18.7) 55.8 / (2.9) 61.4 / (3.5)<br />
Med. Flow <strong>To</strong>tal 99,480 128,600 187,0<strong>20</strong> <strong>20</strong>7,6<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 83,800 110,5<strong>20</strong> 172,400 192,840<br />
GPM / (pd. Ft.) <strong>20</strong>.0 / (6.7) 26.0 / (10.7) 38.0 / (1.4) 42.0 / (1.7)<br />
Low Flow <strong>To</strong>tal 91,180 117,780 135,380 152,240<br />
(12°F ∆T w<br />
) Sensible 79,2<strong>20</strong> 104,1<strong>20</strong> 135,380 152,240<br />
GPM / (pd. Ft.) 15.2 / (4.1) 19.6 / (6.5) 23.0 / (0.5) 25.8 / (0.6)<br />
72°FDB/60°FWB, 50% RH<br />
High Flow <strong>To</strong>tal 89,400 115,160 172,780 191,240<br />
(8°F ∆T w<br />
) Sensible 79,7<strong>20</strong> 104,9<strong>20</strong> 166,1<strong>20</strong> 185,540<br />
GPM / (pd. Ft.) 22.8 / (8.4) 28.8 / (13.2) 43.8 / (1.9) 48.6 / (2.2)<br />
Med. Flow <strong>To</strong>tal 81,040 103,500 131,8<strong>20</strong> 147,960<br />
(10°F ∆T w<br />
) Sensible 74,700 97,480 131,8<strong>20</strong> 147,960<br />
GPM / (pd. Ft.) 16.4 / ( 4.6) <strong>20</strong>.8 / (7.2) 27.0 / (0.7) 30.2 / (0.9)<br />
Low Flow <strong>To</strong>tal 70,400 84,400 99,700 113,280<br />
(12°F ∆T w<br />
) Sensible 67,740 84,400 99,700 113,280<br />
GPM / (pd. Ft.) 12.0 / (2.4) 14.4 / (3.6) 17.2 / (0.2) 19.4 / (0.3)<br />
70°FDB/58.5°FWB, 50% RH<br />
High Flow <strong>To</strong>tal 78,100 99,460 137,960 154,980<br />
(8°F ∆T w<br />
) Sensible 73,<strong>20</strong>0 95,480 137,960 154,980<br />
GPM / (pd. Ft.) 19.6 / (6.5) 25.2 / (10.1) 35.2 / (1.2) 39.4 / (1.5)<br />
Med. Flow <strong>To</strong>tal 67,9<strong>20</strong> 83,540 109,6<strong>20</strong> 123,700<br />
(10°F ∆T w<br />
) Sensible 66,540 83,540 109,6<strong>20</strong> 123,700<br />
GPM /(pd.\Ft.) 13.6 / ( 3.3) 16.8 / (4.9) 22.6 / (0.5) 25.4 / (0.6)<br />
Low Flow <strong>To</strong>tal 55,600 72,8<strong>20</strong> 86,160 91,400<br />
(12°F ∆T w<br />
) Sensible 55,600 72,8<strong>20</strong> 86,160 91,400<br />
GPM / (pd. Ft.) 9.6 / (1.4) 12.4 / (2.6) 15.0 / (0.2) 15.8 / (0.2)<br />
75°FDB/61°FWB, 45% RH<br />
High Flow <strong>To</strong>tal 101,000 130,240 <strong>20</strong>3,640 224,640<br />
(8°F ∆T w<br />
) Sensible 91,6<strong>20</strong> 1<strong>20</strong>,7<strong>20</strong> 195,8<strong>20</strong> 218,340<br />
GPM / (pd. Ft.) 25.2 / (10.3) 32.8 / (16.5) 51.6 / (2.5) 56.8 / (3.0)<br />
Med. Flow <strong>To</strong>tal 93,360 119,100 162,860 182,440<br />
(10°F ∆T w<br />
) Sensible 87,000 113,600 162,860 182,440<br />
GPM / (pd. Ft.) 18.8 / (6.0) 24.0 / (9.3) 33.2 / (1.1) 37.0 / (1.4)<br />
Low Flow <strong>To</strong>tal 83,460 100,840 134,800 151,580<br />
(12°F ∆T w<br />
) Sensible 80,600 100,840 134,800 151,580<br />
GPM / (pd. Ft.) 14.0 / (3.5) 16.8 / (4.9) 23.0 / (0.5) 25.8 / (0.6)<br />
72°FDB/58.5°FWB, 45% RH<br />
High Flow <strong>To</strong>tal 78,9<strong>20</strong> 103,380 157,700 176,5<strong>20</strong><br />
(8°F ∆T w<br />
) Sensible 78,9<strong>20</strong> 103,380 157,700 176,5<strong>20</strong><br />
GPM / (pd. Ft.) <strong>20</strong>.0 / (6.7) 26.0 / (10.9) 40.2 / (1.6) 44.8 / (1.9)<br />
Med. Flow <strong>To</strong>tal 71,980 94,380 131,340 147,4<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 71,980 94,380 131,340 147,4<strong>20</strong><br />
GPM / (pd. Ft.) 14.4 / (3.7) 19.2 / (6.1) 26.8 / (0.7) 30.0 / (0.9)<br />
Low Flow <strong>To</strong>tal 64,260 84,1<strong>20</strong> 99,<strong>20</strong>0 112,680<br />
(12°F ∆T w<br />
) Sensible 64,260 84,1<strong>20</strong> 99,<strong>20</strong>0 112,680<br />
GPM / (pd. Ft.) 10.8 / (1.9) 14.4 / (3.6) 17.0 / (0.2) 19.4 / (0.3)<br />
70°FDB/57°FWB, 45% RH<br />
High Flow <strong>To</strong>tal 70,900 92,980 137,560 154,5<strong>20</strong><br />
(8°F ∆T w<br />
) Sensible 70,900 92,980 137,560 154,5<strong>20</strong><br />
GPM / (pd. Ft.) 18.0 / (5.5) 23.6 / (9.0) 35.0 / (1.2) 39.4 / (1.5)<br />
Med. Flow <strong>To</strong>tal 63,680 83,280 109,160 123,<strong>20</strong>0<br />
(10°F ∆T w<br />
) Sensible 63,680 83,280 109,160 123,<strong>20</strong>0<br />
GPM / (pd. Ft.) 12.8 / (2.9) 16.8 / (4.9) 22.4 / (0.5) 25.2 / (0.6)<br />
Low Flow <strong>To</strong>tal 55,400 72,580 85,9<strong>20</strong> 91,140<br />
(12°F ∆T w<br />
) Sensible 55,400 72,580 85,9<strong>20</strong> 91,140<br />
GPM / (pd. Ft.) 9.2 / (1.4) 12.4 / (2.6) 15.0 / (0.2) 15.8 / (0.2)<br />
4-7
Chilled Water - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />
"MCS" Model MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions<br />
3-way (standard) - Modulating (0-10 Vdc)<br />
Size / (Cv) 1" / (8.0 Cv) 1" / (8.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv)<br />
Qty. of Valves Per System 2(Two) 2(Two) 2(Two) 2(Two)<br />
Valve Pressure Rating 300 psig 300 psig 300 psig 300 psig<br />
<strong>To</strong>tal Unit Pressure Drop 8.0 Ft. 12.5 Ft. 7.8 Ft. 9.5 Ft.<br />
