Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc.

Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc. Engineering From 7 To 20 Tons Manual - Stulz Air Technologies Inc.

<strong>Engineering</strong><br />

<strong>Manual</strong><br />

<strong>From</strong> 7 to <strong>20</strong> <strong>To</strong>ns<br />

(60 Hz Data)<br />

Modular Floor Mounted<br />

Precision <strong>Air</strong> Conditioners<br />

Dual Compressor DX &<br />

Chilled Water Systems!


<strong>Stulz</strong> <strong>Air</strong> Technology Systems, <strong>Inc</strong>. (SATS)<br />

Founded in 1947, STULZ acquired <strong>Air</strong> Technology Systems<br />

(ATS) in March <strong>20</strong>01, naming the new company<br />

<strong>Stulz</strong> <strong>Air</strong> Technology Systems, <strong>Inc</strong>. (SATS). SATS is<br />

dedicated to providing innovative solutions for critical<br />

temperature and humidity control needs. SATS designs<br />

and manufactures specialized environmental<br />

control equipment for commercial, industrial and custom<br />

military applications. SATS serves a diverse marketplace<br />

- including telecommunications, information<br />

technology, medical, financial, educational, industrial<br />

process and government contracts - utilizing worldclass<br />

"island" manufacturing processes in a modern,<br />

150,000 ft 2 facility. The addition of SATS to the STULZ<br />

family of companies solidifies STULZ as a global leader<br />

in the precision air conditioning marketplace. SATS<br />

combines a global network of sales and service companies<br />

with an extensive factory engineering staff and<br />

highly flexible manufacturing resources dedicated to<br />

providing world-class quality, innovation and customer<br />

service.<br />

ISO-9001 Quality Registered<br />

SATS operates in an ISO-9001 registered quality control<br />

environment. Each employee of SATS is committed<br />

to satisfying our customer expectations with the<br />

highest level of consistent, measurable and continuous<br />

quality improvement.<br />

CyberAiR - Precision A/C's<br />

SATS CyberAiR air conditioners provide precision temperature<br />

and/or humidity control for computer rooms and<br />

other critical areas where 24/7 continuous operation is required.<br />

With an extensive installation base, SATS has<br />

earned a solid reputation as a quality supplier and leader in<br />

its field.<br />

ModulAiR modular vertical,<br />

floor mounted A/C's are created by<br />

combining quantity two CyberONE<br />

single compressor 3.5, 5, 8 or 10<br />

ton systems to create quantity one<br />

dual compressor 7, 10, 16 or <strong>20</strong><br />

ton system. The result is a large<br />

tonnage system in a very compact<br />

foot-print that solves difficult rigging<br />

applications. ModulAiR systems<br />

are designed for 100% front service access and are<br />

available with a wide range of options to handle a variety of<br />

precision cooling applications. Typical applications include:<br />

INDUSTRIES:<br />

• Telecommunications<br />

• Internet / Web Hosting<br />

• Financial / Banking<br />

• Insurance<br />

• Legal Services<br />

• <strong>Air</strong>lines / Mass Transit<br />

• Entertainment<br />

• Government<br />

• Colleges / Universities<br />

APPLICATIONS:<br />

• Computer / LAN Rooms<br />

• Telecommunications Rooms<br />

• Colocation Centers<br />

• ISP (Internet Service Providers)<br />

• ASP (Applications Service Providers)<br />

• Copier / Fax Rooms<br />

• ATM Bank Centers<br />

• Hospital Operating & Isolation Rooms<br />

• Laboratories<br />

1-1


Table of Contents<br />

SECTION - 1<br />

Introduction to SATS ........................................................... 1-1<br />

Table of Contents ............................................................... 1-2<br />

ModulAiR SYSTEMS:<br />

SECTION - 2<br />

Outstanding Advantages ..................................................... 2-1<br />

User Oriented Features & Options ..................................... 2-2<br />

Available Configurations .................................................. 2-3/4<br />

MODEL NOMENCLATURE:<br />

Model Nomenclature Chart ................................................. 2-4<br />

Model Nomenclature Specifications .................................... 2-5<br />

SECTION - 3<br />

GUIDE SPECIFICATIONS:<br />

Standard Features Index ..................................................... 3-1<br />

Standard Guide Specifications ......................................... 3-2/4<br />

SECTION - 6<br />

DIMENSIONAL / INSTALLATION DRAWINGS:<br />

Standard ModulAiR "MCS" Systems:<br />

7 to 10 <strong>To</strong>n, Up-Flow Systems ........................................... 6-1<br />

7 to 10 <strong>To</strong>n, Down-Flow Systems ...................................... 6-2<br />

16 to <strong>20</strong> <strong>To</strong>n, Up-Flow Systems ......................................... 6-3<br />

16 to <strong>20</strong> <strong>To</strong>n, Down-Flow Systems .................................... 6-4<br />

Remote <strong>Air</strong> Cooled Condensers/Condensing:<br />

Outdoor Remote Condensers ............................................ 6-5<br />

SATS PRODUCTS:<br />

BACK COVER<br />

CeilAiR - Supplemental Ceiling A/C's ................... Back-Cover<br />

FLAiR - Floor Console Precision A/C's ................ Back-Cover<br />

CyberAiR - Vertical Floor Precision A/C's<br />

CyberONE ....................................................... Back-Cover<br />

ModulAiR .......................................................... Back-Cover<br />

CyberTWO ....................................................... Back-Cover<br />

Optional Features Index...................................................... 3-5<br />

A-Tech-<strong>20</strong> Microprocessor Controls Specifications .......... 3-6/9<br />

Optional Features Guide Specifications ....................... 3-10/13<br />

SECTION - 4<br />

PERFORMANCE / CAPACITY SPECIFICATIONS:<br />

DX - <strong>Air</strong> Cooled Systems ................................................. 4-1/2<br />

DX - Water Cooled Systems ........................................... 4-3/4<br />

DX - Glycol Cooled Systems ........................................... 4-5/6<br />

Chilled Water Systems .................................................. 4-7/10<br />

SECTION - 5<br />

ELECTRICAL DATA: (FLA / MCA / MFS)<br />

DX - Compressorized Systems:<br />

<strong>Air</strong> Cooled, Split Systems ................................................... 5-1<br />

Water Cooled Systems ...................................................... 5-1<br />

Glycol Cooled Systems ...................................................... 5-1<br />

Remote <strong>Air</strong> Cooled Condensers:<br />

Indoor & Outdoor Condensers ............................................ 5-1<br />

Chilled Water <strong>Air</strong> Handling Systems:<br />

Chilled Water Systems ....................................................... 5-2<br />

1-2


2-1<br />

ModulAiR Advantages<br />

ModulAiR A/C’s are created by combining quantity<br />

two CyberONE single compressor 3.5, 5, 8 or 10 ton<br />

systems to create quantity one dual compressor 7, 10, 16<br />

or <strong>20</strong> ton system. The result is a large tonnage system in<br />

a very compact foot-print that solves difficult rigging<br />

applications.<br />

Small Elevator? Easy Rigging:<br />

Many service elevators are too small to accomodate the<br />

rigging of typical 1-piece computer room A/C cabinet. As<br />

a result, the historical solution to this rigging problem, has<br />

been to field “cut-down and disassemble”, and then field<br />

“reassemble” the air conditioner. This historical approach<br />

is not only time consuming and costly to the owner, it is<br />

also very risky to the long-term reliable operation of the<br />

air conditioner. ModulAiR units are designed to be the<br />

cost saving, reliable solution to these difficult rigging<br />

problems.<br />

ModulAiR Systems Offer Outstanding Benefits<br />

Flexibility<br />

A wide variety of types are available to meet your unique<br />

requirements.<br />

• DX - <strong>Air</strong> Cooled<br />

• DX - Water Cooled<br />

• DX - Glycol Cooled (w/ Remote Drycoolers &<br />

Pump Packages<br />

• Chilled Water <strong>Air</strong> Handling Units<br />

Versatility<br />

• Plenum Box Spot Cooling & Ducted systems<br />

• Self-Contained & Split systems<br />

• Modular design permits installation and rigging<br />

through small passage ways<br />

100% Front Service Access<br />

Designed for 100% Front Only Access, ModulAiR<br />

systems require minimal floor space and are easily<br />

tucked into a corner or between cabinets.<br />

Wide Size Range<br />

7 to <strong>20</strong> tons capacity in four incremental sizes.<br />

Non-Proprietary Parts<br />

ModulAiR systems incorporate non-proprietary components<br />

where possible. Most major HVAC, refrigeration<br />

and electrical distributors stock an exact model cross<br />

reference or an alternate to most factory provided<br />

components.<br />

Microprocessor Controls<br />

Precision temperature and/or humidity control with<br />

unrivaled, user-friendly A-Tech-<strong>20</strong> series controls, offer a<br />

wide range of functions and alarms.<br />

Complete Temperature & Humidity<br />

Control<br />

• Electrode Canister Steam Humidification<br />

• Dehumidification Mode with Electric Reheat<br />

Capacity Modulation Options<br />

• Hot Gas Bypass Systems<br />

• Multistage Electric Reheat/Heat<br />

• Modulating Chilled Water Valves (Standard)<br />

Code (UL / CSA) Conformance<br />

NRTL<br />

LISTED<br />

C<br />

Listing E11<strong>20</strong>43<br />

R<br />

+<br />

Complies With<br />

UL 1995<br />

CSA C22.2 No. 236<br />

Heating & Cooling Equipment<br />

=<br />

The compact, 100% front-access ModulAiR 16 & <strong>20</strong> ton<br />

systems have a total installed foot-print of 79.12” wide x<br />

34.0” deep. Comparing, the industry’s historical <strong>20</strong>-ton<br />

DX precision air conditioner has a foot-print of 100” wide x<br />

34” deep. For the owner, that means an additional 22 ft 2 of<br />

useable data center floor space!<br />

• BMS Connection<br />

• Multi-Unit Sequencing<br />

• Digital & Analog Output<br />

... and more!<br />

- NYC MEA Approved (MEA-163-88-E)<br />

- CSA Compliance / Chicago Code Approved


User Oriented Features & Options<br />

Scroll Compressors<br />

ModulAiR DX A/C's incorporate<br />

Scroll Compressor Technology.<br />

Scroll Compressors provide higher<br />

efficiency, higher reliability and<br />

lower sound power than other<br />

compressor technologies.<br />

24/7 Year Round Operation<br />

Option offerings available with ModulAiR A/C's allow for<br />

year-round, 24 hrs-a-day A/C operation in any environment<br />

in the world:<br />

Low Ambient Control (DX - <strong>Air</strong> Cooled)<br />

• -<strong>20</strong>°F Variable Fan Speed<br />

• -30°F Flooded Head Pressure<br />

Modular Motor Controllers<br />

ModulAiR systems incorporate<br />

modular motor controllers with<br />

motor circuit breakers in lieu of<br />

inconvenient replaceable fuses,<br />

eliminating the need for ANY<br />

motor fusing.<br />

Quiet Operation<br />

Low sound power Scroll compressors coupled with low<br />

RPM blowers, acoustically lined cabinets and low velocity<br />

grilles provide the optimum in quiet operation.<br />

Warranty<br />

- 1 Year Parts Standard<br />

- Optional 5 Year Compressor<br />

100% Front Access<br />

(Saves a Minimum 18 ft 2 Floor Space)<br />

Selected Standard Features:<br />

• Main Power Non-Fused Disconnect Switch<br />

• Modular Motor Controllers (w/ motor circuit breakers)<br />

• Acoustical / Thermal Insulation<br />

• Aluminum Finned / Copper Tube Coils<br />

• Thermal Expansion Valve<br />

• Refrigerant Sight Glass<br />

• Filter / Drier Strainer<br />

• Liquid Refrigerant Reclaim Valves<br />

• Non-Corroding Stainless Steel or Polymer Drain Pan<br />

• High / Low Pressure Switches<br />

Other Available Options:<br />

ModulAiR<br />

(Model MCS-240-DAR-D Shown)<br />

- 2 & 3-way Grilled Plenum Boxes<br />

- Floor Stands (with & without turning vanes, seismic)<br />

- Condensate Pumps<br />

- Firestats<br />

- Smoke Detectors<br />

- Water Leak Detectors<br />

- High Static Belt-Drive Blowers<br />

- Special High Efficiency Filtration<br />

(2" & 4" Filters up-to 60% Dust Spot)<br />

- High Pressure DX - Water/Glycol Cooled<br />

Condenser Regulating Valves<br />

- Drycoolers & Pump Packages<br />

- Many more options available (see page 3-5)!<br />

2-2


Application Dependent Configuration Choices<br />

ModulAiR<br />

Configurations<br />

+<br />

=<br />

AIR COOLED SYSTEMS<br />

SPLIT AIR COOLED<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

WATER COOLED SYSTEMS<br />

SELF-CONTAINED<br />

WATER COOLED SYSTEMS<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

HES-( )-DL()A<br />

(Remote Outdoor<br />

Propeller Condenser)<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Remote Water Source<br />