2-way (optional) - Modulating (0-10 Vdc)<br />
Size / (Cv) 1" / (8.0 Cv) 1" / (8.0 Cv) 1" / (18.0 Cv) 1" / (18.0 Cv)<br />
Qty. of Valves Per System 2(Two) 2(Two) 2(Two) 2(Two)<br />
Valve Pressure Rating 300 psig 300 psig 300 psig 300 psig<br />
<strong>To</strong>tal Unit Pressure Drop 7.9 Ft. 12.4 Ft. 6.7 Ft. 8.1 Ft.<br />
Chilled Water Coil - Aluminum Fin, Copper Tube<br />
Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />
Face Velocity, fpm 338 469 434 495<br />
Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />
Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />
CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />
Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />
Qty. of Blowers two two two two<br />
Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />
ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />
@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />
<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />
Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />
Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />
Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />
Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />
Standard Control Cycling Cycling Cycling Cycling<br />
Optional Control - - - - - - - - - - - - - - - - - Modulating (0-10 Vdc) - - - - - - - - - - - - - - - - -<br />
Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />
Up-Flow:<br />
Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />
(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />
Down-Flow:<br />
Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />
Connection Sizes - Copper<br />
Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />
Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />
Water In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />
Physical Data<br />
Approx. Weight 410 lbs x 2 410 lbs x 2 590 lbs x 2 590 lbs x 2<br />
Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />
MCS-( )-C-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />
MCS-( )-C-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />
><br />
Performance Data - Chilled Water (ModulAiR 7 to <strong>20</strong> ton Systems)<br />
4-8
Chilled Water - 42°F EWT, 0% Glycol<br />
Performance Data - Chilled Water Systems @ 42°F EWT<br />
Net Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil @ 50% RH<br />
75°FDB/62.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 127,860 163,5<strong>20</strong> 260,540 287,4<strong>20</strong><br />
(8°F ∆T w<br />
) Sensible 97,280 127,440 <strong>20</strong>9,800 235,000<br />
GPM/(Ft.) 32.0 / (16.0) 40.8 / (25.1) 65.6 / (3.9) 72.8 / (4.8)<br />
Med Flow <strong>To</strong>tal 117,140 151,160 226,780 252,780<br />
(10°F ∆T w<br />
) Sensible 92,0<strong>20</strong> 121,2<strong>20</strong> 192,640 216,140<br />
GPM/(Ft.) 23.6 / (9.0) 30.4 / (14.4) 46.0 / (2.0) 51.0 / (2.5)<br />
Low Flow <strong>To</strong>tal 107,400 139,1<strong>20</strong> 192,700 215,240<br />
(12°F ∆T w<br />
) Sensible 87,100 114,860 173,900 195,1<strong>20</strong><br />
GPM/(Ft.) 18.0 / (5.5) 23.2 / (8.8) 32.6 / (1.1) 36.4 / (1.3)<br />
72°FDB/60°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 106,380 137,140 213,0<strong>20</strong> 236,6<strong>20</strong><br />
(8°F ∆T w<br />
) Sensible 87,980 115,900 187,600 210,080<br />
GPM/(Ft.) 26.8 / (11.4) 34.4 / (18.2) 53.8 / (2.7) 59.6 / (3.3)<br />
Med Flow <strong>To</strong>tal 97,600 125,760 178,680 199,<strong>20</strong>0<br />
(10°F ∆T w<br />
) Sensible 83,3<strong>20</strong> 109,5<strong>20</strong> 167,880 188,160<br />
GPM/(Ft.) 19.6 / (6.5) 25.2 / (10.3) 36.2 / (1.3) 40.2 / (1.6)<br />
Low Flow <strong>To</strong>tal 88,960 114,900 129,940 146,1<strong>20</strong><br />
(12°F ∆T w<br />
) Sensible 78,360 102,860 129,940 146,1<strong>20</strong><br />
GPM/(Ft.) 14.8 / (3.9) 19.2 / (6.2) 22.2 / (0.4) 24.8 / (0.6)<br />
70°FDB/58.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 94,560 121,940 184,640 <strong>20</strong>5,480<br />
(8°F ∆T w<br />
) Sensible 81,780 107,660 171,280 191,9<strong>20</strong><br />
GPM/(Ft.) 24.0 / (9.3) 30.4 / (14.7) 46.8 / (2.1) 52.0 / (2.6)<br />
Med Flow <strong>To</strong>tal 86,1<strong>20</strong> 110,9<strong>20</strong> 138,180 154,980<br />
(10°F ∆T w<br />
) Sensible 76,940 100,940 138,180 154,980<br />
GPM/(Ft.) 17.6 / (5.2) 22.4 / (8.2) 28.2 / (0.8) 31.6 / (1.0)<br />
Low Flow <strong>To</strong>tal 76,900 98,840 106,540 1<strong>20</strong>,240<br />
(12°F ∆T w<br />
) Sensible 71,080 92,8<strong>20</strong> 106,540 1<strong>20</strong>,240<br />
GPM/(Ft.) 12.8 / (2.8) 16.8 / (4.8) 18.4 / (0.3) <strong>20</strong>.6 / (0.4)<br />
Net Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil @ 45% RH<br />
75°FDB/61°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 118,040 152,2<strong>20</strong> 242,640 269,840<br />
(8°F ∆T w<br />
) Sensible 99,960 131,780 216,560 242,7<strong>20</strong><br />
GPM/(Ft.) 29.6 / (13.8) 38.0 / (22.1) 61.2 / (3.5) 68.0 / (4.2)<br />
Med Flow <strong>To</strong>tal 109,460 141,440 210,640 233,700<br />
(10°F ∆T w<br />
) Sensible 95,340 125,660 198,<strong>20</strong>0 221,6<strong>20</strong><br />
GPM/(Ft.) 22.0 / (8.0) 28.4 / (12.8) 42.6 / (1.8) 47.2 / (2.1)<br />
Low Flow <strong>To</strong>tal 101,060 130,6<strong>20</strong> 162,440 182,140<br />
(12°F ∆T w<br />
) Sensible 90,480 118,980 162,440 182,140<br />
GPM/(Ft.) 16.8 / (4.9) 22.0 / (7.9) 27.6 / (0.7) 30.8 / (0.9)<br />
72°FDB/58.5°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 99,300 128,0<strong>20</strong> 197,0<strong>20</strong> 217,960<br />
(8°F ∆T w<br />
) Sensible 91,240 1<strong>20</strong>,060 192,460 214,8<strong>20</strong><br />
GPM/(Ft.) 25.2 / (10.1) 32.0 / (16.1) 49.8 / (2.4) 55.0 / (2.8)<br />
Med Flow <strong>To</strong>tal 91,300 116,580 158,440 177,460<br />
(10°F ∆T w<br />
) Sensible 86,<strong>20</strong>0 112,480 158,440 177,460<br />
GPM/(Ft.) 18.4 / (5.8) 23.6 / (9.0) 32.2 / (1.0) 36.0 / (1.3)<br />
Low Flow <strong>To</strong>tal 81,2<strong>20</strong> 99,260 129,380 145,500<br />
(12°F ∆T w<br />
) Sensible 79,440 99,260 129,380 145,500<br />
GPM/(Ft.) 13.6 / (3.2) 16.8 / (4.8) 22.0 / (0.4) 24.8 / (0.6)<br />
70°FDB/57°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 88,280 112,380 164,180 183,700<br />
(8°F ∆T w<br />
) Sensible 84,7<strong>20</strong> 110,400 164,180 183,700<br />
GPM/(Ft.) 22.4 / (8.3) 28.4 / (12.7) 41.8 / (1.7) 46.6 / (2.1)<br />
Med Flow <strong>To</strong>tal 75,<strong>20</strong>0 98,6<strong>20</strong> 137,700 154,440<br />
(10°F ∆T w<br />
) Sensible 75,<strong>20</strong>0 98,6<strong>20</strong> 137,700 154,440<br />
GPM/(Ft.) 15.2 / (4.1) <strong>20</strong>.0 / (6.7) 28.2 / (0.8) 31.4 / (1.0)<br />
Low Flow <strong>To</strong>tal 67,500 88,280 105,740 119,640<br />
(12°F ∆T w<br />
) Sensible 67,500 88,280 105,740 119,640<br />
GPM/(Ft.) 11.2 / (2.1) 14.8 / (3.9) 18.2 / (0.3) <strong>20</strong>.4 / (0.4)<br />
(Note:<br />
The above Net Cooling capacities include standard motor heat @ standard CFM / e.s.p. as shown on page 4-8, Evaporator Blower/Motor.)<br />
4-9
Chilled Water - 50°F EWT, 0% Glycol<br />
Net Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil @ 50% RH<br />
75°FDB/62.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 79,180 100,400 143,400 160,640<br />
(8°F ∆T w<br />
) Sensible 74,4<strong>20</strong> 97,0<strong>20</strong> 143,400 160,640<br />
GPM/(Ft.) <strong>20</strong>.0 / (6.6) 25.2 / (10.2) 36.6 / (1.3) 40.8 / (1.6)<br />
Med Flow <strong>To</strong>tal 65,3<strong>20</strong> 85,580 116,660 131,600<br />
(10°F ∆T w<br />
) Sensible 65,3<strong>20</strong> 85,580 116,660 131,600<br />
GPM/(Ft.) 13.2 / (3.1) 17.6 / (5.1) 24.0 / (0.5) 27.0 / (0.7)<br />
Low Flow <strong>To</strong>tal 57,300 75,100 86,740 94,900<br />
(12°F ∆T w<br />
) Sensible 57,300 75,100 86,740 94,900<br />
GPM/(Ft.) 9.6 / (1.5) 12.8 / (2.8) 15.0 / (0.2) 16.4 / (0.2)<br />
72°FDB/60°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 59,9<strong>20</strong> 78,640 112,5<strong>20</strong> 126,340<br />
(8°F ∆T w<br />
) Sensible 59,9<strong>20</strong> 78,640 112,5<strong>20</strong> 126,340<br />
GPM/(Ft.) 15.2 / (4.0) <strong>20</strong>.0 / (6.6) 29.0 / (0.8) 32.4 / (1.0)<br />
Med Flow <strong>To</strong>tal 52,360 68,5<strong>20</strong> 81,400 92,3<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 52,360 68,5<strong>20</strong> 81,400 92,3<strong>20</strong><br />
GPM/(Ft.) 10.8 / (1.9) 14.0 / (3.4) 17.0 / 0.2) 19.2 / (0.3)<br />
Low Flow <strong>To</strong>tal 43,480 56,980 68,460 72,600<br />
(12°F ∆T w<br />
) Sensible 43,480 56,980 68,460 72,600<br />
GPM/(Ft.) 7.6 / (0.8) 9.6 / (1.5) 12.0 / (0.1) 12.8 / (0.1)<br />
70°FDB/58.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 51,660 67,6<strong>20</strong> 90,600 102,400<br />
(8°F ∆T w<br />
) Sensible 51,660 67,6<strong>20</strong> 90,600 102,400<br />
GPM/(Ft.) 13.2 / (3.1) 17.2 / (5.0) 23.4 / (0.5) 26.4 / (0.7)<br />
Med Flow <strong>To</strong>tal 43,4<strong>20</strong> 56,860 66,1<strong>20</strong> 70,1<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 43,4<strong>20</strong> 56,860 66,1<strong>20</strong> 70,1<strong>20</strong><br />
GPM/(Ft.) 8.8 / (1.2) 11.6 / (2.3) 14.0 / (0.2) 14.8 / (0.2)<br />
Low Flow <strong>To</strong>tal 35,660 44,<strong>20</strong>0 56,580 59,760<br />
(12°F ∆T w<br />
) Sensible 35,660 44,<strong>20</strong>0 56,580 59,760<br />
GPM/(Ft.) 6.0 / (0.6) 7.6 / (0.8) 10.0 / (0.1) 10.6 / (0.1)<br />
Net Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil @ 45% RH<br />
75°FDB/61°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 72,040 94,540 142,960 160,160<br />