(supplied by others)<br />

MCS-084 thru 240-DAR-( )<br />

(ModulAiR, Split Evaporator)<br />

(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />

MCS-084 thru 240-DW-( )<br />

(ModulAiR, Self-Contained)<br />

(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />

GLYCOL COOLED SYSTEMS<br />

SELF-CONTAINED<br />

GLYCOL COOLED SYSTEMS<br />

CHILLED WATER SYSTEMS<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

HES-()-LGA / GPS-( )<br />

(Outdoor Propeller Drycooler & Pump Package)<br />

Remote Liquid Chiller<br />

(supplied by others)<br />

MCS-084 thru 240-DW-( )<br />

(ModulAiR, Self-Contained)<br />

(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />

MCS-084 thru 240-C-( )<br />

(ModulAiR, Self-Contained, <strong>Air</strong> Handler)<br />

(Up-Flow or Down-Flow <strong>Air</strong> Pattern)<br />

2-3


Flexible <strong>Air</strong> Pattern Configuration Choices<br />

Down-Flow Systems:<br />

<strong>To</strong>p "Free" Return with:<br />

<strong>To</strong>p "Ducted" Return with:<br />

1 2<br />

Bottom Discharge<br />

Into Raised Floor<br />

Up-Flow Systems:<br />

<strong>To</strong>p Discharge Through 2 or 3-<br />

Way Grilled Plenum Box with:<br />

Floor Stand<br />

(Optional)<br />

Bottom Discharge<br />

Into Raised Floor<br />

<strong>To</strong>p "Ducted" Discharge with:<br />

3 4<br />

Front "Free" Return<br />

Front "Free" Return<br />

Model Nomenclature<br />

MCS-240-DG-U<br />

D = Down-Flow <strong>Air</strong> Pattern<br />

U = Up-Flow <strong>Air</strong> Pattern<br />

MCS= Modular Cyber System<br />

HES = Heat Exchanger System<br />

GPS = Glycol Pump System<br />

Nominal Capacity in 1,000's of BTU/H<br />

AR = Remote (Split) <strong>Air</strong> Cooled<br />

C = Chilled Water System<br />

CAA = Indoor Centrifugal Condenser<br />

D( ) = Dual (Two) Circuit or Pump System<br />

G = Glycol Cooled<br />

LSA = Outdoor Propeller Condenser for -<strong>20</strong>°F<br />

LFA = Outdoor Propeller Condenser for -30°F<br />

LGA = Outdoor Propeller Glycol Drycooler<br />

S = Single Pump<br />

W = Water Cooled<br />

2-4


Model Nomenclature Specifications<br />

Nomenclature - ModulAiR System Model Specifications<br />

"ModulAiR"<br />

Model Nomenclature<br />

Guide Specifications<br />

DX - EVAPORATOR SECTIONS<br />

<strong>Air</strong> Cooled Remote Evaporator<br />

(Models MCS-( )-DAR)<br />

The system shall be a remote (split)<br />

air cooled, floor mounted precision air<br />

conditioner evaporator. The evaporator<br />

section shall house, as a minimum,<br />

the evaporator coil, expansion valve,<br />

compressor, evaporator blower/motor<br />

and associated electrical and refrigeration<br />

components.<br />

The MCS-( )-DAR evaporator section<br />

shall be located at some distance from<br />

its corresponding SATS model HES-(<br />

)-DHCA/DVCA indoor or HES-( )-<br />

DL()A outdoor air cooled condenser.<br />

The evaporator system shall require<br />

only single point main power supply<br />

connection; and the system shall ship<br />

from the SATS factory with a dry<br />

nitrogen holding charge ready for field<br />

refrigerant (R-22) charging.<br />

DX - AIR COOLED CONDENSERS<br />

Remote Indoor Centrifugal<br />

(Models HES-( )-DHCA / DVCA)<br />

The system shall be a remote indoor<br />

ceiling mounted air cooled condenser<br />

with centrifugal blower. The condenser<br />

cabinet shall house the<br />

condenser coil, blower and blower<br />

motor, receivers (if applicable) and<br />

condenser motor control / enabling<br />

box. The compressor(s) shall be<br />

located with the MCS-( )-DAR<br />

evaporator section.<br />

The condenser shall be sized to<br />

provide the total heat of rejection of<br />

the system at a 95°F DB ambient<br />

temperature for the corresponding<br />

ModulAiR model MCS-( )-DAR<br />

evaporator.<br />

Remote Outdoor Propeller<br />

(Models HES-( )-DL()A)<br />

The system shall be a remote outdoor<br />

air cooled condenser with directdriven<br />

propeller fan(s). The condenser<br />

cabinet shall house the<br />

condenser coil, fan(s) and fan<br />

motor(s) and Nema 3R condenser<br />

motor control / enabling box. The<br />

compressor(s) shall be located with<br />

the MCS-( )-DAR evaporator section.<br />

The condenser shall be sized to<br />

provide the total heat of rejection of<br />

the system at a 95°F DB ambient<br />

temperature for the corresponding<br />

ModulAiR model MCS-( )-DAR<br />

evaporator.<br />

Note: The outdoor propeller condensers<br />

are model designated as follows:<br />

HES-( )-DLSA:<br />

Low Ambient Head Pressure Control down<br />

to a minimum ambient temperature of -<br />

<strong>20</strong>°F via Variable Fan Speed Head<br />

Pressure Control.<br />

HES-( )-DLFA:<br />

Low Ambient Head Pressure Control down<br />

to a minimum ambient temperature of -<br />

30°F via Flooded Head Pressure<br />

Control.<br />

DX - WATER COOLED SYSTEMS<br />

Integral Self-Contained<br />

(Models MCS-( )-DW)<br />

The system shall be a self-contained,<br />

floor mounted precision air conditioner<br />

to include integral water cooled,<br />

condenser with factory installed head<br />

pressure water regulating control<br />

valve(s). Condenser (source) water<br />

shall be provided by a cooling tower or<br />

some other remote water source.<br />

The system shall require only single<br />

point supply power connection and<br />

shall ship from the SATS factory with<br />

a full operating refrigerant (R-22)<br />

charge.<br />

Water Regulating Valves:<br />

Head pressure shall be automatically<br />

controlled by a factory installed 2-way<br />

water regulating valve rated for 150<br />

psig w.w.p.<br />

(Note: 3-way and high pressure valves<br />

are optionally available, page 3-11.)<br />

DX - GLYCOL COOLED SYSTEMS<br />

Integral Self-Contained<br />

(Models MCS-( )-DG)<br />

The system shall be a self-contained,<br />

floor mounted precision air conditioner<br />

to include integral glycol cooled,<br />

condenser with factory installed head<br />

pressure glycol regulating control<br />

valve(s). Condenser (source) glycol<br />

solution shall be provided via a SATS<br />

model GPS-( )-( ) / HES-( )-LGA<br />

remote glycol pump package and<br />

drycooler system.<br />

The system shall require only single<br />

point supply power connection and<br />

shall ship from the SATS factory with<br />

a full operating refrigerant (R-22)<br />

charge.<br />

Glycol Regulating Valves:<br />

Head pressure shall be automatically<br />

controlled by a factory installed 2-way<br />

glycol regulating valve rated for 150<br />

psig w.w.p.<br />

(Note: 3-way and high pressure valves<br />

are optionally available, page 3-11.)<br />

CHILLED WATER AIR HANDLERS<br />

CHILLED WATER SYSTEM<br />

(Models MCS-( )-C)<br />

The system shall be a floor mounted<br />

chilled water precision air conditioner<br />

to include chilled water cooling coil,<br />

evaporator blower and motor and<br />

chilled water control valve. Chilled<br />

water shall be provided by a remote<br />

liquid chiller system.<br />

Chilled Water Control Valve:<br />

Cooling capacity shall be controlled<br />

with a factory installed 3-way modulating<br />

(0-10 Vdc) control valve rated for<br />

400 psig.<br />

(Note: 2-way modulating valves are<br />

optionally available, page 3-11.)<br />

2-5


Selected Standard Features - "MCS" Series<br />

"MCS" Model MCS-084/1<strong>20</strong>-( ) MCS-192/240-( )<br />

SELECTED STANDARD FEATURES:<br />

TEMPERATURE CONTROL<br />

• 2-Stage Cooling Mode Standard Standard<br />

• 1-Stage Electric Reheating / Heating Standard Standard<br />

• 2-Stage Electric Reheating / Heating Optional Optional<br />

• Cooling &/or Heating Only (No Humidity Control) Optional Optional<br />

HUMIDITY CONTROL<br />

• Electrode Canister Steam Humidifier Standard Standard<br />

• Dehumidification Mode with 1-Stage Electric Reheat Standard Standard<br />

CONTROLS<br />

• A-Tech-<strong>20</strong> Advanced Micropressor w/ Alarms Standard Standard<br />

CABINET<br />

• Powder Coat Painted Galvanneal Steel Standard Standard<br />

• Insulated Stainless Steel or Polymer Condensate Drain Pan Standard Standard<br />

• 2 lb Density Thermal & Sound Insulation Standard Standard<br />

• Floor Stand (Adjustable, turning vanes optional) Optional Optional<br />

FILTERS / PLENUMS<br />

• 2", 30% Dust Spot Eff. Pleated Filters Standard N/A<br />

• 4", 30% Dust Spot Eff. Pleated Filters Optional Standard<br />

• 2 or 3-way Plenum Box (Up-Flow Units) Optional Optional<br />

DX-REFRIGERATION CIRCUIT<br />

• CFC-Free R22 Refrigerant Standard Standard<br />

• Scroll Compressors w/ Rotolock Service Valves Standard Standard<br />

• High Efficiency, Aluminum Fin / Copper Tube Coils Standard Standard<br />

• Thermal Expansion Valves Standard Standard<br />

• Refrigerant Sight Glasses & Filter/Drier Strainers Standard Standard<br />

• Refrigerant Service Valves Standard Standard<br />

BLOWERS / MOTORS<br />

• Belt-Drive Evaporator Blower / Motor Standard Standard<br />

ELECTRICAL<br />

• 3-Phase Power Supply - - - See Electrical Tables Section 5 - - -<br />

• Multi-Voltage Control Transformer (24V Class 2) Standard Standard<br />

• Modular Motor Controllers with Integral Circuit Breakers Standard Standard<br />

SAFETY FEATURES<br />

• A-Tech-<strong>20</strong> Audible/Visual Local & Remote Alarms Standard Standard<br />

• Main Power Non-Fused Disconnect, unit mounted Standard Standard<br />

• High / Low Refrigerant Pressure Switches (DX units) Standard Standard<br />

• Motor Overload Protection Standard Standard<br />

SPECIFIC MODEL STANDARD FEATURES:<br />

AIR COOLED<br />

• Low Ambient Head Pressure Control - - - - Two types -<strong>20</strong>°F or -30°F - - - -<br />

• Remote <strong>Air</strong> Cooled Condenser Standard Standard<br />

WATER / GLYCOL COOLED<br />

• 2-way, 150 psig Water/Glycol Regulating Valves Standard Standard<br />

• High Pressure &/or 3-way Valves Optional Optional<br />

• Coaxial, Tube-in-Tube Heat Exchanger Standard N/A<br />

• Stainless Steel Brazed Plate Heat Exchanger N/A Standard<br />

ALL SPLIT DX SYSTEMS<br />

• Liquid Line Solenoid Valve to Prevent Liquid Slugging Standard Standard<br />

CHILLED WATER SYSTEMS<br />

• 3-way, 300 psig Modulating (0-10 Vdc) Valve Standard N/A<br />

• 3-way, 400 psig Modulating (0-10 Vdc) Valve Optional Standard<br />

• 2-way, Modulating (0-10 Vdc) Valve Optional Optional<br />

Guide Specifications - Standard Features "Quick-Reference" Table<br />

CODE CONFORMANCE<br />

• NRTL Conformance Compliance to UL 1995 Standard Standard Standard<br />

• CSA / NYC MEA-163-88-E / Chicago Code Approval Standard Standard<br />

3-1


Guide Specifications - Standard Equipment<br />

Guide Specifications - Standard Equipment<br />

QUALITY ASSURANCE<br />

(ISO-9001 Registered)<br />

SATS operates in an ISO-9001<br />

registered quality control environment.<br />

Each SATS employee is<br />

committed to satisfying his or her<br />

customer expectations with the<br />

highest level of consistent, measurable<br />

and continuous quality<br />

improvement.<br />

GENERAL GUIDE<br />

SPECIFICATION<br />

General Description<br />

+<br />

=<br />

The system shall be a floor mounted<br />

air conditioner designed and built to<br />

provide precision temperature and<br />

humidity control. The system shall<br />

be complete and factory run-tested<br />

before shipment. The system shall<br />

be MET Laboratory (an NRTL) listed<br />

and labeled in compliance with UL<br />

1995 and CSA C22.2 No. 236. The<br />

system shall be MEA NYC approved<br />

(MEA-163-88-E).<br />

The system shall be manufactured<br />

by <strong>Stulz</strong> <strong>Air</strong> Technology Systems,<br />

<strong>Inc</strong>. in Frederick, Maryland, USA.<br />

100% Front Access<br />

The air conditioner shall require front<br />

only access for all routinely<br />

maintenanced components. No<br />

allowance for side service access<br />

shall be required, however, removable<br />

side access shall be provided<br />

for additional access.<br />

Cabinet Construction<br />

The cabinet and access panels shall<br />

be fabricated from heavy gauge<br />

galvannealed steel and powder-coat<br />

paint processed for decor matching<br />

and corrosion protection. The<br />

panels shall be lined with 2 lb/ft 2 high<br />

density sound and thermal insulation<br />

and sealed with self-extinguishing<br />

gasketing conforming to NFPA 90A<br />

and 90B.<br />

Electrical System<br />

Modular Motor Controllers<br />

The system shall incorporate modular<br />

motor controllers utilizing motor<br />

start protectors and circuit breakers<br />

eliminating the need for fusing, as<br />

well as providing:<br />

• Motor branch circuit short circuit<br />

protection<br />

• Motor load switching controllers<br />

(contactors)<br />

• Motor overload protection<br />

The system shall incorporate overcurrent<br />

and overload protection in<br />

accordance with UL 1995 requirements.<br />

Each blower motor, compressor,<br />

electric heater stage and<br />

humidifier (if applicable) shall be<br />

provided with a factory mounted and<br />

wired starter / contactor.<br />

The control circuit shall be a 24 VAC<br />

Class 2 low voltage circuit including<br />

a circuit breaker for protection. Low<br />

voltage, high voltage and grounding<br />

wires shall be color coded and shall<br />

be individually numbered at each<br />

end for ease of service tracing. All<br />

wiring shall be in accordance with<br />

the National Electric Code (NEC).<br />

Main Power - Electric<br />

Non-Fused Service Switch<br />

As a factory standard, a unit<br />

mounted main power service switch<br />

shall be provided. The service<br />

switch shall be a dust-proof, nonfused<br />

type with lockable handle.<br />

Evaporator Coils<br />

Evaporator systems shall be configured<br />

for a draw-thru air pattern to<br />

provide uniform air distribution over<br />

the evaporator coil face. The coils<br />

shall be seamless drawn copper<br />

tubes, mechanically bonded to<br />

tempered aluminum fins with fin<br />

pattern designed for maximum heat<br />

transfer. Coil end plates shall be hot<br />

dipped galvanized.<br />

The evaporator coil shall be mounted<br />

in an insulated polymeric or<br />

stainless steel condensate drain pan,<br />

depending on unit model size.<br />

DX-Refrigeration System<br />

Thermal Expansion<br />

Valves<br />

Filter Drier/<br />

Strainers<br />

Sight Glasses<br />

All refrigeration piping shall be<br />

refrigerant grade tubing. Each<br />

refrigerant circuit shall include, as a<br />

minimum, refrigerant drier/strainer,<br />

sight glass with moisture detector,<br />

3-2


Guide Specifications - Standard Equipment<br />

thermal expansion valve with rapid<br />

bleed port feature and external<br />

equalizer, evaporator coil, compressor,<br />

high pressure switch with<br />

manual reset and a low pressure<br />

switch with automatic reset.<br />

Split / Remote systems shall have a<br />

liquid line solenoid for refrigerant<br />

isolation to prevent liquid slugging. All<br />

high pressure joints shall be brazed,<br />

and the entire system shall be<br />

pressure tested at the factory with<br />

dry nitrogen, evacuated to at least 50<br />

microns and fully charged with<br />

refrigerant.<br />

Note: All split / remote DX systems<br />

ship with a dry nitrogen holding charge.<br />

All self-contained DX systems ship with a<br />

full refrigerant (R-22) operating charge.<br />

Scroll Compressors<br />

Each compressor shall be a high<br />

efficiency, high reliability and low<br />

sound Scroll Compressor.<br />

The compressor shall be complete<br />

with charging and service schraeder<br />

ports, internal vibration isolation,<br />

internal thermal overloads, internal<br />

pressure relief valve, internal discharge<br />

gas vibration eliminator and<br />

external vibration mounting isolation.<br />

Chilled Water System<br />

(Models MCS-( )-C)<br />

Cooling Coil:<br />

The chilled water coil shall be<br />

constructed of seamless drawn<br />

copper tubes, mechanically bonded<br />

to tempered aluminum fins for<br />

maximum heat transfer. Coil end<br />

plates shall be hot dipped galvanized.<br />

The cooling coil shall be mounted in<br />

an insulated stainless steel condensate<br />

drain pan.<br />

CW Control Valve:<br />

Cooling capacity shall be controlled<br />

by a factory installed 3-way, modulating<br />

(0-10 Vdc) control valve rated<br />

for a maximum 300 psig w.w.p. (7 to<br />

10 <strong>To</strong>n) and 400 psig w.w.p. (16 to<br />

<strong>20</strong> <strong>To</strong>n).<br />

Note: 2-way valves are optionally<br />

available, page 3-11.<br />

Blowers / Motors<br />

Belt Driven Systems<br />

The blower(s) shall be belt driven<br />

with double width, double inlet<br />

housing and forward curved blades<br />

and permanently lubricated ball<br />

bearings sized for an average<br />

100,000 hours of service life. The<br />

blowers shall be dynamically and<br />

statically balanced to minimize<br />

vibration and operate in the Class I<br />

range.<br />

The blower(s) shall have an adjustable<br />

base for belt tensioning and a<br />

locking system to prevent the motors<br />

from moving. The motors’ drive<br />

sheaves shall have an adjustable<br />

pitch to change the speed of the<br />

blowers. The motor(s) shall be 1725<br />

RPM and shall have overload protection<br />

and a minimum NEMA service<br />

factor of 1.15.<br />

Temp & Humid Control<br />

The standard ModulAiR floor A/C<br />

includes the A-Tech-<strong>20</strong> Advanced<br />

Microprocessor Controller, Canister<br />

Steam Humidifier and Dehumidification<br />

Mode with Electric Reheat/Heat<br />

providing precision temperature and<br />

humidity control.<br />

A-TECH-<strong>20</strong><br />

(Microprocessor Controller w/ Alarms)<br />

Control shall be provided by SATS'<br />

Advanced A-Tech-<strong>20</strong> Microprocessor<br />

temperature and humidity controller with<br />

alarms. The user friendly A-Tech-<strong>20</strong><br />

shall provide both local & remote alarm<br />

indication, if applicable, for:<br />

• High Temperature • Loss of <strong>Air</strong> Flow<br />

• Low Temperature • Loss of Power<br />

• High Humidity • Dirty Filter<br />

• Low Humidity • Leak Detection<br />

• High Head Press • Smoke Detection<br />

• Low Suction Press • Firestat<br />

Electrode Canister Steam<br />

Humidifier<br />

The humidifier shall<br />

be an electrode<br />

steam canister type.<br />

<strong>Manual</strong>ly adjustable<br />

ON/OFF steam<br />

output shall be<br />

standard.<br />

Dehumidification Mode<br />

A Dehumidification<br />

mode with<br />

Electric Reheat/<br />

Heat shall be<br />

incorporated as<br />

standard.<br />

(Note: Please refer to pages 3-5 thru 3-10<br />

of this brochure for more specification<br />

details on all ModulAiR Temperature and<br />

Humidity Control Options.)<br />

Guide Specifications - Standard Equipment<br />

3-3


Evaporator<br />

<strong>Air</strong> Outlet<br />

Guide Specifications - Standard Equipment<br />

Guide Specifications - Standard Equipment<br />

Evaporator <strong>Air</strong> Patterns<br />

DOWN-FLOW:<br />

(MCS-( )-( )-D)<br />

The air conditioner shall be configured<br />

for a down-flow air pattern with<br />

free evaporator return air to the top<br />

and conditioned supply air discharge<br />

through bottom of the A/C into the<br />

raised floor. (Floor Stands are<br />

optionally available, page 3-11.)<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Down-Flow<br />

<strong>Air</strong> Pattern<br />

(A top 1" flanged return air duct connection<br />

is optionally available.)<br />

UP-FLOW:<br />

(MCS-( )-( )-U)<br />

The air conditioner shall be configured<br />

for an up-flow air pattern with<br />

free evaporator return air through<br />

front filtered grille and conditioned<br />

supply air through the top of the unit.<br />

Up-Flow<br />

<strong>Air</strong> Pattern<br />

DX - Heat Rejection<br />

AIR COOLED<br />

(Note: Please refer to page 3-11, for<br />

specification details of ModulAiR air<br />

cooled condenser "Low Ambient Control"<br />

options: -<strong>20</strong>°F & -30°F)<br />

Outdoor - Remote Condensers<br />

(Models HES-( )-DL()A Evaporator)<br />

The system shall be a remote<br />

outdoor air cooled condenser with<br />

direct-driven propeller fan(s). The<br />

condenser shall be sized to provide<br />

the total heat of rejection of the<br />

system at a 95°F DB ambient<br />

temperature for the corresponding<br />

model MCS-( )-DAR DX evaporator.<br />

Indoor - Remote Condensers<br />

(Models HES-( )-DHCA / DVCA)<br />

The system shall be a remote indoor<br />

ceiling mounted air cooled condenser<br />

with centrifugal blower. The<br />

condenser shall be sized to provide<br />

the total heat of rejection of the<br />

system at a 95°F DB ambient<br />

temperature for the corresponding<br />

model MCS-( )-DAR DX evaporator.<br />

SS Brazed-Plated:<br />

(Models MCS-192/240-DW/DG)<br />

Each evaporator refrigerant circuit<br />

shall be provided with a factory<br />

installed single pass, counterflow<br />

configured brazed plate heat<br />

exchanger, with integral subcooler,<br />

constructed of type 316 stainless<br />

steel; designed and tested for a 450<br />

psig. w.w.p.<br />

2-Way, 150 psig Regulating Valve<br />

(Standard on all MCS-( )-DW/G)<br />

Each refrigerant circuit's head<br />

pressure shall be controlled by a<br />

factory installed 2-way water / glycol<br />

regulating valve rated for 150 psig.<br />

w.w.p.<br />

(Note: 3-way and high pressure water/<br />

glycol regulating valves are optionally<br />

available, page 3-11.)<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

WATER / GLYCOL COOLED<br />

(A top 1" flanged duct connection shall be<br />

provided as a standard. 2 & 3-way top<br />

discharge plenum boxes are optionally<br />

available, page 3-12.)<br />

<strong>Air</strong> Filtration<br />

The A/C shall have slide out, ___"<br />

deep, class 2 (per U.L. Standard<br />

900) filters. The filters shall be<br />

easily accessed through a front<br />

access door. The filters shall have<br />

an efficiency rating of at least, 30%<br />

dust-spot as measured by ASHRAE<br />

Standard 52-76 test method.<br />

Water/Glycol Cooled<br />

Condensers<br />

Coaxial Tube-In-Tube:<br />

(Models MCS-084/1<strong>20</strong>-DW/DG)<br />

Each evaporator refrigerant circuit<br />

shall be provided with a factory<br />

installed single pass, counterflow<br />

configured, tube-in-tube coaxial<br />

condenser; designed and tested for<br />

a 450 psig. w.w.p.<br />

3-4


Optional Features - Guide Specifications<br />

Optional Features Index<br />

OPTION ................................................... page<br />

Microprocessor Controls<br />

• A-Tech-<strong>20</strong> Microprocessor (standard) ............... 3-6/9<br />