(8°F ∆T w<br />
) Sensible 72,040 94,540 142,960 160,160<br />
GPM/(Ft.) 18.4 / (5.6) 24.0 / (9.2) 36.4 / (1.3) 40.6 / (1.6)<br />
Med Flow <strong>To</strong>tal 65,100 85,360 116,180 131,060<br />
(10°F ∆T w<br />
) Sensible 65,100 85,360 116,180 131,060<br />
GPM/(Ft.) 13.2 / (3.1) 17.2 / (5.1) 23.8 / (0.5) 26.8 / (0.7)<br />
Low Flow <strong>To</strong>tal 57,100 74,860 86,480 94,3<strong>20</strong><br />
(12°F ∆T w<br />
) Sensible 57,100 74,860 86,480 94,3<strong>20</strong><br />
GPM/(Ft.) 9.6 / (1.5) 12.8 / (2.8) 15.0 / (0.2) 16.4 / (0.2)<br />
72°FDB/58.5°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 59,780 78,440 112,140 125,900<br />
(8°F ∆T w<br />
) Sensible 59,780 78,440 112,140 125,900<br />
GPM/(Ft.) 15.2 / (4.0) <strong>20</strong>.0 / (6.6) 28.8 / (0.8) 32.2 / (1.0)<br />
Med Flow <strong>To</strong>tal 52,<strong>20</strong>0 68,3<strong>20</strong> 80,960 91,8<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 52,<strong>20</strong>0 68,3<strong>20</strong> 80,960 91,8<strong>20</strong><br />
GPM/(Ft.) 10.8/ (1.9) 14.0 / (3.4) 16.8 / (0.2) 19.0 / (0.3)<br />
Low Flow <strong>To</strong>tal 43,300 56,760 68,240 72,380<br />
(12°F ∆T w<br />
) Sensible 43,300 56,760 68,240 72,380<br />
GPM/(Ft.) 7.2 / (0.8) 9.6 / (1.5) 12.0 / (0.1) 12.6 / (0.1)<br />
Performance Data - Chilled Water Systems @ 50°F EWT<br />
70°FDB/57°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />
High Flow <strong>To</strong>tal 51,5<strong>20</strong> 67,460 90,2<strong>20</strong> 102,000<br />
(8°F ∆T w<br />
) Sensible 51,5<strong>20</strong> 67,460 90,2<strong>20</strong> 102,000<br />
GPM/(Ft.) 13.2 / (3.0) 17.2 / (5.0) 23.4 / (0.5) 26.4 / (0.7)<br />
Med Flow <strong>To</strong>tal 43,280 56,660 65,9<strong>20</strong> 69,9<strong>20</strong><br />
(10°F ∆T w<br />
) Sensible 43,280 56,660 65,9<strong>20</strong> 69,9<strong>20</strong><br />
GPM/(Ft.) 8.8 / (1.2) 11.6 / (2.3) 14.0 / (0.2) 14.8 / (0.2)<br />
Low Flow <strong>To</strong>tal 35,560 44,000 56,400 59,560<br />
(12°F ∆T w<br />
) Sensible 35,560 44,000 56,400 59,560<br />
GPM/(Ft.) 6.0 / (0.5) 7.6 / (0.8) 10.0 / (0.1) 10.6 / (0.1)<br />
(Note:<br />
The above Net Cooling capacities include standard motor heat @ standard CFM / e.s.p. as shown on page 4-8, Evaporator Blower/Motor.)<br />
4-10
Electrical Data - "ModulAiR" DX Compressorized Systems<br />
Electrical Data - "ModulAiR" DX Compressorized Systems<br />
MODEL<br />
MCS-084-DAR, DW & DG<br />
(7 <strong>To</strong>n, Single Pt. Power)<br />
DAR<br />
COOLING with<br />
FLA (OEM rated)<br />
DW<br />
DG<br />
MCA<br />
MFS<br />
MCS-1<strong>20</strong>-DAR, DW & DG<br />
(10 <strong>To</strong>n, Single Pt. Power)<br />
DAR<br />
FLA (OEM rated)<br />
DW<br />
Systems<br />
with<br />
MCA<br />
MFS<br />
Remote <strong>Air</strong> Cooled Condensers<br />
DG<br />
10<br />
Kw<br />
ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />
MCS-192-DAR, DW & DG<br />
(16 <strong>To</strong>n, Single Pt. Power)<br />
DAR<br />
FLA (OEM rated)<br />
DW<br />
DG<br />
10<br />
Kw<br />
Electric Reheat and/or Heat<br />
MCA<br />
MFS<br />
MCS-240-DAR, DW & DG<br />
(<strong>20</strong> <strong>To</strong>n Single Pt. Power)<br />
DAR<br />
FLA (OEM rated)<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
27.<br />
3 25.<br />
5 27.<br />
9 37.<br />
7 40<br />
32.<br />
5 30.<br />
1 33.<br />
3 43.<br />
5 50<br />
54.<br />
2 50.<br />
8 55.<br />
2 70.<br />
0 80<br />
61.<br />
2 57.<br />
0 62.<br />
6 76.<br />
3 90<br />
575/3/60<br />
21.<br />
9 <strong>20</strong>.<br />
5 22.<br />
4 29.<br />
9 30<br />
26.<br />
0 24.<br />
1 26.<br />
7 33.<br />
5 35<br />
43.<br />
9 40.<br />
9 44.<br />
7 53.<br />
8 60<br />
48.<br />
7 44.<br />
9 49.<br />
9 57.<br />
8 60<br />
COOLING and<br />
10<br />
Kw<br />
ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
27.<br />
3 25.<br />
5 27.<br />
9 37.<br />
7 40<br />
32.<br />
5 30.<br />
1 33.<br />
3 43.<br />
5 50<br />
54.<br />
2 50.<br />
8 55.<br />
2 70.<br />
0 80<br />
61.<br />
2 57.<br />
0 62.<br />
6 76.<br />
3 90<br />
575/3/60<br />
21.<br />
9 <strong>20</strong>.<br />
5 22.<br />
4 29.<br />
9 30<br />
26.<br />
0 24.<br />
1 26.<br />
7 33.<br />
5 35<br />
43.<br />
9 40.<br />
9 44.<br />
7 53.<br />
8 60<br />
48.<br />
7 44.<br />
9 49.<br />
9 57.<br />
8 60<br />
COOLING and<br />
10<br />
Kw<br />
ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
16.<br />
1 16.<br />
1 16.<br />
1 22.<br />
0 30<br />
19.<br />
9 17.<br />
9 <strong>20</strong>.<br />
7 27.<br />
8 35<br />
41.<br />
6 38.<br />
2 42.<br />
6 54.<br />
3 70<br />
48.<br />
6 44.<br />
4 50.<br />
0 60.<br />
6 70<br />
575/3/60<br />
13.<br />
0 13.<br />
0 13.<br />
0 17.<br />
3 <strong>20</strong><br />
16.<br />
0 14.<br />
4 16.<br />
6 21.<br />
0 25<br />
33.<br />
8 30.<br />
8 34.<br />
7 41.<br />
2 50<br />
38.<br />
6 34.<br />
8 39.<br />
8 45.<br />
3 50<br />
COOLING with<br />
Systems<br />
with Optional<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />
<strong>20</strong><br />
Kw<br />
Electric Reheat and/or Heat<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
39.<br />
9 25.<br />
5 27.<br />
9 53.<br />
4 60<br />
45.<br />
1 30.<br />
1 33.<br />
3 59.<br />
2 60<br />
66.<br />
8 50.<br />
8 55.<br />
2 85.<br />
7 90<br />
73.<br />
8 57.<br />
0 62.<br />
6 92.<br />
0 100<br />
575/3/60<br />
32.<br />
0 <strong>20</strong>.<br />
5 22.<br />
4 42.<br />
5 45<br />
36.<br />
1 24.<br />
1 26.<br />
7 46.<br />
1 50<br />
53.<br />
9 40.<br />
9 44.<br />
7 66.<br />
4 70<br />
58.<br />
7 44.<br />
9 49.<br />
9 70.<br />
4 80<br />
COOLING and<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
39.<br />
9 25.<br />
5 27.<br />
9 53.<br />
4 60<br />
45.<br />
1 30.<br />
1 33.<br />
3 59.<br />
2 60<br />
66.<br />
8 50.<br />
8 55.<br />
2 85.<br />
7 90<br />
73.<br />
8 57.<br />
0 62.<br />
6 92.<br />
0 100<br />
575/3/60<br />
32.<br />
0 <strong>20</strong>.<br />
5 22.<br />
4 42.<br />
5 45<br />
36.<br />
1 24.<br />
1 26.<br />
7 46.<br />
1 50<br />
53.<br />
9 40.<br />
9 44.<br />
7 66.<br />
4 70<br />
58.<br />
7 44.<br />
9 49.<br />
9 70.<br />
4 80<br />
COOLING and<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
17.<br />
1 15.<br />
6 17.<br />
5 22.<br />
5 25<br />
21.<br />
2 19.<br />
3 21.<br />
8 26.<br />
2 30<br />
39.<br />
0 36.<br />
0 39.<br />
9 46.<br />
4 60<br />
43.<br />
8 40.<br />
0 45.<br />
0 50.<br />
5 60<br />
575/3/60<br />
23.<br />
0 13.<br />
0 13.<br />
0 28.<br />
8 30<br />
24.<br />
4 14.<br />
4 16.<br />
6 30.<br />
5 35<br />
34.<br />
3 30.<br />
8 34.<br />
7 42.<br />
9 50<br />
38.<br />
6 34.<br />
8 39.<br />
8 45.<br />
3 50<br />
Systems<br />
COOLING and HUMIDIFIER ONLY, (No Electric RH/HT)<br />
W<br />
ithout<br />
Electric Reheat and/or Heat<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
21.<br />
1 19.<br />
3 21.<br />
7 28.<br />
4 35<br />
26.<br />
3 23.<br />
9 27.<br />
1 34.<br />
2 40<br />
48.<br />
0 44.<br />
6 49.<br />
0 60.<br />
7 70<br />
55.<br />
0 50.<br />
8 56.<br />
4 67.<br />
0 80<br />
575/3/60<br />
17.<br />
1 15.<br />
6 17.<br />
5 22.<br />
5 25<br />
21.<br />
2 19.<br />
3 21.<br />
8 26.<br />
2 30<br />
39.<br />
0 36.<br />
0 39.<br />
9 46.<br />
4 50<br />
43.<br />
8 40.<br />
0 45.<br />
0 50.<br />
5 60<br />
COOLING ONLY, (No Electric RH/HT or Humidifier)<br />
<strong>20</strong>8/3/60<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
- - - - - -<br />
460/3/60<br />
14.<br />
7 12.<br />
9 15.<br />
3 22.<br />
0 30<br />
19.<br />
9 17.<br />
5 <strong>20</strong>.<br />
7 27.<br />
8 40<br />
41.<br />
6 38.<br />
2 42.<br />
6 54.<br />
3 70<br />
48.<br />
6 44.<br />
4 50.<br />
0 60.<br />
6 70<br />
575/3/60<br />
11.<br />
9 10.<br />
4 12.<br />
3 17.<br />
3 <strong>20</strong><br />
16.<br />
0 14.<br />
1 16.<br />
6 21.<br />
0 25<br />
33.<br />
8 30.<br />
8 34.<br />
7 41.<br />
2 50<br />
38.<br />
6 34.<br />
8 39.<br />
8 45.<br />
3 50<br />
OUTDOOR<br />
<strong>20</strong>8/3/60<br />
460/3/60<br />
575/3/60<br />
MODEL<br />
FLA<br />
MCA<br />
MFS<br />
HES-1<strong>20</strong>-DLSA or DLFA 5.<br />
2 5.<br />
9 15<br />
2.<br />
6 2.<br />
9 15<br />
1.<br />
9 2.<br />
4 15<br />
HES-168-DLSA or DLFA 5.<br />
2 5.<br />
9 15<br />
2.<br />
6 2.<br />
9 15<br />
1.<br />
9 2.<br />
4 15<br />
HES-192-DLSA or DLFA 5.<br />
2 5.<br />
9 15<br />
2.<br />
6 2.<br />
9 15<br />
1.<br />
9 2.<br />
4 15<br />
HES-339-DLSA or DLFA 14.<br />
0 15.<br />
8 <strong>20</strong><br />
7.<br />
0 8.<br />
8 15<br />
5.<br />
6 7.<br />
0 15<br />
HES-399-DLSA or DLFA 14.<br />
0 15.<br />
8 <strong>20</strong><br />
7.<br />
0 8.<br />
8 15<br />
5.<br />
6 7.<br />
0 15<br />
HES-525-DLSA or DLFA 14.<br />
0 15.<br />
8 <strong>20</strong><br />
7.<br />
0 8.<br />
8 15<br />
5.<br />
6 7.<br />
0 15<br />
FLA<br />
MCA<br />
MFS<br />
FLA<br />
MCA<br />
MFS<br />
DW<br />
DG<br />
Table Legend:<br />
MCA<br />
MFS<br />
- - - - - Consult Factory for<br />
<strong>20</strong>8/3/60 Applications.<br />
FLA<br />
MCA<br />
MFS<br />
FLA = Full Load Amps<br />
MCA = Minimum Circuit Amps<br />
(wire size amps)<br />
MFS = Maximum Fuse Size<br />
5-1
Electrical Data - "ModulAiR" Chilled Water Systems<br />
MODEL<br />
Example:<br />
MCS-084-C<br />
(7 <strong>To</strong>n, Single Pt.)<br />
FLA<br />
COOLING with<br />
MCA<br />
MFS<br />
Systems<br />
with<br />
MCS-1<strong>20</strong>-C<br />
(10 <strong>To</strong>n, Single Pt.)<br />
FLA<br />
MCA<br />
MFS<br />
MCS-192-C<br />
(16 <strong>To</strong>n, Single Pt.)<br />
Suppose an application calls for a nominal <strong>20</strong> <strong>To</strong>n ModulAiR air cooled<br />