• CyberLAN Networking Options ......................... 3-8/9<br />

- Multi-Unit "N+1" Sequencing.............................. 3-8/9<br />

- Multi-Unit Capacity Assist-Mode ........................... 3-9<br />

- Remote BMS Communications ............................. 3-9<br />

Humidity Control Options<br />

• Steam Humidifier (standard) ................................ 3-10<br />

• Dehumidification Cycle<br />

- Electric Reheat / Heat (standard) ....................... 3-10<br />

High Static Pressure Blowers<br />

• High Static Belt-Drive Blower Upgrade ................... 3-10<br />

(Up to 2.0" ext. static pressure)<br />

High Efficiency Filtration (IAQ)<br />

• IAQ High Efficiency Filters .................................... 3-10<br />

Head Pressure Control Options<br />

DX - Capacity Modulation<br />

• Snap-Acting, Hot Gas Bypass ............................ 3-11<br />

Chilled Water Modulating Control Valves<br />

• 3-way, 300 & 400 psig, 0-10 Vdc (standard) ....... 3-11<br />

• 2-way, 300 & 400 psig, 0-10 Vdc ........................ 3-11<br />

ACCESSORIES<br />

• Floor Stands<br />

- Turning Vanes .................................................... 3-11<br />

- Seismic Floor Stand ........................................... 3-12<br />

• 2 or 3-Way Plenum Discharge Box .................... 3-12<br />

• Condensate Pump ............................................... 3-12<br />

• Smoke Detector ................................................... 3-12<br />

• Firestat ................................................................. 3-12<br />

• Remote Water Detector:<br />

- Qty. One, Spot Type ........................................... 3-12<br />

- Qty. Two, Spot Type ............................................ 3-12<br />

- 40 Ft. - Strip/Cable Type..................................... 3-12<br />

- Water Detector Auxiliary Contact ........................ 3-12<br />

• Acoustical Compressor Sound Jackets ........ 3-12/13<br />

Optional Features - Index<br />

<strong>Air</strong> Cooled - Low Ambient Control<br />

• -<strong>20</strong>°F Ambient .................................................... 3-11<br />