split system with the following features:<br />
MCS-240-DAR-()<br />
HES-168-DLSA<br />
- 460/3/60 Main Power Supply (both evap and cond)<br />
- 10 Kw Electric Reheat/Heat, (Standard)<br />
- 15 lb/hr Steam Humidifier, (Standard)<br />
Solution:<br />
<strong>From</strong> DX Compressorized Electrical Data table shown on page 5-1 for<br />
model MCS-240-DAR incorporating COOLING with ELECTRIC<br />
REHEAT/HEAT and HUMIDIFIER:<br />
FLA<br />
MCA<br />
MFS<br />
MCS-240-C<br />
(<strong>20</strong> <strong>To</strong>n, Single Pt.)<br />
FLA<br />
10<br />
Kw<br />
Electric Reheat and/or Heat<br />
10<br />
Kw<br />
ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />
<strong>20</strong>8/3/60<br />
45.<br />
9 57.<br />
3 60<br />
49.<br />
5 61.<br />
8 70<br />
72.<br />
7 90.<br />
8 100<br />
72.<br />
7 90.<br />
8 100<br />
460/3/60<br />
22.<br />
5 28.<br />
1 30<br />
24.<br />
3 30.<br />
3 35<br />
35.<br />
9 44.<br />
8 50<br />
35.<br />
9 44.<br />
8 50<br />
575/3/60<br />
18.<br />
2 22.<br />
7 25<br />
19.<br />
6 24.<br />
5 25<br />
29.<br />
0 36.<br />
2 45<br />
29.<br />
0 36.<br />
2 45<br />
COOLING and<br />
10<br />
Kw<br />
ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />
<strong>20</strong>8/3/60<br />
31.<br />
7 39.<br />
6 40<br />
35.<br />
3 44.<br />
1 45<br />
58.<br />
5 73.<br />
1 90<br />
58.<br />
5 73.<br />
1 90<br />
460/3/60<br />
16.<br />
1 <strong>20</strong>.<br />
1 25<br />
17.<br />
9 22.<br />
3 25<br />
29.<br />
5 36.<br />
8 50<br />
29.<br />
5 36.<br />
8 50<br />
575/3/60<br />
13.<br />
0 16.<br />
2 <strong>20</strong><br />
14.<br />
4 18.<br />
0 <strong>20</strong><br />
23.<br />
8 29.<br />
7 40<br />
23.<br />
8 29.<br />
7 40<br />
COOLING and<br />
10<br />
Kw<br />
ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />
<strong>20</strong>8/3/60<br />
31.<br />
7 39.<br />
6 40<br />
35.<br />
3 44.<br />
1 45<br />
58.<br />
5 73.<br />
1 90<br />
58.<br />
5 73.<br />
1 90<br />
460/3/60<br />
16.<br />
1 <strong>20</strong>.<br />
1 25<br />
17.<br />
9 22.<br />
3 25<br />
29.<br />
5 36.<br />
8 50<br />
29.<br />
5 36.<br />
8 50<br />
575/3/60<br />
13.<br />
0 16.<br />
2 <strong>20</strong><br />
14.<br />
4 18.<br />
0 <strong>20</strong><br />
23.<br />
8 29.<br />
7 40<br />
23.<br />
8 29.<br />
7 40<br />
COOLING with<br />
Systems<br />
with Optional<br />
<strong>20</strong><br />
Kw<br />
Electric Reheat and/or Heat<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />
<strong>20</strong>8/3/60<br />
71.<br />
0 88.<br />
8 90<br />
74.<br />
6 93.<br />
3 100<br />
97.<br />
8 122.<br />
3 125<br />
97.<br />
8 122.<br />
3 125<br />
460/3/60<br />
35.<br />
1 43.<br />
8 45<br />
36.<br />
9 46.<br />
1 50<br />
48.<br />
5 60.<br />
6 70<br />
48.<br />
5 60.<br />
6 70<br />
575/3/60<br />
28.<br />
2 35.<br />
3 40<br />
29.<br />
6 37.<br />
0 40<br />
39.<br />
0 48.<br />
8 50<br />
39.<br />
0 48.<br />
8 50<br />
COOLING and<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />
<strong>20</strong>8/3/60<br />
56.<br />
8 71.<br />
0 80<br />
60.<br />
4 75.<br />
5 80<br />
83.<br />
6 104.<br />
5 125<br />
83.<br />
6 104.<br />
5 125<br />
460/3/60<br />
28.<br />
7 35.<br />
8 40<br />
30.<br />
5 38.<br />
1 40<br />
42.<br />
1 52.<br />
6 60<br />
42.<br />
1 52.<br />
6 60<br />
575/3/60<br />
23.<br />
0 28.<br />
8 30<br />
24.<br />
4 30.<br />
5 35<br />
33.<br />
8 42.<br />
3 50<br />
33.<br />
8 42.<br />
3 50<br />
COOLING and<br />
MCA<br />
<strong>20</strong><br />
Kw<br />
ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />
<strong>20</strong>8/3/60<br />
56.<br />
8 71.<br />
0 80<br />
60.<br />
4 75.<br />
5 80<br />
83.<br />
6 104.<br />
5 125<br />
83.<br />
6 104.<br />
5 125<br />
460/3/60<br />
28.<br />
7 35.<br />
8 40<br />
30.<br />
5 38.<br />
1 40<br />
42.<br />
1 52.<br />
6 60<br />
42.<br />
1 52.<br />
6 60<br />
575/3/60<br />
23.<br />
0 28.<br />
8 30<br />
24.<br />
4 30.<br />
5 35<br />
33.<br />
8 42.<br />
3 50<br />
33.<br />
8 42.<br />
3 50<br />
Systems<br />
W<br />
ithout<br />
COOLING and HUMIDIFIER ONLY, (No Electric RH/HT)<br />
Electric Reheat and/or Heat<br />
<strong>20</strong>8/3/60<br />
<strong>20</strong>.<br />
7 25.<br />
9 30<br />
24.<br />
3 30.<br />
4 35<br />
47.<br />
5 59.<br />
4 80<br />
47.<br />
5 59.<br />
4 80<br />
460/3/60<br />
9.<br />
9 12.<br />
4 15<br />
11.<br />
7 14.<br />
6 <strong>20</strong><br />
23.<br />
3 29.<br />
1 40<br />
23.<br />
3 29.<br />
1 40<br />
575/3/60<br />
8.<br />
1 10.<br />
1 15<br />
9.<br />
5 11.<br />
9 <strong>20</strong><br />
18.<br />
9 23.<br />
6 35<br />
18.<br />
9 23.<br />
6 35<br />
COOLING ONLY, (No Electric RH/HT or Humidifier)<br />
<strong>20</strong>8/3/60<br />
6.<br />