• -30°F Ambient .................................................... 3-11<br />

Water/Glycol Cooled - Regulating Valves<br />

• 2-way, 150 psig (standard) ................................. 3-11<br />

• 2-way, 350 psig .................................................. 3-11<br />

• 2-way, 450 psig .................................................. 3-11<br />

• 3-way, 150 psig .................................................. 3-11<br />

• 3-way, 350 psig .................................................. 3-11<br />

• 3-way, 450 psig .................................................. 3-11<br />

Glycol Pump Packages & Drycoolers<br />

• Glycol Pump Packages:<br />

- Single Pump Packages ...................................... 3-13<br />

- Dual Pump Packages ......................................... 3-13<br />

• Remote Drycoolers.............................................. 3-13<br />

3-5


Microprocessor Controls - A-Tech-<strong>20</strong><br />

Guide Specifications - Microprocessor Control Options<br />

A-Tech-<strong>20</strong> Series Controls:<br />

Advanced Microprocessor<br />

Temperature & Humidity<br />

Controller with Alarms<br />

The ModulAiR floor mounted air<br />

conditioner shall be provided with<br />

SATS' A-Tech-<strong>20</strong> Advanced Microprocessor<br />

based Temperature and<br />

Humidity controller with Alarms. The<br />

controller shall incorporate a "userfriendly"<br />

operating environment, to<br />

allow easy system setup and operation.<br />

DISPLAY / KEYPAD:<br />

Featuring an easy to read, 4 x <strong>20</strong><br />

character liquid-crystal alphanumerical<br />

display, the attractive unit<br />

mounted (standard) or remote<br />

mounted (optional) keypad/display,<br />

allows the operator to visually monitor<br />

and customize unit functions and<br />

settings. Self-explanatory, keypad<br />

nomenclature makes for easy<br />

location of system programming<br />

features.<br />

Performing simple functions such<br />

as adjusting the Temperature or<br />

Humidity set point are made obvious:<br />

Press TEMP SETPT or HUMID<br />

SETPT, ARROW UP or DOWN to<br />

adjust & press ENTER to accept.<br />

FIELD CONFIGURABLE:<br />

The A-Tech-<strong>20</strong> controller is field<br />

program configurable and capable of<br />

matching the unique needs of any<br />

data center, telecommunication or<br />

other critical area.<br />

Display/Sensor Options:<br />

Display Location Options:<br />

As a standard, the A-Tech-<strong>20</strong><br />

controller display is factory unit<br />

mounted to the front of the ModulAiR<br />

unit.<br />

Optionally, the A-Tech-<strong>20</strong> keypad/<br />

display can be shipped loose for<br />

remote wall mounting.<br />

Remote Display Cable Options:<br />

• 30 ft. cable length (standard option)<br />

• 75 ft. cable length<br />

• 150 ft. cable length<br />

Sensor Location Options:<br />

As a standard, the A-Tech-<strong>20</strong><br />

temperature and humidity sensor is<br />

factory unit mounted in the return air<br />

stream of the ModulAiR unit, after<br />

the filter(s).<br />

Optionally, the A-Tech-<strong>20</strong> temperature<br />

and humidity sensor can be<br />

shipped loose for remote wall<br />

mounting.<br />

Remote Sensor Cable Options:<br />

• 75 ft. cable length (standard option)<br />

• 150 ft. cable length<br />

Dual-Sensor Selection: (Optional)<br />

Through a menu selection option<br />

screen within the A-Tech-<strong>20</strong> controller,<br />

an automatic or a manual selection is<br />

available for local T/H sensor control or<br />

remote T/H sensor control. Typically,<br />

the local (standard) T/H sensor is<br />

factory unit mounted within the return<br />

air stream of the ModulAiR unit, while<br />

the remote (optional) T/H sensor is<br />

remote wall (or "sensor-tree")<br />

mounted.<br />

During automatic dual-sensor<br />

selection mode, A-Tech-<strong>20</strong> control<br />

logic shall compare T/H sensor input<br />

readings. The sensor reading that is<br />

the greater from setpoint will be used<br />

to control the unit's temperature and/<br />

or humidity output control devices.<br />

During manual dual-sensor selection<br />

mode, the user can manually select<br />

which sensor controls the unit.<br />

Remote Sensor Cable Options:<br />

The cable shall be type NEC CMP 2<br />

shielded twisted paired and comply<br />

with NEC Article 600 (UL: 150°C,<br />

300V) and c(UL)PCC FT 6 .<br />

• 75 ft. cable length (standard option)<br />

• 150 ft. cable length<br />

SYSTEM SETUP & ADJUSTMENTS:<br />

The A-Tech-<strong>20</strong> is completely factory<br />

preprogrammed, and therefore, most<br />

applications will require no field setup.<br />

However, the “default” set points and<br />

their ranges are easily adjusted from<br />

A-Tech-<strong>20</strong> kepad/display.<br />

The system is supplied with the<br />

following factory preprogrammed<br />

and field adjustable default settings:<br />

Temp/Humid Control:<br />

Temp Set Point<br />

72°F DB<br />

Humidity Set Point<br />

50% RH<br />

Heat/Cool Dead-Band 2°F DB<br />

Humid/Dehumid Dead-Band 5% RH<br />

Inter-stage Differential 1°F DB<br />

Alarms:<br />

High Temp Alarm<br />

Low Temp Alarm<br />

High Humid Alarm<br />

Low Humid Alarm<br />

Compressor Short Cycle:<br />

Cold-Start Time Delay<br />

Minimum ON Time<br />

Minimum OFF Time<br />

80°F DB<br />

60°F DB<br />

70% RH<br />

30% RH<br />

3 min<br />

2 min<br />

4 min<br />

3-6


Microprocessor Controls - A-Tech-<strong>20</strong><br />

UNIT STATUS DISPLAY:<br />

The A-Tech-<strong>20</strong> displays current unit<br />

functions and room status:<br />

• Current Dry Bulb Temp Set Point<br />

• Current Relative Humidity Set Point<br />

Current Unit Status: (if applicable)<br />

• System ON/OFF • Free Cooling<br />

• Cooling<br />

• AWS Cooling<br />

• Heating<br />

• Compr. Lock-Out<br />

• Humidifying • Capacity Assist<br />

• Dehumidifying • Standby Mode<br />

• Reheating • <strong>Manual</strong> Mode<br />

• Actual Room DB Temperature<br />

• Actual Room Relative Humidity<br />

Run Times<br />

The historical run-time in hours of<br />

the following major components is<br />

available directly from the A-Tech-<strong>20</strong><br />

keypad/display: (if applicable)<br />

• Evaporator Blower Motor<br />

• Compressor<br />

• Humidifier<br />

• Chilled Water Valve<br />

• Free-Cooling Valve<br />

• Alternate Water Source Valve<br />

ALARM CONDITIONS:<br />

Alarm conditions activate an audible<br />

and visual indicator, as well as, close<br />

a summary alarm dry contact<br />

connection. An alarm is acknowledged<br />

through the Alarm and Alarm<br />

Mute buttons located on the keypad<br />

display.<br />

The A-Tech-<strong>20</strong> alerts to the following<br />

alarm conditions (if applicable):<br />

• High Temperature • Dirty Filter<br />

• Low Temperature • Smoke Detection<br />

• High Humidity • Firestat<br />

• Low Humidity • Leak Detection<br />

• High Head Press • GC Pump Failure<br />

• Low Suction Press • Sensor Failure<br />

• Loss of <strong>Air</strong> Flow • Comm. Failure<br />

• Loss of Power<br />

The operator may select which<br />

alarms are active or inactive.<br />

Summary Alarm Contacts:<br />

• A user-configurable summary<br />

alarm dry-contact (n/o) connection<br />

is available for remote<br />

annunciation of an alarm condition.<br />

• An additional user-configurable<br />

custom alarm dry-contact is also<br />

available on most system configurations.<br />

Alarm History:<br />

The A-Tech-<strong>20</strong> controller provides<br />

users with a recorded history of the<br />

last 25 alarms, including the time and<br />

date of the alarm.<br />

CONTROL INPUTS / OUTPUTS:<br />

The A-Tech-<strong>20</strong> is capable of both<br />

digital (on/off) and analog (proportional<br />

integral, PI) input and output<br />

device control. Prior to shipment,<br />

each ModulAiR unit's A-Tech-<strong>20</strong> is<br />

factory program configured to match<br />

the unit's system operational requirements:<br />

Digital (On/Off) Outputs:<br />

• 2 (two) Cool (if applicable)<br />

• 2 (two) Reheat/Heat<br />

• 1 (one) Humidification<br />

Analog (0-10 Vdc) Outputs:<br />

• 1 (one) Cool<br />

• 1 (one) Reheating/Heat (opt.)<br />

• 1 (one) Humidification (opt.)<br />

Temperature Anticipation:<br />

The A-Tech-<strong>20</strong> incorporates a selfcalibrating<br />

and self-adjusting control<br />

logic that adjusts the response of the<br />

SATS air conditioner to changes in<br />

temperature and humidity. The<br />

system provides premium setpoint<br />

accuracy while controlling the room<br />

conditions rate of change, minimizing<br />

the equipment energy consumption<br />

and maximizing the system’s<br />

operating life and reliability.<br />

Remote Stop / Start:<br />

<strong>Inc</strong>luded in the system's electrical<br />

control circuit shall be a 2-pin<br />

terminal connection for remote stop /<br />

start of the ModulAiR air conditioner<br />

by a remote source.<br />

POWER LOSS RESTART:<br />

In the event of a loss of power to the<br />

system, the A-Tech-<strong>20</strong> can be<br />

configured for Automatic or <strong>Manual</strong><br />

Restart. The A-Tech-<strong>20</strong>'s nonvolatile<br />

memory enables the system<br />

to restart when power is restored,<br />

without the loss of the "last" stored<br />

set points and other system configuration<br />

settings.<br />

Sequential Load Activation:<br />

<strong>To</strong> minimize the total in-rush current<br />

loads during system start-up/restart,<br />

the A-Tech-<strong>20</strong> controller can be<br />

configured for time-delay sequence<br />

start-up. The user can designate<br />

specific unit restart time-delays, as<br />

well as, each unit's respective<br />

compressor, electric heater and/or<br />

humidifier. Unit restart delay can be<br />

adjusted from 0 to 10 minutes. Unit<br />

compressor, electric heater and/or<br />

humidifier restart delay can be<br />

adjusted from 0 to 60 seconds.<br />

Recovery Delay:<br />

After a power loss, the A-Tech-<strong>20</strong>'s<br />

Recovery Delay feature allows the<br />

ModulAiR A/C to operate without<br />

initiating any high or low temperature<br />

or humidity alarms for a delayed<br />

period. This feature allows the A/C<br />

time (15 to 60 minutes adj.) to "pulldown"<br />

the conditioned space's load<br />

without nuisance alarms during initial<br />

start-up or power loss restart.<br />

COMPRESSOR OPERATIONS:<br />

Short cycle protection:<br />

Each compressor is protected from<br />

frequent compressor cycling through<br />

the A-Tech-<strong>20</strong>'s minimum compressor<br />

ON and minimum compressor<br />

OFF short cycle timers.<br />

Cold Start Time Delay:<br />

Each compressor of a DX Split<br />

system is protected from liquid<br />

slugging through the A-Tech-<strong>20</strong>'s<br />

Cold Start compressor time delay.<br />

The Cold Start timer delays, and<br />

therefore, overrides the system's<br />

refrigerant low suction pressure<br />

Guide Specifications - Microprocessor Control Options<br />

3-7


Microprocessor Controls - A-Tech-<strong>20</strong><br />

Guide Specifications - Microprocessor Control Options<br />

switch during system start-up. This<br />

allows the system time to build<br />

sufficient discharge pressure during<br />

cold weather start-up.<br />

Pump-Down Cycle:<br />

The A-Tech-<strong>20</strong> is pre-programmed<br />

for a one-time refrigerant system<br />

pump-down cycle upon compressor<br />

shutdown on all split DX systems.<br />

This assists in the prevention of<br />

liquid slugging at start-up/restart.<br />

SECURITY:<br />

Multiple security levels prevent<br />

unauthorized adjustment of critical<br />

system parameters. The user may<br />

select a four-digit password for<br />

setpoint and configuration changes.<br />

Keypad Lockout:<br />

The A-Tech-<strong>20</strong> includes a selectable<br />

Keypad Lock-Out feature that<br />

prevents unauthorized users from<br />

making changes to system setpoints<br />

and settings available directly from<br />

the multi-function keypad/display.<br />

Keypad Lock-Out eliminates the<br />

need for stat-guards.<br />

DIAGNOSTICS & SERVICE MODE<br />

The A-Tech-<strong>20</strong> incorporates a<br />

unique self-diagnostics algorithm that<br />

continually tests system functions<br />

and hardware operation. In the<br />

event of such a failure, the user will<br />

be alerted to the condition via a<br />

visual and audible alarm.<br />

Control Board:<br />

Initiates a self-test of the control<br />

system.<br />

Input diagnostics:<br />

All system inputs and input devices<br />

are continuously monitored for<br />

proper operation.<br />

Output diagnostics:<br />

(Service Mode)<br />

Major component functionality can<br />

be tested by manually turning<br />

components ON and OFF from the<br />

A-Tech-<strong>20</strong> control panel. Select<br />

output devices that can be manually<br />

tested include (if applicable):<br />

• Compressor 1 or 2 • CW Valve<br />

• Blower Motor • HW Valve<br />

• Humidifier • FC Valve<br />

• Heat 1, 2 or 3 stgs • AWS Valve<br />

• Summary Alarm • Liq-Line Solenoid<br />

• Custom Alarm 1 • GC Pump Enable<br />

TIME CLOCK & NIGHT SET-BACK<br />

The A-Tech-<strong>20</strong> includes both Time<br />

Clock and Night Set-Back occupied/<br />

non-occupied energy saving modes.<br />

These features enable the user to<br />

customize each unit's daily 5-day/<br />

weekly and 2-day/weekend operational<br />

schedule.<br />

Time-Clock Feature:<br />

The Time-Clock feature enables the<br />

user to create an automatic time<br />

schedule for the unit to be allowed<br />

ON. The Time-Clock 5-2 day<br />

schedule allows the user to limit unit<br />

operation to occupied periods only.<br />

Night Set-Back Feature:<br />

The Night Set-Back feature enables<br />

the user to create a schedule for<br />

automatic relaxing of the unit's<br />

temperature and humidity control set<br />

points. For example, during the<br />

space occupied periods of 7am to<br />

6pm, the unit operates at a temperature<br />

setpoint of 72°F. Then, during<br />

the space unoccupied periods of<br />

6pm to 7am the next morning, the<br />

temperature setpoint automatically<br />

"relaxes" to 77°F. The Set-Back<br />

schedule resets again after 7am that<br />

morning where the temperature<br />

setpoint changes back to 72°F for<br />

Day Time Operation.<br />

Override Feature:<br />

During the unoccupied time cycles,<br />

the user can temporarily "override"<br />

the Time-Clock and/or Set-Back<br />

features. The user can override<br />

these functions for a time duration of<br />

1 to 6 hours.<br />

CyberLAN<br />

Networking Options<br />

MULTI-UNIT "N+1"<br />

SEQUENCING<br />

(Optional)<br />

AC-1 AC-2 AC-3<br />

(Master)<br />

AC-4 AC-5 AC-6<br />

(Standby)<br />

Critical control applications can<br />

incorporate the A-Tech-<strong>20</strong>'s Cyber-<br />

LAN multi-unit sequencing program<br />

logic, where under an A/C failure<br />

condition, the A-Tech-<strong>20</strong> will automatically<br />

initiate the unit operation of<br />

a designated standby/backup unit.<br />

Multi-Unit Sequencing:<br />

Multiple CyberAiR air conditioners<br />

incorporating A-Tech-<strong>20</strong> controls can<br />

be configured in groups of up to 6<br />

(six) units to allow for "N+1" redundancy/backup<br />

critical application<br />

operation.<br />

The "N" in N+1, represents the<br />

number of concurrent units in an On-<br />

Line Operational Mode with 1(one)<br />

unit in a standby mode. The value of<br />

"N" can range from 1 unit to a<br />

maximum of 5 units with a minimum<br />

and maximum of quantity 1 unit in<br />

standby mode.<br />

3-8


Microprocessor Controls - A-Tech-<strong>20</strong><br />

<strong>To</strong> allow for equal unit runtime and/or<br />

to ensure unit operation, the A-Tech-<br />

<strong>20</strong> can be configured for automatic<br />

timed and/or manual lead-lag of<br />

standby unit operation.<br />

The CyberLAN Multi-Unit Sequencing<br />

control logic shall automatically<br />

initiate the current standby unit upon<br />

a user selectable system failure<br />

alarm condition.<br />

The A-Tech-<strong>20</strong> is programmed to<br />

automatically change from current<br />

primary unit operation to secondary<br />

standby unit operation via three<br />

methods:<br />

1) <strong>Manual</strong> ChangeOver<br />

2) Automatic Timed (1-30 days)<br />

3) Automatic ChangeOver on Unit<br />

Failure (if applicable):<br />

• High Temperature<br />

• Low Temperature<br />

• High Humidity<br />

• Low Humidity<br />

• High Head Press<br />

• Low Suction Press<br />

• Sensor Failure<br />

• Loss of <strong>Air</strong> Flow<br />

• Dirty Filter<br />

• Leak Detection<br />

• Smoke Detection<br />

• Firestat<br />

• GC Pump Failure<br />

• Comm. Failure<br />

Factory defaults set a "logical" active/<br />

inactive state for the alarms. This is<br />

to limit "nuisance" type alarms that<br />

may occur because of conditions<br />

inherent to a particular application or<br />

system and that are not critical to the<br />

operation of the system.<br />

(For example: If Low Humidity is not<br />

critical to a particular application, and<br />

therefore, the A/C unit is not equipped<br />

with a Humidifier, the Low Humidity Alarm<br />

can be set to an inactive state.)<br />

Multi-Unit Network Grouping<br />

Interconnect Cable Options:<br />

• 75 ft. cable length (standard option)<br />

• 150 ft. cable length<br />

Capacity Assist-Mode:<br />

(Additionally Optional)<br />

In addition to switchover via manual,<br />

automatic timed or failure, the<br />

CyberLAN Multi-Unit Sequencing<br />

“Capacity Assist-Mode” can initiate<br />

switchover to standby unit operation<br />

to assist in the temperature and/or<br />

humidity control of the space.<br />

Remote Wall Mounted<br />

Capacity Assist T/H Sensor<br />

Sequence of Operation:<br />

The optional Capacity Assist Mode<br />

includes quantity one remote wall<br />

mounted Capacity Assist-Mode T/H<br />

Sensor with interconnect cable. This<br />

single capacity assist remote T/H<br />

sensor controls all N+1 units in the<br />

respective CyberLAN Group. <strong>To</strong><br />

establish a single point of control<br />

reference, the CyberLAN Group’s<br />

temperature and humidity set point is<br />

determined by the Master Unit’s<br />

(U1’s) A-Tech-<strong>20</strong> setpoints. Therefore,<br />

each of the current on-line units<br />

of the CyberLAN Group operate and<br />

control space temperature and/or<br />

humidity based on the Master Unit’s<br />

(U1’s) TEMP and HUMID SETPT in<br />

respect to their individual deadband.<br />

Capacity Assist Sensor Cable Options:<br />

• 75 ft. cable length (standard option)<br />

• 150 ft. cable length<br />

The current standby unit is enabled<br />

when the actual space temperature<br />

or humidity rises or falls to a condition<br />

equal to the Master Unit’s (U1’s)<br />

setpoint plus dead-band plus stage<br />

differential (if appl.) plus Capacity<br />

Assist Differential.<br />

(Note: As standard, each unit of a<br />

CyberLAN Group incorporating Capacity<br />

Assist Mode additionally includes its own<br />

standard unit mounted return air T/H<br />

sensor. If the Capacity Assist Sensor or its<br />

communications cable were to fail, Multi-<br />

Unit & Capacity Assist Mode operations will<br />

be automatically disabled, and the N+1<br />

Units will perform as stand-alone systems.<br />

CyberLAN - REMOTE<br />

COMMUNICATIONS<br />

(Optional)<br />

REMOTE BMS CONNECTION<br />

(ModBus Gateway)<br />

A-Tech-<strong>20</strong> Inputs & Outputs can be<br />

remotely monitored (address readable)<br />

and remotely controlled<br />

(address writable) via any building<br />

management system (BMS) / local<br />

area network (LAN) control system<br />

that can communicate via a ModBus<br />

protocol. Each A-Tech-<strong>20</strong> configured<br />

for BMS communication shall<br />

incorporate an optional Serial<br />

Communication Port that is field<br />

wired to a factory provided wall<br />

mounted ModBus Gateway.<br />

(Note: A list of the addressable I/Os are<br />

available upon request from your local<br />

SATS Sales Representative.)<br />

16 Units Per CyberLAN ModBus:<br />

Each ModBus Gateway can accommodate<br />

up to 16 (sixteen) A/C units<br />

in a group.<br />

The total number of Gateways<br />

required for a given application may<br />

not depend only on the number of<br />

maximum (16) units each Gateway<br />

can accommodate, but also the<br />

facility layout.<br />

(Note: The units of a CyberLAN<br />

Networking Group must be connected to<br />

each other and then to the ModBus<br />

Gateway via shielded serial twisted-pair<br />

cabling. This cabling is not included in<br />

SATS' CyberLAN Remote Communications<br />

/ ModBus Gateway option, as a<br />

standard. This cabling is typically<br />

provided by the installing contractor.)<br />

Guide Specifications - Microprocessor Control Options<br />

3-9


Optional Features - Guide Specifications<br />

Optional Features - Guide Specifications<br />

3-10<br />

SELECTED OPTIONS<br />

Humidity Control<br />

ModulAiR floor systems include<br />

the A-Tech-<strong>20</strong> Microprocessor<br />

Controller, Electrode Canister<br />

Steam Humidifier and Dehumidification<br />

Mode with Electric Reheat/<br />

Heat for total temperature and<br />

humidity control, as a standard.<br />

However, these standard features<br />

can be deleted and/or substituted<br />

with alternate features to allow you<br />

the flexibility to select the configuration<br />

best suited for your unique<br />

application.<br />

Canister Steam Humidification:<br />

(standard)<br />

The humidifier shall be an electrode<br />

steam canister type and shall have<br />

an adjustable humidity output setting<br />

from 25 to 100% of the full rated<br />

humidifier capacity. The humidifier<br />

shall incorporate an automatic flush<br />

cycle that senses the current consumption<br />

of the humidifier and<br />

controls mineral concentration of the<br />

water. A “Change Cylinder” light shall<br />

notify service personnel when the<br />

humidification output is below rated<br />

requirements and when maintenance<br />

is due.<br />

Dehumidification Cycle: (standard)<br />

The floor A/C shall be provided with a<br />

refrigeration based dehumidification<br />

mode. Moisture is condensed on the<br />

cooling coil and discharged through<br />

the condensate drain. Electric reheat<br />

shall be provided to offset sensible<br />

cooling during the dehumidification<br />

cycle.<br />

Electric Heat/Reheat: (standard)<br />

A factory mounted and wired electric<br />

resistance heater shall be included to<br />

provide automatic sensible reheating<br />

mode during the dehumidification cycle<br />

and automatic heating mode as<br />

required. Electric heaters shall be<br />

provided with thermal / magnetic circuit<br />

breakers which shall protect each<br />

conductor. <strong>Inc</strong>luded shall be one<br />

automatic resetting and one manual<br />

resettable over-temperature safety<br />

device (pilot duty).<br />

Heater elements shall be of a safe lowwatt<br />

density, plated fin-tubular design.<br />

High Static Pressure<br />

Belt-Drive Blowers<br />

The ModulAiR vertical floor air<br />

conditioner shall be provided with a<br />

high static pressure belt-driven<br />

evaporator blower to provide standard<br />

unit CFM @ ____ " e.s.p.<br />

(Note: Due to the probable change in<br />

standard unit blower motor horsepower for<br />

the High Static Belt-Drive Blower option,<br />

please consult your local SATS sales<br />

representative for the following unit<br />

specification changes:<br />

• Blower Motor Horsepower<br />

• Net Cooling Capacity<br />

• Electrical Data<br />

• Discharge Blower Data<br />

Unit AIr Flow Rate (CFM) will match the<br />

standard data as shown in Section 4 of this<br />

manual for each respective unit model.<br />

Filtration<br />

ModulAiR vertical floor A/C's are<br />

available with the following standard<br />

and optional high efficiency IAQ<br />

conscious filtration:<br />

F1: 2", 30% Eff. Filters (std 084/1<strong>20</strong>)<br />

F2: 4", 30% Eff. Filters (std 192/240)<br />

F3: 4", 60% Eff. Filters<br />

F4: 2", 30% Pre / 4", 60% Eff. Final Filters<br />

<strong>Air</strong> Pattern Type Filters Avail.<br />

MCS-084/1<strong>20</strong>-( )-U:<br />

w/ free-front return: F1<br />

w/ ducted rear return: F1, F2, F3, F4<br />

MCS-084/1<strong>20</strong>-( )-D:<br />

w/ top return: F1, F2, F3, F4<br />

MCS-192/240-( )-U:<br />

w/ free-front return: F2, F3<br />

w/ ducted rear return: F2, F3, F4<br />

MCS-192/240-( )-D:<br />

w/ top return: F2, F3, F4<br />

Filter ratings are based on dust spot<br />

efficiency ratings per ASHRAE Test<br />

Standard 52-76.<br />

(Note: Optional filters create additional<br />

static pressure and may require the High<br />

Static Pressure Belt-Drive Option. Please<br />

consult your local SATS sales representative<br />

for details.)


HP<br />

LP<br />

Optional Features - Guide Specifications<br />

Head Pressure Control<br />

AIR COOLED - Low Ambient<br />

-<strong>20</strong>°F, Variable Speed Control<br />

(Model HES-( )-LSA Condensers)<br />

The air cooled system shall incorporate<br />

a low ambient variable speed fan<br />

head pressure control for year-round<br />

system operation down to -<strong>20</strong>°F DB<br />

minimum ambient air temperature.<br />

-30°F, Flooded Control<br />

Remote <strong>Air</strong><br />

Cooled Condenser<br />

Flooded<br />

Head Pressure<br />

Control Valve<br />

Relief<br />

Valve<br />

Liquid Refrigerant<br />

Receiver<br />

Scroll<br />

Compressor<br />

Evaporator<br />

Cooling Coil<br />

High<br />

Low<br />

Feeler<br />

Pressure<br />

Pressure<br />

Bulb<br />

Switch<br />

Switch<br />

Liquid Line<br />

Sight<br />

Solenoid Valve<br />

Glass<br />

Refrigerant<br />

Refrigerant Drier / Strainer Thermal Expansion<br />

Reclaim Port<br />

Valve<br />

Equalizer<br />

Line<br />

The air cooled system shall incorporate<br />

a low ambient flooded head<br />

pressure control for year-round<br />

system operation down to -30°F DB<br />

minimum ambient air temperature.<br />

This option shall include a factory<br />

installed crankcase heater, cold-start<br />

relay, liquid refrigerant receiver with<br />

receiver liquid level sight glass and<br />

head pressure regulating valve for<br />

flooded condenser operation.<br />

Each refrigerant circuit's head<br />

pressure shall be controlled by a<br />

factory installed ____-way water /<br />

glycol regulating valve rated for ____<br />

psig. w.w.p.<br />

DX - Capacity Modulation<br />

/ Free-Protecion<br />

SNAP-ACTING, Hot Gas Bypass<br />

(Models MCS-()-DAR, DW & DG only)<br />

The ModulAiR floor A/C shall incorporate<br />

a snap acting hot gas bypass<br />

system to provide modulation of the<br />

unit’s cooling capacity and evaporator<br />

coil freeze protection under low load<br />

conditions.<br />

Remote <strong>Air</strong><br />

Cooled Condenser<br />

Flooded<br />

Head Pressure<br />

Control Valve<br />

Relief<br />

Valve<br />

Liquid Refrigerant<br />

Receiver<br />

Refrigerant<br />

Reclaim Port<br />

High<br />

Pressure<br />

Switch<br />

HP<br />

Scroll<br />

Compressor<br />

Refrigerant<br />

Drier / Strainer<br />

Low<br />

Pressure<br />

LP Switch<br />

Hot Gas<br />

Regulator Valve<br />

(Optional)<br />

Liquid Line<br />

Sight<br />

Solenoid Valve<br />

Glass<br />

Equalizer<br />

Line<br />

Thermal Expansion<br />

Valve<br />

Chilled Water<br />

Control Valves<br />

Feeler<br />

Bulb<br />

Evaporator<br />

Cooling Coil<br />

Standard (0-10 Vdc) Valve Control:<br />

A ____-way modulating CW or AWS<br />

cooling control valve rated for a<br />

maximum ____ psig w.w.p. shall be<br />

factory installed. Precision cooling<br />

control shall be accomplished via a 0-<br />

10 Vdc A-Tech-<strong>20</strong> analog control<br />

signal to the proportionally actuating<br />

control valve.<br />

ACCESSORIES<br />

Adjustable Floor Stand:<br />

A _____ " high adjustable floor stand<br />

shall be provided to allow for ease of<br />

installation of the ModulAiR A/C onto<br />

a raised floor. The floor stand shall be<br />

field installed.<br />

Floor Stand<br />

Nominal Height<br />

Dimensional<br />

Data -<br />

"A" Dimension<br />

Floor Stand Heights<br />

Adjustable Height<br />

Minimum<br />

Maximum<br />

Turning Vane<br />

Availability<br />

4 .0" ( Upflow Units Only)<br />

3 .5"<br />

4.5"<br />

Not Availabl e<br />

6 .0"<br />

5 .0"<br />

7.0"<br />

Not Availabl e<br />

Optional Features - Guide Specifications<br />

WATER / GLYCOL COOLED<br />

12.0"<br />

11.0"<br />

15.0"<br />

Optional<br />

15.0"<br />

14.0"<br />

18.0"<br />

Optional<br />

18.0"<br />

17.0"<br />

21.0"<br />

Optional<br />

24.0"<br />

23.0"<br />

26.0"<br />

Optional<br />

DX Water Cooled and Glycol Cooled<br />

systems are available with following<br />

standard (V1) and optional (V2-V6)<br />

head pressure regulating control<br />

valves:<br />

V1: 2-way, 150 psig (standard)<br />

V2: 2-way, 350 psig<br />

V3: 2-way, 450 psig<br />

V4: 3-way, 150 psig<br />

V5: 3-way, 350 psig<br />

V6: 3-way, 450 psig<br />

Chilled Water and Alternate Water<br />

Source cooling shall be controlled by<br />

the following standard and optional<br />

control valves:<br />

Models MCS-084/1<strong>20</strong>-C:<br />

V1: 3-way, 300 psig (standard)<br />

V2: 3-way, 400 psig<br />

V3: 2-way, 300 psig<br />

V4: 2-way, 400 psig<br />

Models MCS-192/240-C:<br />

V5: 3-way, 400 psig (standard)<br />

V6: 2-way, 400 psig<br />

Note: For additional floor stand heights,<br />

please contact your local SATS sales<br />

representative.<br />

Additional Floor Stand Options:<br />

Turning Vanes:<br />

Turning vanes shall be factory<br />

provided for field installation to each<br />

unit's floor stand.<br />

3-11


Optional Features - Guide Specifications<br />

Optional Features - Guide Specifications<br />

Seismic Zone-4 Rate:<br />

The adjustable floor stand shall be<br />

certified rated for seismic zone-4<br />

installation.<br />

<strong>To</strong>p Discharge Plenum Box:<br />

(Up-Flow units only)<br />

A 2 or 3-way (please specify) plenum<br />

discharge box shall be provided. The<br />

plenum box shall include doubledeflecting,<br />

adjustable grilles. The<br />

plenum box shall ship separately for<br />

rigging purposes.<br />

Condensate Pump<br />

(Factory Mounting Available)<br />

A condensate pump shall be factory<br />

installed within the ModulAiR system<br />

for automatic removal of condensate<br />

and humidifier flush water (if applicable).<br />

The condensate pump shall include an<br />

internal overflow safety float switch<br />

which, when wired to the A/C's remote<br />

stop/start terminals, shall open the A/<br />

C's control circuit, thereby shutting the<br />

A/C down in the event of a condensate<br />

overflow.<br />

The condensate pump shall be<br />

specifically designed to operate with<br />

the higher condensate temperatures<br />

caused by the flush and drain cycle of<br />

the electrode canister humidifiers.<br />

Smoke Detector<br />

A photo-electric smoke detector shall<br />

be factory installed in the ModulAiR<br />

evaporator section on the suction side<br />

of the evaporator blower.<br />

The smoke detector shall be rated for<br />

high air velocity applications, and shall<br />

shut down the air conditioner upon<br />

sensing smoke in the return air<br />

stream.<br />

Optional Auxiliary Contact:<br />

An auxiliary dry-contact (n/o) terminal<br />

connection shall be provided for<br />

remote notification of a smoke<br />

detection alarm.<br />

Firestat<br />

The air conditioner shall be provided<br />

with a factory wired and mounted<br />

firestat. The firestat shall shut down<br />

the air conditioner upon sensing a<br />

high return air temperature.<br />

Remote Water Detectors<br />

Single (one) - Spot Type Detector:<br />

Quantity 1(one) remote spot type<br />

water/leak detector per A/C unit shall<br />

be factory provided for remote field<br />

installation. Upon sensing a water<br />

leak, the normally closed water<br />

detector control circuit shall open,<br />

thereby shutting down the air<br />

conditioner's water producing operations.<br />

Dual (two) - Spot Type Detectors:<br />

Quantity 2(two) remote spot type<br />

water/leak detectors per A/C unit shall<br />

be factory provided for remote field<br />

installation. Upon sensing a water<br />

leak, the normally closed water<br />

detector control circuit shall open,<br />

thereby shutting down the air<br />

conditioner's water producing operations.<br />

40 Ft. - Strip/Cable Type Detector:<br />

A 40 Ft. in length remote strip/cable<br />

type water/leak detector shall be<br />

factory provided for remote field<br />

installation. In addition to the 40 Ft.<br />

cable, a 24V water detector power<br />

module shall require field mounting<br />

and wiring to factory provided terminal<br />

connection. Upon sensing a water<br />

leak, the normally closed water<br />

detector control circuit shall open,<br />

thereby shutting down the air<br />

conditioner's water producing operations.<br />

Optional Auxiliary Contact:<br />

An auxiliary dry-contact (n/o) terminal<br />

connection shall be provided for<br />

remote notification of a water detection<br />

alarm.<br />

Compressor Sound Jackets<br />

(MCS-( )-DW/DG-() Only!)<br />

Each compressor shall be provided<br />

with a factory installed acoustical<br />

3-12


Optional Features - Guide Specifications<br />

sound jacket. Each sound jacket shall<br />

have a snap closure system for ease<br />

of removing and reinstallation during<br />

maintenance. Each sound jacket shall<br />

have a Noise Reduction Coefficient<br />

NRC of 85 per ASTM C-423 and a<br />

Sound Transmission Loss STC of 11<br />

per ASTM E-90.<br />

Glycol Pump Packages<br />

Single Pump Packages<br />

(Models GPS-( )-S)<br />

The system shall be a single pump<br />

package designed to provide the total<br />

required glycol condenser coolant<br />

flow rate at the total rated system<br />

pressure drop.<br />

(Dual Pump Packages)<br />

(Models GPS-( )-D)<br />

The system shall be a dual (two),<br />

redundant, pump package designed to<br />

provide the total required glycol<br />

condenser coolant flow rate at the total<br />

rated system pressure drop. A field<br />

installed coolant sensing flow switch<br />

shall be provided for automatic<br />

switchover from primary to backup<br />

pump operation in the event of a loss of<br />

coolant flow.<br />

<strong>To</strong> allow for equal pump run-time<br />

and/or to ensure pump operation, a<br />

manual lead-lag toggle switch shall<br />

be factory included with the Dual<br />

Pump Package controls.<br />

Single & Dual Pump Packages:<br />

Each pump shall be mounted on a<br />

galvanized steel chassis and protected<br />

by a removable galvanized<br />

steel cover. The pump controls shall<br />

consist of individual pumps controls<br />

mounted in a NEMA-3R enclosure at<br />

the end of each pump package. The<br />

glycol pump package shall be<br />

electrically interfaced with each<br />

drycooler and indoor evaporator via<br />

a 24-Vac low voltage connection.<br />

The pump package controls shall<br />

include, but not be limited to:<br />

• Pump starter(s)/contactor(s) with<br />

fusing per NEC;<br />

• Main Power Non-Fused Disconnect<br />

Switch with lockable handle;<br />

• Powered Pump Package with 24<br />

Volt Control Transformer;<br />

• Main Power Distribution Block with<br />

grounding lug;<br />

The pump shall be sized to<br />

provide:<br />

____<br />

____<br />

____<br />

or<br />

____<br />

GPM (total system flow rate)<br />

ft. w.g. (total system press drop)<br />

% Ethylene Glycol Solution<br />

% Propylene Glycol Solution<br />

Remote Drycoolers<br />

(MODELS HES-( )-LGA)<br />

Remote Drycooler<br />

(Models HES-( )-LGA)<br />

The system shall be a remote<br />

outdoor air cooled glycol drycooler<br />

(fluid-cooler) sized to provide the<br />

total heat of rejection of the system<br />

glycol condenser source solution at<br />

a ___°F DB ambient temperature.<br />

Drycooler casings shall be fabricated<br />

from heavy gauge aluminum for<br />

corrosion protection and appearance.<br />

Structural components shall be<br />

fabricated from galvanized steel for<br />

support.<br />

The drycooler shall incorporate<br />

direct-driven propeller fan(s). Each<br />

fan shall be provided with a low RPM,<br />

non-overloading direct driven motor.<br />

The fan blades shall be made from<br />

aluminum and have zinc plated hubs<br />

for strength and corrosion protection.<br />

Multiple fan drycoolers shall<br />

have internal air baffles to prevent air<br />

bypass from one fan section to<br />

another and to maximize air through<br />

each coil section.<br />

Each drycooler shall be provided<br />

with a field installed 15 gallon<br />

expansion tank and airtrol fitting.<br />

Drycooler - Fan Cycling Controls:<br />

The drycooler control box shall<br />

include, but not be limited to:<br />

• Weather Rated Enclosure<br />

• Fan Motor starter(s)/contactor(s)<br />

with fusing per NEC;<br />

• Aquastat(s) to sense and maintain<br />

proper coolant temperature in DX<br />

mode;<br />

• Main Power Non-Fused Disconnect<br />

Switch;<br />

• Main Power Distribution Block with<br />

grounding lug.<br />

Optional Features - Guide Specifications<br />

3-13


<strong>Air</strong> Cooled - 7 to <strong>20</strong> <strong>To</strong>n “MCS”<br />

Performance Data - <strong>Air</strong> Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

"MCS" Model MCS-084-DAR MCS-1<strong>20</strong>-DAR MCS-192-DAR MCS-240-DAR<br />

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />

75°FDB/62.5°FWB, 50% RH<br />

<strong>To</strong>tal 94,150 119,8<strong>20</strong> 189,560 244,510<br />

Sensible 78,580 100,440 168,080 <strong>20</strong>3,400<br />

72°FDB/60°FWB, 50% RH<br />

<strong>To</strong>tal 89,700 114,070 180,3<strong>20</strong> 233,150<br />

Sensible 77,0<strong>20</strong> 98,4<strong>20</strong> 164,580 199,500<br />

70°FDB/58.5°FWB, 50% RH<br />

<strong>To</strong>tal 87,110 110,750 174,940 226,580<br />

Sensible 75,340 96,2<strong>20</strong> 160,680 195,180<br />

75°FDB/61°FWB, 45% RH<br />

<strong>To</strong>tal 91,480 116,060 184,180 237,080<br />

Sensible 83,990 107,580 179,610 217,810<br />

72°FDB/58.5°FWB, 45% RH<br />

<strong>To</strong>tal 87,190 110,430 175,010 225,880<br />

Sensible 82,400 105,390 172,590 213,730<br />

70°FDB/57°FWB, 45% RH<br />

<strong>To</strong>tal 84,680 107,180 170,040 219,440<br />

Sensible 80,680 103,100 167,980 <strong>20</strong>9,290<br />

Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />

ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />

@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />

<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />

Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />

Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />

Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />

Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />

Standard Control Cycling Cycling Cycling Cycling<br />

Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />

Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />

CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />

Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />

Qty. of Blowers two two two two<br />

Evaporator Coils - Aluminum Fin, Copper Tube<br />

Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />

Face Velocity, fpm 338 469 434 495<br />

Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />

Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />

Watts Input 7,696 9,918 15,582 <strong>20</strong>,878<br />

<strong>To</strong>t. Heat of Rej. (BTU/H) 1<strong>20</strong>,4<strong>20</strong> 153,670 242,740 315,770<br />

Connection Sizes - Copper, (Please refer to ModulAiR IOM <strong>Manual</strong> for proper interconnecting refrigerant line sizing.)<br />

Refrigerant:<br />

Liquid Line, (Qty.) 1/2" OD, (2) 1/2" OD, (2) 7/8" OD, (2) 7/8" OD (2)<br />

Hot Gas Line, (Qty.) 7/8" OD, (2) 7/8" OD, (2) 7/8" OD, (2) 1-1/8" OD (2)<br />

Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />

Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />

4-1


<strong>Air</strong> Cooled - Remote Condenser Data (7 to <strong>20</strong> <strong>To</strong>n “MCS”)<br />

"MCS" Model MCS-084-DAR MCS-1<strong>20</strong>-DAR MCS-192-DAR MCS-240-DAR<br />

Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />

Up-Flow:<br />

Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />

(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />

Down-Flow:<br />

Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />

Physical Data<br />

Approx. Weight 500 lbs x 2 500 lbs x 2 725 lbs x 2 735 lbs x 2<br />

Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />

MCS-( )-DAR-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />

MCS-( )-DAR-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />

><br />

Remote <strong>Air</strong> Cooled Condenser Data:<br />

HES-( )-DL()A - (Remote Outdoor Propeller Fan, <strong>Air</strong> Cooled Condenser for Model MCS-( )-DAR Evaporator Section)<br />

Cond. Model @ 95°F Amb. HES-1<strong>20</strong>-DL()A HES-168-DL()A HES-252-DL()A HES-339-DL()A<br />

Condenser Fan Data<br />

CFM @ free discharge 10,100 13,700 <strong>20</strong>,500 23,000<br />

Motor Hp, (Qty.) 1/3 Hp, (2) 1/3 Hp, (2) 1/3 Hp, (3) 1.5 Hp, (2)<br />

Fan RPM 1,140 1,140 1,140 1,140<br />

Drive Method Direct Driven Direct Driven Direct Driven Direct Driven<br />

Condenser Coil<br />

Rows/Face Area (ft 2 ) 3/ 16.7 3/ 22.2 3/ 32.1 2/ 32.3<br />

Refrigerant Connections<br />

Liquid Line, (Qty.) 7/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 1-3/8" OD, (2)<br />

Hot Gas Line, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-3/8" OD, (2)<br />

Compressors are located with the model MCS-( )-DAR Evaporator Section<br />

HES-( )-DL()A - (Remote Outdoor Propeller Fan(s), <strong>Air</strong> Cooled Condenser for Model MCS-( )-DAR Evaporator Section)<br />

Cond. Model @ 105°F Amb. HES-168-DL()A HES-192-DL()A HES-399-DL()A HES-525-DL()A<br />

Condenser Fan Data<br />

CFM @ free discharge 13,700 12,900 23,<strong>20</strong>0 <strong>20</strong>,700<br />

Motor Hp, (Qty.) 1/3 Hp, (2) 1/3 Hp, (2) 1.5 Hp, (2) 1.5 Hp, (2)<br />

Fan RPM 1,140 1,140 1,140 1,140<br />

Drive Method Direct Driven Direct Driven Direct Driven Direct Driven<br />

Condenser Coil<br />

Rows/Face Area (ft 2 ) 3/ 22.2 4/ 22.2 3/ 32.3 4/ 32.3<br />

Refrigerant Connections<br />

Liquid Line, (Qty.) 7/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />

Hot Gas Line, (Qty.) 1-1/8" OD, (2) 1-3/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />

Compressors are located with the model MCS-( )-DAR Evaporator Section<br />

Low Ambient Control<br />

Std Minimum Op. Amb. -<strong>20</strong>°F -<strong>20</strong>°F -<strong>20</strong>°F -<strong>20</strong>°F<br />

Head Press. Method Variable Speed Variable Speed Variable Speed Variable Speed<br />

Optional Min. Oper. Method -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded)<br />

Performance Data - <strong>Air</strong> Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

4-2


Water Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />

Performance Data - Water Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

"MCS" Model MCS-084-DW MCS-1<strong>20</strong>-DW MCS-192-DW MCS-240-DW<br />

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />

75°FDB/62.5°FWB, 50% RH<br />

<strong>To</strong>tal 100,980 128,540 <strong>20</strong>2,540 261,7<strong>20</strong><br />

Sensible 81,190 103,540 173,0<strong>20</strong> <strong>20</strong>9,8<strong>20</strong><br />

72°FDB/60°FWB, 50% RH<br />

<strong>To</strong>tal 96,260 122,460 192,900 249,110<br />

Sensible 79,470 101,370 169,610 <strong>20</strong>6,580<br />

70°FDB/58.5°FWB, 50% RH<br />

<strong>To</strong>tal 93,380 118,980 187,300 242,180<br />

Sensible 77,900 99,190 165,770 <strong>20</strong>2,280<br />

75°FDB/61°FWB, 45% RH<br />

<strong>To</strong>tal 97,780 124,<strong>20</strong>0 196,7<strong>20</strong> 253,3<strong>20</strong><br />

Sensible 86,580 110,840 185,600 224,300<br />

72°FDB/58.5°FWB, 45% RH<br />

<strong>To</strong>tal 93,240 118,300 187,430 241,580<br />

Sensible 85,060 108,830 181,580 2<strong>20</strong>,4<strong>20</strong><br />

70°FDB/57°FWB, 45% RH<br />

<strong>To</strong>tal 90,590 114,860 182,0<strong>20</strong> 234,760<br />

Sensible 83,400 106,630 177,480 216,100<br />

Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />

ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />

@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />

<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />

Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />

Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />

Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />

Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />

Standard Control Cycling Cycling Cycling Cycling<br />

Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />

Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />

CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />

Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />

Qty. of Blowers two two two two<br />

Evaporator Coils - Aluminum Fin, Copper Tube<br />

Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />

Face Velocity, fpm 338 469 434 495<br />

Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />

Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />

Watts Input 5.946 7,734 12,568 17,070<br />

Water Cooled Condenser Data - Based on 0% Glycol Solution<br />

<strong>To</strong>t Heat of Reject. 121,280 Btu/h 154,940 Btu/h 245,440 Btu/h 319,980 Btu/h<br />

GPM @ 85°F EWT / 95°F LWT 24.2 GPM 31.0 GPM 29.0 GPM 64.0 GPM<br />

Press. Drop (Ft. of H 2<br />

O) 15.3 Ft. 26.0 Ft. 18.1 Ft. 27.9 Ft.<br />

Condenser Type Coaxial Brazed-Plate Brazed-Plate Brazed-Plate<br />

Std Head Pressure Control - - - - 2-way, 150 psig DX Water Source Regulating Valve - factory installed - - - -<br />

4-3


Water Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />

"MCS" Model MCS-084-DW MCS-1<strong>20</strong>-DW MCS-192-DW MCS-240-DW<br />

Connection Sizes - Copper<br />

Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />

Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />

Water Source In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-3/8 " OD, (2) 1-3/8 " OD, (2)<br />

Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />

Up-Flow:<br />

Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />

(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />

Down-Flow:<br />

Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />

Physical Data<br />

Approx. Weight 530 lbs x 2 530 lbs x 2 800 lbs x 2 810 lbs x 2<br />

Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />

MCS-( )-DW-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />

MCS-( )-DW-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />

><br />

Performance Data - Water Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

4-4


Glycol Cooled - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />

Performance Data - Glycol Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

"MCS" Model MCS-084-DG MCS-1<strong>20</strong>-DG MCS-192-DG MCS-240-DG<br />

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)<br />

75°FDB/62.5°FWB, 50% RH<br />

<strong>To</strong>tal 89,770 113,640 179,800 232,600<br />

Sensible 76,800 98,000 164,450 198,600<br />

72°FDB/60°FWB, 50% RH<br />

<strong>To</strong>tal 85,460 108,040 170,880 221,6<strong>20</strong><br />

Sensible 75,280 96,010 160,710 194,8<strong>20</strong><br />

70°FDB/58.5°FWB, 50% RH<br />

<strong>To</strong>tal 82,960 104,8<strong>20</strong> 165,690 215,270<br />

Sensible 73,600 93,780 156,700 190,480<br />

75°FDB/61°FWB, 45% RH<br />

<strong>To</strong>tal 87,2<strong>20</strong> 110,000 174,640 225,350<br />

Sensible 82,230 105,030 171,860 213,1<strong>20</strong><br />

72°FDB/58.5°FWB, 45% RH<br />

<strong>To</strong>tal 83,1<strong>20</strong> 104,600 166,960 214,580<br />

Sensible 80,460 102,380 165,310 <strong>20</strong>8,500<br />

70°FDB/57°FWB, 45% RH<br />

<strong>To</strong>tal 80,7<strong>20</strong> 101,470 162,080 <strong>20</strong>8,400<br />

Sensible 78,660 99,880 160,740 <strong>20</strong>3,760<br />

Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />

ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />

@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />

<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />

Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />

Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />

Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />

Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />

Standard Control Cycling Cycling Cycling Cycling<br />

Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />

Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />

CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />

Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />

Qty. of Blowers two two two two<br />

Evaporator Coils - Aluminum Fin, Copper Tube<br />

Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />

Face Velocity, fpm 338 469 434 495<br />

Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22<br />

Type, (Qty.) Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2)<br />

Watts Input 8.<strong>20</strong>6 10,580 16,482 21,998<br />

Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution<br />

<strong>To</strong>t. Heat of Reject. 117,780 Btu/h 149,750 Btu/h 236,060 Btu/h 307,680 Btu/h<br />

GPM @ 110°F EGT / 1<strong>20</strong>°F LGT 26.0 GPM 33.2 GPM 52.2 GPM 68.0 GPM<br />

Press. Drop (Ft. of H 2<br />

O) 16.6 Ft. 28.1 Ft. 19.9 Ft. 30.1 Ft.<br />

Condenser Type Coaxial Coaxial Brazed-Plate Brazed-Plate<br />

Std Head Pressure Control - - - - 2-way, 150 psig DX Glycol Source Regulating Valve - factory installed - - - -<br />

4-5


Glycol Cooled - Condenser Data (7 to <strong>20</strong> <strong>To</strong>n "MCS")<br />

"MCS" Model MCS-084-DG MCS-1<strong>20</strong>-DG MCS-192-DG MCS-240-DG<br />

Connection Sizes - Copper<br />

Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />

Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />

Water Source In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-3/8 " OD, (2) 1-3/8 " OD, (2)<br />

Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />

Up-Flow:<br />

Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />

(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />

Down-Flow:<br />

Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />

Physical Data<br />

Approx. Weight 530 lbs x 2 530 lbs x 2 800 lbs x 2 810 lbs x 2<br />

Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />

MCS-( )-DG-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />

MCS-( )-DG-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />

><br />

Drycooler / Pump Package<br />

Selection @ 95°F HES-1<strong>20</strong>-LGA HES-168-LGA HES-252-LGA HES-447-LGA<br />

GPM @ 1<strong>20</strong>°F EGT/110°F LGT 26.0 GPM 33.2 GPM 52.2 GPM 68.0 GPM<br />

Press. Drop (Ft. of H 2<br />

O) 6.7 Ft. 13.2 Ft. 6.4 Ft. 14.1 Ft.<br />

No. of Circuits 24 24 48 21<br />

Epansion Tank 15 Gal 15 Gal 15 Gal 15 Gal<br />

Pipe Connection (In/Out) 2-1/8" OD 2-1/8" OD 2-5/8" OD 2-5/8" OD<br />

105°F Amb. Selections Optional - Please refer to Glycol Pump / Drycooler <strong>Engineering</strong> <strong>Manual</strong><br />