5 8.<br />
1 15<br />
10.<br />
1 12.<br />
6 <strong>20</strong><br />
33.<br />
3 41.<br />
6 70<br />
33.<br />
3 41.<br />
6 70<br />
460/3/60<br />
3.<br />
5 4.<br />
4 15<br />
5.<br />
3 6.<br />
6 15<br />
16.<br />
9 21.<br />
1 35<br />
16.<br />
9 21.<br />
1 35<br />
575/3/60<br />
2.<br />
9 3.<br />
6 15<br />
4.<br />
3 5.<br />
4 15<br />
13.<br />
7 17.<br />
1 30<br />
13.<br />
7 17.<br />
1 30<br />
MFS<br />
MCS-240-DAR @ 460/3/60 with above options:<br />
61.2 FLA / 76.3 MCA / 90 MFS<br />
HES-168-DLSA @ 460/3/60 with above options:<br />
2.6 FLA / 2.9 MCA / 15 MFS<br />
Table Legend:<br />
FLA<br />
MCA<br />
MFS<br />
FLA = Full Load Amps<br />
MCA = Minimum Circuit Amps (wire size amps)<br />
MFS = Maximum Fuse Size<br />
Electrical Data - "ModulAiR" Chilled Water Systems<br />
5-2
7 to 10 <strong>To</strong>n MCS - "Down-Flow" <strong>Air</strong> Pattern Systems<br />
Dimensional Data - 7 to 10 <strong>To</strong>ns ("Down-Flow" <strong>Air</strong> Pattern Systems)<br />
(MC-01) MCS-084/1<strong>20</strong>-DAR, DW, DG & C-D<br />
"Down-Flow" Modular Vertical A/C<br />
("Free-Return" or "Ducted-Return")<br />
Filter<br />
Access<br />
29.0"<br />
2.62"<br />
(Filler)<br />
Optional 1.0"<br />
Duct Flange<br />
Connection<br />
62.12"<br />
(Overall) 29.0"<br />
(Base)<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Into Raised Floor<br />
FRONT / RIGHT<br />
60.62"<br />
Filter Box<br />
(Field Installed)<br />
1.0"<br />
76.0"<br />
29.0"<br />
(Base)<br />
29.75"<br />
(Overall)<br />
Adjustable Floor Stand: (Optional)<br />
24.0" High<br />
Stands Only<br />
29.0"<br />
8.78"<br />
28.63"<br />
7.62"<br />
19.8"<br />
60.62"<br />
6.0"<br />
21.4"<br />
82.0"<br />
A<br />
83.0"<br />
w/ Optional<br />
Duct<br />
Connection<br />
BLOWER DIMENSIONAL DATA<br />
M ODEL<br />
“ L”<br />
“M”<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
M CL<br />
REA R / LEFT<br />
Dimensional<br />
Data - Floor Stand Heights<br />
Floor Stand<br />
Nominal Height<br />
Piping<br />
Connections<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Into Raised Floor<br />
"A" Dimension<br />
Adjustable Height<br />
Minimum<br />
2.0"<br />
Utility<br />
Connections<br />
Maximum<br />
Turning Vane<br />
Availability<br />
4 .0" ( Upflow Units Only)<br />
3 .5"<br />
4.5"<br />
Not Availabl e<br />
6 .0"<br />
5 .0"<br />
7.0"<br />
Not Availabl e<br />
12.0"<br />
11.0"<br />
15.0"<br />
Optional<br />
15.0"<br />
14.0"<br />
18.0"<br />
Optional<br />
18.0"<br />
17.0"<br />
21.0"<br />
Optional<br />
24.0"<br />
23.0"<br />
26.0"<br />
Optional<br />
L<br />
Based on<br />
Std CFM @<br />
M CS-084 & 1<strong>20</strong>-( )-D 11.38"<br />
13.12"<br />
0.5" e.s. p<br />
28.63"<br />
24.0" High<br />
Stands Only<br />
6-1
7 to 10 <strong>To</strong>n MCS - "Up-Flow" <strong>Air</strong> Pattern Systems<br />
(MC-02) MCS-084/1<strong>20</strong>-DAR, DW, DG & C-U<br />
"Up-Flow" Modular Vertical A/C<br />
(as "Ducted or with Opt. "2 or 3-way Plenum Box")<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
18.5"<br />
29.0"<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
29.0"<br />
60.62"<br />
2.62"<br />
(Filler)<br />
62.12"<br />
(Overall) 29.0"<br />
(Base)<br />
60.62"<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
FRONT / RIGHT<br />
C M L<br />
2 or 3-Way Plenum<br />
Discharge Box - field<br />
installed (Optional)<br />
29.0"<br />
(Base)<br />
29.75"<br />
(Overall)<br />
Adjustable Floor Stand: (Optional)<br />
24.0" High<br />
Stands Only<br />
29.0"<br />
28.63"<br />
60.62"<br />
L<br />
Standard 1.0"<br />
Duct Flange<br />
Connection<br />
1.0"<br />
2.0"<br />
76.0"<br />
A<br />
77.0"<br />
w/ Standard<br />
Duct<br />
Connection<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
BLOWER DIMENSIONAL DATA<br />
M ODEL<br />
“ L”<br />
“M”<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Dimensional<br />
Data -<br />
Floor Stand<br />
Nominal Height<br />
REA R / LEFT<br />
Floor Stand Heights<br />
"A" Dimension<br />
Adjustable Height<br />
Minimum<br />
Piping<br />
Connections<br />
Maximum<br />
4 .0" ( Upflow Units Only)<br />
3 .5"<br />
4.5"<br />
6 .0"<br />
5 .0"<br />
7.0"<br />
12.0"<br />
11.0"<br />
15.0"<br />
15.0"<br />
14.0"<br />
18.0"<br />
18.0"<br />
17.0"<br />
21.0"<br />
24.0"<br />
23.0"<br />
26.0"<br />
Based on<br />
Std CFM @<br />
M CS-084 & 1<strong>20</strong>-( )-U 11.38"<br />
13.12"<br />
0.5" e.s. p<br />
Utility<br />
Connections<br />
Dimensional Data - 7 to 10 <strong>To</strong>ns ("Up-Flow" <strong>Air</strong> Pattern Systems)<br />
28.63"<br />
24.0" High<br />
Stands Only<br />
6-2
16 to <strong>20</strong> <strong>To</strong>n MCS - "Down-Flow" <strong>Air</strong> Pattern Systems<br />
Dimensional Data - 16 to <strong>20</strong> <strong>To</strong>ns ("Down-Flow" <strong>Air</strong> Pattern Systems)<br />