Standard Pump GPS-015-S GPS-015-S GPS-0<strong>20</strong>-S GPS-030-S<br />

Quantity 1(one) 1(one) 1(one) 1(one)<br />

Horsepower 1.5 Hp 1.5 Hp 2.0 Hp 3.0Hp<br />

<strong>To</strong>tal Hd Press. (ft. w.g.) Ft. Ft. Ft. Ft.<br />

Dual Pump Packages Optional - Please refer to Glycol Pump / Drycooler <strong>Engineering</strong> <strong>Manual</strong><br />

Performance Data - Glycol Cooled (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

4-6


Chilled Water - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />

Performance Data - Chilled Water (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

"MCS" Model MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

NET COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings)<br />

75°FDB/62.5°FWB, 50% RH<br />

High Flow <strong>To</strong>tal 108,4<strong>20</strong> 139,660 2<strong>20</strong>,280 244,0<strong>20</strong><br />

(8°F ∆T w<br />

) Sensible 88,340 116,440 190,600 213,160<br />

GPM / (pd. Ft.) 27.2 / (11.7) 34.8 / (18.7) 55.8 / (2.9) 61.4 / (3.5)<br />

Med. Flow <strong>To</strong>tal 99,480 128,600 187,0<strong>20</strong> <strong>20</strong>7,6<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 83,800 110,5<strong>20</strong> 172,400 192,840<br />

GPM / (pd. Ft.) <strong>20</strong>.0 / (6.7) 26.0 / (10.7) 38.0 / (1.4) 42.0 / (1.7)<br />

Low Flow <strong>To</strong>tal 91,180 117,780 135,380 152,240<br />

(12°F ∆T w<br />

) Sensible 79,2<strong>20</strong> 104,1<strong>20</strong> 135,380 152,240<br />

GPM / (pd. Ft.) 15.2 / (4.1) 19.6 / (6.5) 23.0 / (0.5) 25.8 / (0.6)<br />

72°FDB/60°FWB, 50% RH<br />

High Flow <strong>To</strong>tal 89,400 115,160 172,780 191,240<br />

(8°F ∆T w<br />

) Sensible 79,7<strong>20</strong> 104,9<strong>20</strong> 166,1<strong>20</strong> 185,540<br />

GPM / (pd. Ft.) 22.8 / (8.4) 28.8 / (13.2) 43.8 / (1.9) 48.6 / (2.2)<br />

Med. Flow <strong>To</strong>tal 81,040 103,500 131,8<strong>20</strong> 147,960<br />

(10°F ∆T w<br />

) Sensible 74,700 97,480 131,8<strong>20</strong> 147,960<br />

GPM / (pd. Ft.) 16.4 / ( 4.6) <strong>20</strong>.8 / (7.2) 27.0 / (0.7) 30.2 / (0.9)<br />

Low Flow <strong>To</strong>tal 70,400 84,400 99,700 113,280<br />

(12°F ∆T w<br />

) Sensible 67,740 84,400 99,700 113,280<br />

GPM / (pd. Ft.) 12.0 / (2.4) 14.4 / (3.6) 17.2 / (0.2) 19.4 / (0.3)<br />

70°FDB/58.5°FWB, 50% RH<br />

High Flow <strong>To</strong>tal 78,100 99,460 137,960 154,980<br />

(8°F ∆T w<br />

) Sensible 73,<strong>20</strong>0 95,480 137,960 154,980<br />

GPM / (pd. Ft.) 19.6 / (6.5) 25.2 / (10.1) 35.2 / (1.2) 39.4 / (1.5)<br />

Med. Flow <strong>To</strong>tal 67,9<strong>20</strong> 83,540 109,6<strong>20</strong> 123,700<br />

(10°F ∆T w<br />

) Sensible 66,540 83,540 109,6<strong>20</strong> 123,700<br />

GPM /(pd.\Ft.) 13.6 / ( 3.3) 16.8 / (4.9) 22.6 / (0.5) 25.4 / (0.6)<br />

Low Flow <strong>To</strong>tal 55,600 72,8<strong>20</strong> 86,160 91,400<br />

(12°F ∆T w<br />

) Sensible 55,600 72,8<strong>20</strong> 86,160 91,400<br />

GPM / (pd. Ft.) 9.6 / (1.4) 12.4 / (2.6) 15.0 / (0.2) 15.8 / (0.2)<br />

75°FDB/61°FWB, 45% RH<br />

High Flow <strong>To</strong>tal 101,000 130,240 <strong>20</strong>3,640 224,640<br />

(8°F ∆T w<br />

) Sensible 91,6<strong>20</strong> 1<strong>20</strong>,7<strong>20</strong> 195,8<strong>20</strong> 218,340<br />

GPM / (pd. Ft.) 25.2 / (10.3) 32.8 / (16.5) 51.6 / (2.5) 56.8 / (3.0)<br />

Med. Flow <strong>To</strong>tal 93,360 119,100 162,860 182,440<br />

(10°F ∆T w<br />

) Sensible 87,000 113,600 162,860 182,440<br />

GPM / (pd. Ft.) 18.8 / (6.0) 24.0 / (9.3) 33.2 / (1.1) 37.0 / (1.4)<br />

Low Flow <strong>To</strong>tal 83,460 100,840 134,800 151,580<br />

(12°F ∆T w<br />

) Sensible 80,600 100,840 134,800 151,580<br />

GPM / (pd. Ft.) 14.0 / (3.5) 16.8 / (4.9) 23.0 / (0.5) 25.8 / (0.6)<br />

72°FDB/58.5°FWB, 45% RH<br />

High Flow <strong>To</strong>tal 78,9<strong>20</strong> 103,380 157,700 176,5<strong>20</strong><br />

(8°F ∆T w<br />

) Sensible 78,9<strong>20</strong> 103,380 157,700 176,5<strong>20</strong><br />

GPM / (pd. Ft.) <strong>20</strong>.0 / (6.7) 26.0 / (10.9) 40.2 / (1.6) 44.8 / (1.9)<br />

Med. Flow <strong>To</strong>tal 71,980 94,380 131,340 147,4<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 71,980 94,380 131,340 147,4<strong>20</strong><br />

GPM / (pd. Ft.) 14.4 / (3.7) 19.2 / (6.1) 26.8 / (0.7) 30.0 / (0.9)<br />

Low Flow <strong>To</strong>tal 64,260 84,1<strong>20</strong> 99,<strong>20</strong>0 112,680<br />

(12°F ∆T w<br />

) Sensible 64,260 84,1<strong>20</strong> 99,<strong>20</strong>0 112,680<br />

GPM / (pd. Ft.) 10.8 / (1.9) 14.4 / (3.6) 17.0 / (0.2) 19.4 / (0.3)<br />

70°FDB/57°FWB, 45% RH<br />

High Flow <strong>To</strong>tal 70,900 92,980 137,560 154,5<strong>20</strong><br />

(8°F ∆T w<br />

) Sensible 70,900 92,980 137,560 154,5<strong>20</strong><br />

GPM / (pd. Ft.) 18.0 / (5.5) 23.6 / (9.0) 35.0 / (1.2) 39.4 / (1.5)<br />

Med. Flow <strong>To</strong>tal 63,680 83,280 109,160 123,<strong>20</strong>0<br />

(10°F ∆T w<br />

) Sensible 63,680 83,280 109,160 123,<strong>20</strong>0<br />

GPM / (pd. Ft.) 12.8 / (2.9) 16.8 / (4.9) 22.4 / (0.5) 25.2 / (0.6)<br />

Low Flow <strong>To</strong>tal 55,400 72,580 85,9<strong>20</strong> 91,140<br />

(12°F ∆T w<br />

) Sensible 55,400 72,580 85,9<strong>20</strong> 91,140<br />

GPM / (pd. Ft.) 9.2 / (1.4) 12.4 / (2.6) 15.0 / (0.2) 15.8 / (0.2)<br />

4-7


Chilled Water - 7 to <strong>20</strong> <strong>To</strong>n "MCS"<br />

"MCS" Model MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions<br />

3-way (standard) - Modulating (0-10 Vdc)<br />

Size / (Cv) 1" / (8.0 Cv) 1" / (8.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv)<br />

Qty. of Valves Per System 2(Two) 2(Two) 2(Two) 2(Two)<br />

Valve Pressure Rating 300 psig 300 psig 300 psig 300 psig<br />

<strong>To</strong>tal Unit Pressure Drop 8.0 Ft. 12.5 Ft. 7.8 Ft. 9.5 Ft.<br />

2-way (optional) - Modulating (0-10 Vdc)<br />

Size / (Cv) 1" / (8.0 Cv) 1" / (8.0 Cv) 1" / (18.0 Cv) 1" / (18.0 Cv)<br />

Qty. of Valves Per System 2(Two) 2(Two) 2(Two) 2(Two)<br />

Valve Pressure Rating 300 psig 300 psig 300 psig 300 psig<br />

<strong>To</strong>tal Unit Pressure Drop 7.9 Ft. 12.4 Ft. 6.7 Ft. 8.1 Ft.<br />

Chilled Water Coil - Aluminum Fin, Copper Tube<br />

Rows/Face Area (ft 2 ) 4/ 10.6 4/ 10.6 4/ 19.4 4/ 19.4<br />

Face Velocity, fpm 338 469 434 495<br />

Evaporator Blowers / Motors - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys<br />

Horsepower, (Qty.) 3/4 Hp, (2) 1-1/2 Hp, (2) 3 Hp, (2) 3 Hp, (2)<br />

CFM @ ext. st. press. 3,600 @ 0.5” 5,000 @ 0.5” 8,400 @ 0.5" 9,600 @ 0.5"<br />

Drive Method Belt Driven Belt Driven Belt Driven Belt Driven<br />

Qty. of Blowers two two two two<br />

Reheat/Heat - BTU/H Performance Capacities <strong>Inc</strong>lude Motor Heat<br />

ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)<br />

@ 230 & 460V, Htr Kw Rating (# Stages) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg) 10.02 Kw (1-stg)<br />

<strong>To</strong>t BTU/H with Evap Mtr Ht (Kw) 39,560 (11.6 Kw) 43,740 (12.8 Kw) 53,710 (15.7 Kw) 53,710 (15.7 Kw)<br />

Optional Electric Reheat/Heat <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg) <strong>20</strong>.04 Kw (2-stg)<br />

Humidification - Electrode Steam Canister Humidifier with <strong>Manual</strong>ly Adjustable Output, (Standard)<br />

Steam Output, Lbs/Hr 4-15 4-15 4-15 4-15<br />

Power Input 5.1 Kw 5.1 Kw 5.1 Kw 5.1 Kw<br />

Standard Control Cycling Cycling Cycling Cycling<br />

Optional Control - - - - - - - - - - - - - - - - - Modulating (0-10 Vdc) - - - - - - - - - - - - - - - - -<br />

Filters - 2" deep (084/1<strong>20</strong>) & 4" deep (192/240), 30% Dust Spot Efficient, throwaway<br />

Up-Flow:<br />

Nom. Size (in.), (Qty.) 12x24, (2) 12x24, (2) 37x33, (2) 37x33, (2)<br />

(2 total filters per unit) <strong>20</strong>x24, (2) <strong>20</strong>x24, (2) - - - - - - - - - -<br />

Down-Flow:<br />

Nom. Size (in.), (Qty.) 24x24, (2) 24x24, (2) 37x33, (2) 37x33, (2)<br />

Connection Sizes - Copper<br />

Condensate Drain, (with pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD)<br />

Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD<br />

Water In/Out, (Qty.) 1-1/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-5/8" OD, (2)<br />

Physical Data<br />

Approx. Weight 410 lbs x 2 410 lbs x 2 590 lbs x 2 590 lbs x 2<br />

Dimensions: (<strong>To</strong>tal Installed H"xW"xD"), includes access panels, w/o Plenum Box option.)<br />

MCS-( )-C-U (up-flow) 76"x62"x30" 76"x62"x30" 76"x79"x34" 76"x79"x34"<br />

MCS-( )-C-D (down-flow) 82"x62"x30" 82"x62"x30" 82"x79"x34" 82"x79"x34"<br />

><br />

Performance Data - Chilled Water (ModulAiR 7 to <strong>20</strong> ton Systems)<br />

4-8


Chilled Water - 42°F EWT, 0% Glycol<br />

Performance Data - Chilled Water Systems @ 42°F EWT<br />

Net Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil @ 50% RH<br />

75°FDB/62.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 127,860 163,5<strong>20</strong> 260,540 287,4<strong>20</strong><br />

(8°F ∆T w<br />

) Sensible 97,280 127,440 <strong>20</strong>9,800 235,000<br />

GPM/(Ft.) 32.0 / (16.0) 40.8 / (25.1) 65.6 / (3.9) 72.8 / (4.8)<br />

Med Flow <strong>To</strong>tal 117,140 151,160 226,780 252,780<br />

(10°F ∆T w<br />

) Sensible 92,0<strong>20</strong> 121,2<strong>20</strong> 192,640 216,140<br />

GPM/(Ft.) 23.6 / (9.0) 30.4 / (14.4) 46.0 / (2.0) 51.0 / (2.5)<br />

Low Flow <strong>To</strong>tal 107,400 139,1<strong>20</strong> 192,700 215,240<br />

(12°F ∆T w<br />

) Sensible 87,100 114,860 173,900 195,1<strong>20</strong><br />

GPM/(Ft.) 18.0 / (5.5) 23.2 / (8.8) 32.6 / (1.1) 36.4 / (1.3)<br />

72°FDB/60°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 106,380 137,140 213,0<strong>20</strong> 236,6<strong>20</strong><br />

(8°F ∆T w<br />

) Sensible 87,980 115,900 187,600 210,080<br />

GPM/(Ft.) 26.8 / (11.4) 34.4 / (18.2) 53.8 / (2.7) 59.6 / (3.3)<br />

Med Flow <strong>To</strong>tal 97,600 125,760 178,680 199,<strong>20</strong>0<br />

(10°F ∆T w<br />

) Sensible 83,3<strong>20</strong> 109,5<strong>20</strong> 167,880 188,160<br />

GPM/(Ft.) 19.6 / (6.5) 25.2 / (10.3) 36.2 / (1.3) 40.2 / (1.6)<br />

Low Flow <strong>To</strong>tal 88,960 114,900 129,940 146,1<strong>20</strong><br />

(12°F ∆T w<br />

) Sensible 78,360 102,860 129,940 146,1<strong>20</strong><br />

GPM/(Ft.) 14.8 / (3.9) 19.2 / (6.2) 22.2 / (0.4) 24.8 / (0.6)<br />

70°FDB/58.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 94,560 121,940 184,640 <strong>20</strong>5,480<br />

(8°F ∆T w<br />

) Sensible 81,780 107,660 171,280 191,9<strong>20</strong><br />

GPM/(Ft.) 24.0 / (9.3) 30.4 / (14.7) 46.8 / (2.1) 52.0 / (2.6)<br />

Med Flow <strong>To</strong>tal 86,1<strong>20</strong> 110,9<strong>20</strong> 138,180 154,980<br />

(10°F ∆T w<br />

) Sensible 76,940 100,940 138,180 154,980<br />

GPM/(Ft.) 17.6 / (5.2) 22.4 / (8.2) 28.2 / (0.8) 31.6 / (1.0)<br />

Low Flow <strong>To</strong>tal 76,900 98,840 106,540 1<strong>20</strong>,240<br />

(12°F ∆T w<br />

) Sensible 71,080 92,8<strong>20</strong> 106,540 1<strong>20</strong>,240<br />

GPM/(Ft.) 12.8 / (2.8) 16.8 / (4.8) 18.4 / (0.3) <strong>20</strong>.6 / (0.4)<br />

Net Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil @ 45% RH<br />

75°FDB/61°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 118,040 152,2<strong>20</strong> 242,640 269,840<br />

(8°F ∆T w<br />

) Sensible 99,960 131,780 216,560 242,7<strong>20</strong><br />

GPM/(Ft.) 29.6 / (13.8) 38.0 / (22.1) 61.2 / (3.5) 68.0 / (4.2)<br />

Med Flow <strong>To</strong>tal 109,460 141,440 210,640 233,700<br />

(10°F ∆T w<br />

) Sensible 95,340 125,660 198,<strong>20</strong>0 221,6<strong>20</strong><br />

GPM/(Ft.) 22.0 / (8.0) 28.4 / (12.8) 42.6 / (1.8) 47.2 / (2.1)<br />

Low Flow <strong>To</strong>tal 101,060 130,6<strong>20</strong> 162,440 182,140<br />

(12°F ∆T w<br />

) Sensible 90,480 118,980 162,440 182,140<br />

GPM/(Ft.) 16.8 / (4.9) 22.0 / (7.9) 27.6 / (0.7) 30.8 / (0.9)<br />

72°FDB/58.5°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 99,300 128,0<strong>20</strong> 197,0<strong>20</strong> 217,960<br />

(8°F ∆T w<br />

) Sensible 91,240 1<strong>20</strong>,060 192,460 214,8<strong>20</strong><br />

GPM/(Ft.) 25.2 / (10.1) 32.0 / (16.1) 49.8 / (2.4) 55.0 / (2.8)<br />

Med Flow <strong>To</strong>tal 91,300 116,580 158,440 177,460<br />

(10°F ∆T w<br />

) Sensible 86,<strong>20</strong>0 112,480 158,440 177,460<br />

GPM/(Ft.) 18.4 / (5.8) 23.6 / (9.0) 32.2 / (1.0) 36.0 / (1.3)<br />

Low Flow <strong>To</strong>tal 81,2<strong>20</strong> 99,260 129,380 145,500<br />

(12°F ∆T w<br />

) Sensible 79,440 99,260 129,380 145,500<br />

GPM/(Ft.) 13.6 / (3.2) 16.8 / (4.8) 22.0 / (0.4) 24.8 / (0.6)<br />

70°FDB/57°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 88,280 112,380 164,180 183,700<br />

(8°F ∆T w<br />

) Sensible 84,7<strong>20</strong> 110,400 164,180 183,700<br />

GPM/(Ft.) 22.4 / (8.3) 28.4 / (12.7) 41.8 / (1.7) 46.6 / (2.1)<br />

Med Flow <strong>To</strong>tal 75,<strong>20</strong>0 98,6<strong>20</strong> 137,700 154,440<br />

(10°F ∆T w<br />

) Sensible 75,<strong>20</strong>0 98,6<strong>20</strong> 137,700 154,440<br />

GPM/(Ft.) 15.2 / (4.1) <strong>20</strong>.0 / (6.7) 28.2 / (0.8) 31.4 / (1.0)<br />

Low Flow <strong>To</strong>tal 67,500 88,280 105,740 119,640<br />

(12°F ∆T w<br />

) Sensible 67,500 88,280 105,740 119,640<br />

GPM/(Ft.) 11.2 / (2.1) 14.8 / (3.9) 18.2 / (0.3) <strong>20</strong>.4 / (0.4)<br />

(Note:<br />

The above Net Cooling capacities include standard motor heat @ standard CFM / e.s.p. as shown on page 4-8, Evaporator Blower/Motor.)<br />

4-9


Chilled Water - 50°F EWT, 0% Glycol<br />

Net Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil @ 50% RH<br />

75°FDB/62.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 79,180 100,400 143,400 160,640<br />

(8°F ∆T w<br />

) Sensible 74,4<strong>20</strong> 97,0<strong>20</strong> 143,400 160,640<br />

GPM/(Ft.) <strong>20</strong>.0 / (6.6) 25.2 / (10.2) 36.6 / (1.3) 40.8 / (1.6)<br />

Med Flow <strong>To</strong>tal 65,3<strong>20</strong> 85,580 116,660 131,600<br />

(10°F ∆T w<br />

) Sensible 65,3<strong>20</strong> 85,580 116,660 131,600<br />

GPM/(Ft.) 13.2 / (3.1) 17.6 / (5.1) 24.0 / (0.5) 27.0 / (0.7)<br />

Low Flow <strong>To</strong>tal 57,300 75,100 86,740 94,900<br />

(12°F ∆T w<br />

) Sensible 57,300 75,100 86,740 94,900<br />

GPM/(Ft.) 9.6 / (1.5) 12.8 / (2.8) 15.0 / (0.2) 16.4 / (0.2)<br />

72°FDB/60°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 59,9<strong>20</strong> 78,640 112,5<strong>20</strong> 126,340<br />

(8°F ∆T w<br />

) Sensible 59,9<strong>20</strong> 78,640 112,5<strong>20</strong> 126,340<br />

GPM/(Ft.) 15.2 / (4.0) <strong>20</strong>.0 / (6.6) 29.0 / (0.8) 32.4 / (1.0)<br />

Med Flow <strong>To</strong>tal 52,360 68,5<strong>20</strong> 81,400 92,3<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 52,360 68,5<strong>20</strong> 81,400 92,3<strong>20</strong><br />

GPM/(Ft.) 10.8 / (1.9) 14.0 / (3.4) 17.0 / 0.2) 19.2 / (0.3)<br />

Low Flow <strong>To</strong>tal 43,480 56,980 68,460 72,600<br />

(12°F ∆T w<br />

) Sensible 43,480 56,980 68,460 72,600<br />

GPM/(Ft.) 7.6 / (0.8) 9.6 / (1.5) 12.0 / (0.1) 12.8 / (0.1)<br />

70°FDB/58.5°FWB, 50% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 51,660 67,6<strong>20</strong> 90,600 102,400<br />

(8°F ∆T w<br />

) Sensible 51,660 67,6<strong>20</strong> 90,600 102,400<br />

GPM/(Ft.) 13.2 / (3.1) 17.2 / (5.0) 23.4 / (0.5) 26.4 / (0.7)<br />

Med Flow <strong>To</strong>tal 43,4<strong>20</strong> 56,860 66,1<strong>20</strong> 70,1<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 43,4<strong>20</strong> 56,860 66,1<strong>20</strong> 70,1<strong>20</strong><br />

GPM/(Ft.) 8.8 / (1.2) 11.6 / (2.3) 14.0 / (0.2) 14.8 / (0.2)<br />

Low Flow <strong>To</strong>tal 35,660 44,<strong>20</strong>0 56,580 59,760<br />

(12°F ∆T w<br />

) Sensible 35,660 44,<strong>20</strong>0 56,580 59,760<br />

GPM/(Ft.) 6.0 / (0.6) 7.6 / (0.8) 10.0 / (0.1) 10.6 / (0.1)<br />

Net Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil @ 45% RH<br />

75°FDB/61°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 72,040 94,540 142,960 160,160<br />

(8°F ∆T w<br />

) Sensible 72,040 94,540 142,960 160,160<br />

GPM/(Ft.) 18.4 / (5.6) 24.0 / (9.2) 36.4 / (1.3) 40.6 / (1.6)<br />

Med Flow <strong>To</strong>tal 65,100 85,360 116,180 131,060<br />

(10°F ∆T w<br />

) Sensible 65,100 85,360 116,180 131,060<br />

GPM/(Ft.) 13.2 / (3.1) 17.2 / (5.1) 23.8 / (0.5) 26.8 / (0.7)<br />

Low Flow <strong>To</strong>tal 57,100 74,860 86,480 94,3<strong>20</strong><br />

(12°F ∆T w<br />

) Sensible 57,100 74,860 86,480 94,3<strong>20</strong><br />

GPM/(Ft.) 9.6 / (1.5) 12.8 / (2.8) 15.0 / (0.2) 16.4 / (0.2)<br />

72°FDB/58.5°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 59,780 78,440 112,140 125,900<br />

(8°F ∆T w<br />

) Sensible 59,780 78,440 112,140 125,900<br />

GPM/(Ft.) 15.2 / (4.0) <strong>20</strong>.0 / (6.6) 28.8 / (0.8) 32.2 / (1.0)<br />

Med Flow <strong>To</strong>tal 52,<strong>20</strong>0 68,3<strong>20</strong> 80,960 91,8<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 52,<strong>20</strong>0 68,3<strong>20</strong> 80,960 91,8<strong>20</strong><br />

GPM/(Ft.) 10.8/ (1.9) 14.0 / (3.4) 16.8 / (0.2) 19.0 / (0.3)<br />

Low Flow <strong>To</strong>tal 43,300 56,760 68,240 72,380<br />

(12°F ∆T w<br />

) Sensible 43,300 56,760 68,240 72,380<br />

GPM/(Ft.) 7.2 / (0.8) 9.6 / (1.5) 12.0 / (0.1) 12.6 / (0.1)<br />

Performance Data - Chilled Water Systems @ 50°F EWT<br />

70°FDB/57°FWB, 45% RH MCS-084-C MCS-1<strong>20</strong>-C MCS-192-C MCS-240-C<br />

High Flow <strong>To</strong>tal 51,5<strong>20</strong> 67,460 90,2<strong>20</strong> 102,000<br />

(8°F ∆T w<br />

) Sensible 51,5<strong>20</strong> 67,460 90,2<strong>20</strong> 102,000<br />

GPM/(Ft.) 13.2 / (3.0) 17.2 / (5.0) 23.4 / (0.5) 26.4 / (0.7)<br />

Med Flow <strong>To</strong>tal 43,280 56,660 65,9<strong>20</strong> 69,9<strong>20</strong><br />

(10°F ∆T w<br />

) Sensible 43,280 56,660 65,9<strong>20</strong> 69,9<strong>20</strong><br />

GPM/(Ft.) 8.8 / (1.2) 11.6 / (2.3) 14.0 / (0.2) 14.8 / (0.2)<br />

Low Flow <strong>To</strong>tal 35,560 44,000 56,400 59,560<br />

(12°F ∆T w<br />

) Sensible 35,560 44,000 56,400 59,560<br />

GPM/(Ft.) 6.0 / (0.5) 7.6 / (0.8) 10.0 / (0.1) 10.6 / (0.1)<br />

(Note:<br />

The above Net Cooling capacities include standard motor heat @ standard CFM / e.s.p. as shown on page 4-8, Evaporator Blower/Motor.)<br />

4-10


Electrical Data - "ModulAiR" DX Compressorized Systems<br />

Electrical Data - "ModulAiR" DX Compressorized Systems<br />

MODEL<br />

MCS-084-DAR, DW & DG<br />

(7 <strong>To</strong>n, Single Pt. Power)<br />

DAR<br />

COOLING with<br />

FLA (OEM rated)<br />

DW<br />

DG<br />

MCA<br />

MFS<br />

MCS-1<strong>20</strong>-DAR, DW & DG<br />

(10 <strong>To</strong>n, Single Pt. Power)<br />

DAR<br />

FLA (OEM rated)<br />

DW<br />

Systems<br />

with<br />

MCA<br />

MFS<br />

Remote <strong>Air</strong> Cooled Condensers<br />

DG<br />

10<br />

Kw<br />

ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />

MCS-192-DAR, DW & DG<br />

(16 <strong>To</strong>n, Single Pt. Power)<br />

DAR<br />

FLA (OEM rated)<br />

DW<br />

DG<br />

10<br />

Kw<br />

Electric Reheat and/or Heat<br />

MCA<br />

MFS<br />

MCS-240-DAR, DW & DG<br />

(<strong>20</strong> <strong>To</strong>n Single Pt. Power)<br />

DAR<br />

FLA (OEM rated)<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

27.<br />

3 25.<br />

5 27.<br />

9 37.<br />

7 40<br />

32.<br />

5 30.<br />

1 33.<br />

3 43.<br />

5 50<br />

54.<br />

2 50.<br />

8 55.<br />

2 70.<br />

0 80<br />

61.<br />

2 57.<br />

0 62.<br />

6 76.<br />

3 90<br />

575/3/60<br />

21.<br />

9 <strong>20</strong>.<br />

5 22.<br />

4 29.<br />

9 30<br />

26.<br />

0 24.<br />

1 26.<br />

7 33.<br />

5 35<br />

43.<br />

9 40.<br />

9 44.<br />

7 53.<br />

8 60<br />

48.<br />

7 44.<br />

9 49.<br />

9 57.<br />

8 60<br />

COOLING and<br />

10<br />

Kw<br />

ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

27.<br />

3 25.<br />

5 27.<br />

9 37.<br />

7 40<br />

32.<br />

5 30.<br />

1 33.<br />

3 43.<br />

5 50<br />

54.<br />

2 50.<br />

8 55.<br />

2 70.<br />

0 80<br />

61.<br />

2 57.<br />

0 62.<br />

6 76.<br />

3 90<br />

575/3/60<br />

21.<br />

9 <strong>20</strong>.<br />

5 22.<br />

4 29.<br />

9 30<br />

26.<br />

0 24.<br />

1 26.<br />

7 33.<br />

5 35<br />

43.<br />

9 40.<br />

9 44.<br />

7 53.<br />

8 60<br />

48.<br />

7 44.<br />

9 49.<br />

9 57.<br />

8 60<br />

COOLING and<br />

10<br />

Kw<br />

ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

16.<br />

1 16.<br />

1 16.<br />

1 22.<br />

0 30<br />

19.<br />

9 17.<br />

9 <strong>20</strong>.<br />

7 27.<br />

8 35<br />

41.<br />

6 38.<br />

2 42.<br />

6 54.<br />

3 70<br />

48.<br />

6 44.<br />

4 50.<br />

0 60.<br />

6 70<br />

575/3/60<br />

13.<br />

0 13.<br />

0 13.<br />

0 17.<br />

3 <strong>20</strong><br />

16.<br />

0 14.<br />

4 16.<br />

6 21.<br />

0 25<br />

33.<br />

8 30.<br />

8 34.<br />

7 41.<br />

2 50<br />

38.<br />

6 34.<br />

8 39.<br />

8 45.<br />

3 50<br />

COOLING with<br />

Systems<br />

with Optional<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />

<strong>20</strong><br />

Kw<br />

Electric Reheat and/or Heat<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

39.<br />

9 25.<br />

5 27.<br />

9 53.<br />

4 60<br />

45.<br />

1 30.<br />

1 33.<br />

3 59.<br />

2 60<br />

66.<br />

8 50.<br />

8 55.<br />

2 85.<br />

7 90<br />

73.<br />

8 57.<br />

0 62.<br />

6 92.<br />

0 100<br />

575/3/60<br />

32.<br />

0 <strong>20</strong>.<br />

5 22.<br />

4 42.<br />

5 45<br />

36.<br />

1 24.<br />

1 26.<br />

7 46.<br />

1 50<br />

53.<br />

9 40.<br />

9 44.<br />

7 66.<br />

4 70<br />

58.<br />

7 44.<br />

9 49.<br />

9 70.<br />

4 80<br />

COOLING and<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

39.<br />

9 25.<br />

5 27.<br />

9 53.<br />

4 60<br />

45.<br />

1 30.<br />

1 33.<br />

3 59.<br />

2 60<br />

66.<br />

8 50.<br />

8 55.<br />

2 85.<br />

7 90<br />

73.<br />

8 57.<br />

0 62.<br />

6 92.<br />

0 100<br />

575/3/60<br />

32.<br />

0 <strong>20</strong>.<br />

5 22.<br />

4 42.<br />

5 45<br />

36.<br />

1 24.<br />

1 26.<br />

7 46.<br />

1 50<br />

53.<br />

9 40.<br />

9 44.<br />

7 66.<br />

4 70<br />

58.<br />

7 44.<br />

9 49.<br />

9 70.<br />

4 80<br />

COOLING and<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

17.<br />

1 15.<br />

6 17.<br />

5 22.<br />

5 25<br />

21.<br />

2 19.<br />

3 21.<br />

8 26.<br />

2 30<br />

39.<br />

0 36.<br />

0 39.<br />

9 46.<br />

4 60<br />

43.<br />

8 40.<br />

0 45.<br />

0 50.<br />

5 60<br />

575/3/60<br />

23.<br />

0 13.<br />

0 13.<br />

0 28.<br />

8 30<br />

24.<br />

4 14.<br />

4 16.<br />

6 30.<br />

5 35<br />

34.<br />

3 30.<br />

8 34.<br />

7 42.<br />

9 50<br />

38.<br />

6 34.<br />

8 39.<br />

8 45.<br />

3 50<br />

Systems<br />

COOLING and HUMIDIFIER ONLY, (No Electric RH/HT)<br />

W<br />

ithout<br />

Electric Reheat and/or Heat<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

21.<br />

1 19.<br />

3 21.<br />

7 28.<br />

4 35<br />

26.<br />

3 23.<br />

9 27.<br />

1 34.<br />

2 40<br />

48.<br />

0 44.<br />

6 49.<br />

0 60.<br />

7 70<br />

55.<br />

0 50.<br />

8 56.<br />

4 67.<br />

0 80<br />

575/3/60<br />

17.<br />

1 15.<br />

6 17.<br />

5 22.<br />

5 25<br />

21.<br />

2 19.<br />

3 21.<br />

8 26.<br />

2 30<br />

39.<br />

0 36.<br />

0 39.<br />

9 46.<br />

4 50<br />

43.<br />

8 40.<br />

0 45.<br />

0 50.<br />

5 60<br />

COOLING ONLY, (No Electric RH/HT or Humidifier)<br />

<strong>20</strong>8/3/60<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

- - - - - -<br />

460/3/60<br />

14.<br />

7 12.<br />

9 15.<br />

3 22.<br />

0 30<br />

19.<br />

9 17.<br />

5 <strong>20</strong>.<br />

7 27.<br />

8 40<br />

41.<br />

6 38.<br />

2 42.<br />

6 54.<br />

3 70<br />

48.<br />

6 44.<br />

4 50.<br />

0 60.<br />

6 70<br />

575/3/60<br />

11.<br />

9 10.<br />

4 12.<br />

3 17.<br />

3 <strong>20</strong><br />

16.<br />

0 14.<br />

1 16.<br />

6 21.<br />

0 25<br />

33.<br />

8 30.<br />

8 34.<br />

7 41.<br />

2 50<br />

38.<br />

6 34.<br />

8 39.<br />

8 45.<br />

3 50<br />

OUTDOOR<br />

<strong>20</strong>8/3/60<br />

460/3/60<br />

575/3/60<br />

MODEL<br />

FLA<br />

MCA<br />

MFS<br />

HES-1<strong>20</strong>-DLSA or DLFA 5.<br />

2 5.<br />

9 15<br />

2.<br />

6 2.<br />

9 15<br />

1.<br />

9 2.<br />

4 15<br />

HES-168-DLSA or DLFA 5.<br />

2 5.<br />

9 15<br />

2.<br />

6 2.<br />

9 15<br />

1.<br />

9 2.<br />

4 15<br />

HES-192-DLSA or DLFA 5.<br />

2 5.<br />

9 15<br />

2.<br />

6 2.<br />

9 15<br />

1.<br />

9 2.<br />

4 15<br />

HES-339-DLSA or DLFA 14.<br />

0 15.<br />

8 <strong>20</strong><br />

7.<br />

0 8.<br />

8 15<br />

5.<br />

6 7.<br />

0 15<br />

HES-399-DLSA or DLFA 14.<br />

0 15.<br />

8 <strong>20</strong><br />

7.<br />

0 8.<br />

8 15<br />

5.<br />

6 7.<br />

0 15<br />

HES-525-DLSA or DLFA 14.<br />

0 15.<br />

8 <strong>20</strong><br />

7.<br />

0 8.<br />

8 15<br />

5.<br />

6 7.<br />

0 15<br />

FLA<br />

MCA<br />

MFS<br />

FLA<br />

MCA<br />

MFS<br />

DW<br />

DG<br />

Table Legend:<br />

MCA<br />

MFS<br />

- - - - - Consult Factory for<br />

<strong>20</strong>8/3/60 Applications.<br />

FLA<br />

MCA<br />

MFS<br />

FLA = Full Load Amps<br />

MCA = Minimum Circuit Amps<br />

(wire size amps)<br />

MFS = Maximum Fuse Size<br />

5-1


Electrical Data - "ModulAiR" Chilled Water Systems<br />

MODEL<br />

Example:<br />

MCS-084-C<br />

(7 <strong>To</strong>n, Single Pt.)<br />

FLA<br />

COOLING with<br />

MCA<br />

MFS<br />

Systems<br />

with<br />

MCS-1<strong>20</strong>-C<br />

(10 <strong>To</strong>n, Single Pt.)<br />

FLA<br />

MCA<br />

MFS<br />

MCS-192-C<br />

(16 <strong>To</strong>n, Single Pt.)<br />

Suppose an application calls for a nominal <strong>20</strong> <strong>To</strong>n ModulAiR air cooled<br />