(MC-03) MCS-192/240-DAR, DW, DG & C-D<br />
Filter<br />
Access<br />
"Down-Flow" Modular Vertical A/C<br />
("Free-Return" or "Ducted-Return")<br />
34.0"<br />
Adjustable Floor Stand: (Optional)<br />
24.0" High<br />
Stands Only<br />
2.62"<br />
(Filler)<br />
79.12"<br />
(Overall) 37.5"<br />
(Base)<br />
32.88"<br />
8.78"<br />
Optional 1.0"<br />
Duct Flange<br />
Connection<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Into Raised Floor<br />
37.14"<br />
FRONT / RIGHT<br />
7.5"<br />
19.8"<br />
79.12"<br />
Filter Box<br />
(Field Installed)<br />
76.0"<br />
32.88"<br />
(Base)<br />
34.0"<br />
(Overall)<br />
77.63"<br />
6.0"<br />
19.8"<br />
1.0"<br />
10.2"<br />
82.0"<br />
83.0"<br />
w/ Optional<br />
Duct<br />
Connection<br />
A<br />
BLOWER DIMENSIONAL DATA<br />
M ODEL<br />
“ L”<br />
“M”<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Dimensional<br />
Data - Floor Stand Heights<br />
Floor Stand<br />
Nominal Height<br />
M<br />
Piping<br />
Connections<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
Into Raised Floor<br />
REAR / LEFT<br />
"A" Dimension<br />
Adjustable Height<br />
Minimum<br />
9.6"<br />
Maximum<br />
Based on<br />
Std CFM @<br />
M CS-192 & 240-( )-D 13.44"<br />
15.62"<br />
0.5" e.s. p<br />
1.75"<br />
Utility<br />
Connections<br />
Turning Vane<br />
Availability<br />
4 .0" ( Upflow Units Only)<br />
3 .5"<br />
4.5"<br />
Not Availabl e<br />
6 .0"<br />
5 .0"<br />
7.0"<br />
Not Availabl e<br />
12.0"<br />
11.0"<br />
15.0"<br />
Optional<br />
15.0"<br />
14.0"<br />
18.0"<br />
Optional<br />
18.0"<br />
17.0"<br />
21.0"<br />
Optional<br />
24.0"<br />
23.0"<br />
26.0"<br />
Optional<br />
L<br />
37.14"<br />
24.0" High<br />
Stands Only<br />
6-3
16 to <strong>20</strong> <strong>To</strong>n MCS - "Up-Flow" <strong>Air</strong> Pattern Systems<br />
(MC-04) MCS-192/240-DAR, DW, DG & C-U<br />
"Up-Flow" Modular Vertical A/C<br />
(as "Ducted or with Opt. "2 or 3-way Plenum Box")<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
Adjustable Floor Stand: (Optional)<br />
24.0" High<br />
Stands Only<br />
18.5"<br />
34.0"<br />
32.88"<br />
Evaporator<br />
<strong>Air</strong> Inlet<br />
2.62"<br />
(Filler)<br />
79.12"<br />
(Overall) 37.5"<br />
(Base)<br />
32.88"<br />
77.62"<br />
37.14"<br />
79.12"<br />
Evaporator<br />
<strong>Air</strong> Outlet<br />
FRONT / RIGHT<br />
2 or 3-Way Plenum<br />
Discharge Box - field<br />
installed (Optional)<br />
M<br />
L<br />
8.5"<br />
1.75"<br />
1.0"<br />
76.0"<br />
32.88"<br />
(Base)<br />
34.0"<br />
(Overall)<br />
77.63"<br />
Standard 1.0"<br />
Duct Flange<br />
Connection<br />
77.0"<br />
w/ Standard<br />
Duct<br />
Connection<br />
A<br />
BLOWER DIMENSIONAL DATA<br />
M ODEL<br />
“ L”<br />
“M”<br />
Piping<br />
Connections<br />
Dimensional<br />
Data -<br />
Floor Stand<br />
Nominal Height<br />
REAR / LEFT<br />
Floor Stand Heights<br />
"A" Dimension<br />
Adjustable Height<br />
Minimum<br />
Maximum<br />
4 .0" ( Upflow Units Only)<br />
3 .5"<br />
4.5"<br />
6 .0"<br />
5 .0"<br />
7.0"<br />
Based on<br />
Std CFM @<br />
M CS-192 & 240-( )-U 13.44"<br />
15.62"<br />
0.5" e.s. p<br />
12.0"<br />
11.0"<br />
15.0"<br />
15.0"<br />
14.0"<br />
18.0"<br />
18.0"<br />
17.0"<br />
21.0"<br />
24.0"<br />
23.0"<br />
26.0"<br />
Utility<br />
Connections<br />
Dimensional Data - 16 to <strong>20</strong> <strong>To</strong>ns ("Up-Flow" <strong>Air</strong> Pattern Systems)<br />
37.14"<br />
24.0" High<br />
Stands Only<br />
6-4
<strong>Air</strong> Cooled - Remote Outdoor DX Condensers<br />
Dimensional Data - <strong>Air</strong> Cooled (Remote Outdoor DX Condensers)<br />
(MC-05) HES-1<strong>20</strong> thru 525-DL()A<br />
Outdoor - Propeller Fan<br />
Remote <strong>Air</strong> Cooled Condenser<br />
A<br />
B<br />
D<br />
C<br />
DIMENSIONAL DATA<br />
M ODEL<br />
“ A”<br />
“ B”<br />
“ C”<br />
“ D”<br />
Approx. Wt.<br />
H ES-1<strong>20</strong>-DLSA & DLFA 69.75"<br />
43.0"<br />
41.0"<br />
60.0"<br />
450 lbs.<br />
H ES-168-DLSA & DLFA 89.75"<br />
43.0"<br />
41.0"<br />
80.0"<br />
510 lbs.<br />
H ES-192-DLSA & DLFA 89.75"<br />
43.0"<br />
41.0"<br />
80.0"<br />
530 lbs.<br />
H ES-339-DLSA & DLFA 1<strong>20</strong>.5"<br />
45.5"<br />
50.0"<br />
114.0"<br />
730 lbs.<br />
H ES-399-DLSA & DLFA 1<strong>20</strong>.5"<br />
45.5"<br />
50.0"<br />
114.0"<br />
770 lbs.<br />
H ES-525-DLSA & DLFA 1<strong>20</strong>.5"<br />
45.5"<br />
50.0"<br />
114.0"<br />
880 lbs.<br />
6-5
1572 Tilco Drive, Frederick, Maryland 21704, USA Copyright 12/01 - Form L-01-F-140<br />
Phone: (301) 6<strong>20</strong>-<strong>20</strong>33, Facsimile: (301) 662-5487<br />
www.stulz-ats.com<br />
Specifications are subject<br />
to change without notice.