split system with the following features:<br />

MCS-240-DAR-()<br />

HES-168-DLSA<br />

- 460/3/60 Main Power Supply (both evap and cond)<br />

- 10 Kw Electric Reheat/Heat, (Standard)<br />

- 15 lb/hr Steam Humidifier, (Standard)<br />

Solution:<br />

<strong>From</strong> DX Compressorized Electrical Data table shown on page 5-1 for<br />

model MCS-240-DAR incorporating COOLING with ELECTRIC<br />

REHEAT/HEAT and HUMIDIFIER:<br />

FLA<br />

MCA<br />

MFS<br />

MCS-240-C<br />

(<strong>20</strong> <strong>To</strong>n, Single Pt.)<br />

FLA<br />

10<br />

Kw<br />

Electric Reheat and/or Heat<br />

10<br />

Kw<br />

ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />

<strong>20</strong>8/3/60<br />

45.<br />

9 57.<br />

3 60<br />

49.<br />

5 61.<br />

8 70<br />

72.<br />

7 90.<br />

8 100<br />

72.<br />

7 90.<br />

8 100<br />

460/3/60<br />

22.<br />

5 28.<br />

1 30<br />

24.<br />

3 30.<br />

3 35<br />

35.<br />

9 44.<br />

8 50<br />

35.<br />

9 44.<br />

8 50<br />

575/3/60<br />

18.<br />

2 22.<br />

7 25<br />

19.<br />

6 24.<br />

5 25<br />

29.<br />

0 36.<br />

2 45<br />

29.<br />

0 36.<br />

2 45<br />

COOLING and<br />

10<br />

Kw<br />

ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />

<strong>20</strong>8/3/60<br />

31.<br />

7 39.<br />

6 40<br />

35.<br />

3 44.<br />

1 45<br />

58.<br />

5 73.<br />

1 90<br />

58.<br />

5 73.<br />

1 90<br />

460/3/60<br />

16.<br />

1 <strong>20</strong>.<br />

1 25<br />

17.<br />

9 22.<br />

3 25<br />

29.<br />

5 36.<br />

8 50<br />

29.<br />

5 36.<br />

8 50<br />

575/3/60<br />

13.<br />

0 16.<br />

2 <strong>20</strong><br />

14.<br />

4 18.<br />

0 <strong>20</strong><br />

23.<br />

8 29.<br />

7 40<br />

23.<br />

8 29.<br />

7 40<br />

COOLING and<br />

10<br />

Kw<br />

ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />

<strong>20</strong>8/3/60<br />

31.<br />

7 39.<br />

6 40<br />

35.<br />

3 44.<br />

1 45<br />

58.<br />

5 73.<br />

1 90<br />

58.<br />

5 73.<br />

1 90<br />

460/3/60<br />

16.<br />

1 <strong>20</strong>.<br />

1 25<br />

17.<br />

9 22.<br />

3 25<br />

29.<br />

5 36.<br />

8 50<br />

29.<br />

5 36.<br />

8 50<br />

575/3/60<br />

13.<br />

0 16.<br />

2 <strong>20</strong><br />

14.<br />

4 18.<br />

0 <strong>20</strong><br />

23.<br />

8 29.<br />

7 40<br />

23.<br />

8 29.<br />

7 40<br />

COOLING with<br />

Systems<br />

with Optional<br />

<strong>20</strong><br />

Kw<br />

Electric Reheat and/or Heat<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC REHEAT/HEAT and HUMIDIFIE R<br />

<strong>20</strong>8/3/60<br />

71.<br />

0 88.<br />

8 90<br />

74.<br />

6 93.<br />

3 100<br />

97.<br />

8 122.<br />

3 125<br />

97.<br />

8 122.<br />

3 125<br />

460/3/60<br />

35.<br />

1 43.<br />

8 45<br />

36.<br />

9 46.<br />

1 50<br />

48.<br />

5 60.<br />

6 70<br />

48.<br />

5 60.<br />

6 70<br />

575/3/60<br />

28.<br />

2 35.<br />

3 40<br />

29.<br />

6 37.<br />

0 40<br />

39.<br />

0 48.<br />

8 50<br />

39.<br />

0 48.<br />

8 50<br />

COOLING and<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC REHEAT/HEAT ONLY, (No Humidifier )<br />

<strong>20</strong>8/3/60<br />

56.<br />

8 71.<br />

0 80<br />

60.<br />

4 75.<br />

5 80<br />

83.<br />

6 104.<br />

5 125<br />

83.<br />

6 104.<br />

5 125<br />

460/3/60<br />

28.<br />

7 35.<br />

8 40<br />

30.<br />

5 38.<br />

1 40<br />

42.<br />

1 52.<br />

6 60<br />

42.<br />

1 52.<br />

6 60<br />

575/3/60<br />

23.<br />

0 28.<br />

8 30<br />

24.<br />

4 30.<br />

5 35<br />

33.<br />

8 42.<br />

3 50<br />

33.<br />

8 42.<br />

3 50<br />

COOLING and<br />

MCA<br />

<strong>20</strong><br />

Kw<br />

ELECTRIC HEAT ONLY, (No Electric Reheat or Humidifier )<br />

<strong>20</strong>8/3/60<br />

56.<br />

8 71.<br />

0 80<br />

60.<br />

4 75.<br />

5 80<br />

83.<br />

6 104.<br />

5 125<br />

83.<br />

6 104.<br />

5 125<br />

460/3/60<br />

28.<br />

7 35.<br />

8 40<br />

30.<br />

5 38.<br />

1 40<br />

42.<br />

1 52.<br />

6 60<br />

42.<br />

1 52.<br />

6 60<br />

575/3/60<br />

23.<br />

0 28.<br />

8 30<br />

24.<br />

4 30.<br />

5 35<br />

33.<br />

8 42.<br />

3 50<br />

33.<br />

8 42.<br />

3 50<br />

Systems<br />

W<br />

ithout<br />

COOLING and HUMIDIFIER ONLY, (No Electric RH/HT)<br />

Electric Reheat and/or Heat<br />

<strong>20</strong>8/3/60<br />

<strong>20</strong>.<br />

7 25.<br />

9 30<br />

24.<br />

3 30.<br />

4 35<br />

47.<br />

5 59.<br />

4 80<br />

47.<br />

5 59.<br />

4 80<br />

460/3/60<br />

9.<br />

9 12.<br />

4 15<br />

11.<br />

7 14.<br />

6 <strong>20</strong><br />

23.<br />

3 29.<br />

1 40<br />

23.<br />

3 29.<br />

1 40<br />

575/3/60<br />

8.<br />

1 10.<br />

1 15<br />

9.<br />

5 11.<br />

9 <strong>20</strong><br />

18.<br />

9 23.<br />

6 35<br />

18.<br />

9 23.<br />

6 35<br />

COOLING ONLY, (No Electric RH/HT or Humidifier)<br />

<strong>20</strong>8/3/60<br />

6.<br />

5 8.<br />

1 15<br />

10.<br />

1 12.<br />

6 <strong>20</strong><br />

33.<br />

3 41.<br />

6 70<br />

33.<br />

3 41.<br />

6 70<br />

460/3/60<br />

3.<br />

5 4.<br />

4 15<br />

5.<br />

3 6.<br />

6 15<br />

16.<br />

9 21.<br />

1 35<br />

16.<br />

9 21.<br />

1 35<br />

575/3/60<br />

2.<br />

9 3.<br />

6 15<br />

4.<br />

3 5.<br />

4 15<br />

13.<br />

7 17.<br />

1 30<br />

13.<br />

7 17.<br />

1 30<br />

MFS<br />

MCS-240-DAR @ 460/3/60 with above options:<br />

61.2 FLA / 76.3 MCA / 90 MFS<br />

HES-168-DLSA @ 460/3/60 with above options:<br />

2.6 FLA / 2.9 MCA / 15 MFS<br />

Table Legend:<br />

FLA<br />

MCA<br />

MFS<br />

FLA = Full Load Amps<br />

MCA = Minimum Circuit Amps (wire size amps)<br />

MFS = Maximum Fuse Size<br />

Electrical Data - "ModulAiR" Chilled Water Systems<br />

5-2


7 to 10 <strong>To</strong>n MCS - "Down-Flow" <strong>Air</strong> Pattern Systems<br />

Dimensional Data - 7 to 10 <strong>To</strong>ns ("Down-Flow" <strong>Air</strong> Pattern Systems)<br />

(MC-01) MCS-084/1<strong>20</strong>-DAR, DW, DG & C-D<br />

"Down-Flow" Modular Vertical A/C<br />

("Free-Return" or "Ducted-Return")<br />

Filter<br />

Access<br />

29.0"<br />

2.62"<br />

(Filler)<br />

Optional 1.0"<br />

Duct Flange<br />

Connection<br />

62.12"<br />

(Overall) 29.0"<br />

(Base)<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Into Raised Floor<br />

FRONT / RIGHT<br />

60.62"<br />

Filter Box<br />

(Field Installed)<br />

1.0"<br />

76.0"<br />

29.0"<br />

(Base)<br />

29.75"<br />

(Overall)<br />

Adjustable Floor Stand: (Optional)<br />

24.0" High<br />

Stands Only<br />

29.0"<br />

8.78"<br />

28.63"<br />

7.62"<br />

19.8"<br />

60.62"<br />

6.0"<br />

21.4"<br />

82.0"<br />

A<br />

83.0"<br />

w/ Optional<br />

Duct<br />

Connection<br />

BLOWER DIMENSIONAL DATA<br />

M ODEL<br />

“ L”<br />

“M”<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

M CL<br />

REA R / LEFT<br />

Dimensional<br />

Data - Floor Stand Heights<br />

Floor Stand<br />

Nominal Height<br />

Piping<br />

Connections<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Into Raised Floor<br />

"A" Dimension<br />

Adjustable Height<br />

Minimum<br />

2.0"<br />

Utility<br />

Connections<br />

Maximum<br />

Turning Vane<br />

Availability<br />

4 .0" ( Upflow Units Only)<br />

3 .5"<br />

4.5"<br />

Not Availabl e<br />

6 .0"<br />

5 .0"<br />

7.0"<br />

Not Availabl e<br />

12.0"<br />

11.0"<br />

15.0"<br />

Optional<br />

15.0"<br />

14.0"<br />

18.0"<br />

Optional<br />

18.0"<br />

17.0"<br />

21.0"<br />

Optional<br />

24.0"<br />

23.0"<br />

26.0"<br />

Optional<br />

L<br />

Based on<br />

Std CFM @<br />

M CS-084 & 1<strong>20</strong>-( )-D 11.38"<br />

13.12"<br />

0.5" e.s. p<br />

28.63"<br />

24.0" High<br />

Stands Only<br />

6-1


7 to 10 <strong>To</strong>n MCS - "Up-Flow" <strong>Air</strong> Pattern Systems<br />

(MC-02) MCS-084/1<strong>20</strong>-DAR, DW, DG & C-U<br />

"Up-Flow" Modular Vertical A/C<br />

(as "Ducted or with Opt. "2 or 3-way Plenum Box")<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

18.5"<br />

29.0"<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

29.0"<br />

60.62"<br />

2.62"<br />

(Filler)<br />

62.12"<br />

(Overall) 29.0"<br />

(Base)<br />

60.62"<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

FRONT / RIGHT<br />

C M L<br />

2 or 3-Way Plenum<br />

Discharge Box - field<br />

installed (Optional)<br />

29.0"<br />

(Base)<br />

29.75"<br />

(Overall)<br />

Adjustable Floor Stand: (Optional)<br />

24.0" High<br />

Stands Only<br />

29.0"<br />

28.63"<br />

60.62"<br />

L<br />

Standard 1.0"<br />

Duct Flange<br />

Connection<br />

1.0"<br />

2.0"<br />

76.0"<br />

A<br />

77.0"<br />

w/ Standard<br />

Duct<br />

Connection<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

BLOWER DIMENSIONAL DATA<br />

M ODEL<br />

“ L”<br />

“M”<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Dimensional<br />

Data -<br />

Floor Stand<br />

Nominal Height<br />

REA R / LEFT<br />

Floor Stand Heights<br />

"A" Dimension<br />

Adjustable Height<br />

Minimum<br />

Piping<br />

Connections<br />

Maximum<br />

4 .0" ( Upflow Units Only)<br />

3 .5"<br />

4.5"<br />

6 .0"<br />

5 .0"<br />

7.0"<br />

12.0"<br />

11.0"<br />

15.0"<br />

15.0"<br />

14.0"<br />

18.0"<br />

18.0"<br />

17.0"<br />

21.0"<br />

24.0"<br />

23.0"<br />

26.0"<br />

Based on<br />

Std CFM @<br />

M CS-084 & 1<strong>20</strong>-( )-U 11.38"<br />

13.12"<br />

0.5" e.s. p<br />

Utility<br />

Connections<br />

Dimensional Data - 7 to 10 <strong>To</strong>ns ("Up-Flow" <strong>Air</strong> Pattern Systems)<br />

28.63"<br />

24.0" High<br />

Stands Only<br />

6-2


16 to <strong>20</strong> <strong>To</strong>n MCS - "Down-Flow" <strong>Air</strong> Pattern Systems<br />

Dimensional Data - 16 to <strong>20</strong> <strong>To</strong>ns ("Down-Flow" <strong>Air</strong> Pattern Systems)<br />

(MC-03) MCS-192/240-DAR, DW, DG & C-D<br />

Filter<br />

Access<br />

"Down-Flow" Modular Vertical A/C<br />

("Free-Return" or "Ducted-Return")<br />

34.0"<br />

Adjustable Floor Stand: (Optional)<br />

24.0" High<br />

Stands Only<br />

2.62"<br />

(Filler)<br />

79.12"<br />

(Overall) 37.5"<br />

(Base)<br />

32.88"<br />

8.78"<br />

Optional 1.0"<br />

Duct Flange<br />

Connection<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Into Raised Floor<br />

37.14"<br />

FRONT / RIGHT<br />

7.5"<br />

19.8"<br />

79.12"<br />

Filter Box<br />

(Field Installed)<br />

76.0"<br />

32.88"<br />

(Base)<br />

34.0"<br />

(Overall)<br />

77.63"<br />

6.0"<br />

19.8"<br />

1.0"<br />

10.2"<br />

82.0"<br />

83.0"<br />

w/ Optional<br />

Duct<br />

Connection<br />

A<br />

BLOWER DIMENSIONAL DATA<br />

M ODEL<br />

“ L”<br />

“M”<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Dimensional<br />

Data - Floor Stand Heights<br />

Floor Stand<br />

Nominal Height<br />

M<br />

Piping<br />

Connections<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

Into Raised Floor<br />

REAR / LEFT<br />

"A" Dimension<br />

Adjustable Height<br />

Minimum<br />

9.6"<br />

Maximum<br />

Based on<br />

Std CFM @<br />

M CS-192 & 240-( )-D 13.44"<br />

15.62"<br />

0.5" e.s. p<br />

1.75"<br />

Utility<br />

Connections<br />

Turning Vane<br />

Availability<br />

4 .0" ( Upflow Units Only)<br />

3 .5"<br />

4.5"<br />

Not Availabl e<br />

6 .0"<br />

5 .0"<br />

7.0"<br />

Not Availabl e<br />

12.0"<br />

11.0"<br />

15.0"<br />

Optional<br />

15.0"<br />

14.0"<br />

18.0"<br />

Optional<br />

18.0"<br />

17.0"<br />

21.0"<br />

Optional<br />

24.0"<br />

23.0"<br />

26.0"<br />

Optional<br />

L<br />

37.14"<br />

24.0" High<br />

Stands Only<br />

6-3


16 to <strong>20</strong> <strong>To</strong>n MCS - "Up-Flow" <strong>Air</strong> Pattern Systems<br />

(MC-04) MCS-192/240-DAR, DW, DG & C-U<br />

"Up-Flow" Modular Vertical A/C<br />

(as "Ducted or with Opt. "2 or 3-way Plenum Box")<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

Adjustable Floor Stand: (Optional)<br />

24.0" High<br />

Stands Only<br />

18.5"<br />

34.0"<br />

32.88"<br />

Evaporator<br />

<strong>Air</strong> Inlet<br />

2.62"<br />

(Filler)<br />

79.12"<br />

(Overall) 37.5"<br />

(Base)<br />

32.88"<br />

77.62"<br />

37.14"<br />

79.12"<br />

Evaporator<br />

<strong>Air</strong> Outlet<br />

FRONT / RIGHT<br />

2 or 3-Way Plenum<br />

Discharge Box - field<br />

installed (Optional)<br />

M<br />

L<br />

8.5"<br />

1.75"<br />

1.0"<br />

76.0"<br />

32.88"<br />

(Base)<br />

34.0"<br />

(Overall)<br />

77.63"<br />

Standard 1.0"<br />

Duct Flange<br />

Connection<br />

77.0"<br />

w/ Standard<br />

Duct<br />

Connection<br />

A<br />

BLOWER DIMENSIONAL DATA<br />

M ODEL<br />

“ L”<br />

“M”<br />

Piping<br />

Connections<br />

Dimensional<br />

Data -<br />

Floor Stand<br />

Nominal Height<br />

REAR / LEFT<br />

Floor Stand Heights<br />

"A" Dimension<br />

Adjustable Height<br />

Minimum<br />

Maximum<br />

4 .0" ( Upflow Units Only)<br />

3 .5"<br />

4.5"<br />

6 .0"<br />

5 .0"<br />

7.0"<br />

Based on<br />

Std CFM @<br />

M CS-192 & 240-( )-U 13.44"<br />

15.62"<br />

0.5" e.s. p<br />

12.0"<br />

11.0"<br />

15.0"<br />

15.0"<br />

14.0"<br />

18.0"<br />

18.0"<br />

17.0"<br />

21.0"<br />

24.0"<br />

23.0"<br />

26.0"<br />

Utility<br />

Connections<br />

Dimensional Data - 16 to <strong>20</strong> <strong>To</strong>ns ("Up-Flow" <strong>Air</strong> Pattern Systems)<br />

37.14"<br />

24.0" High<br />

Stands Only<br />

6-4


<strong>Air</strong> Cooled - Remote Outdoor DX Condensers<br />

Dimensional Data - <strong>Air</strong> Cooled (Remote Outdoor DX Condensers)<br />

(MC-05) HES-1<strong>20</strong> thru 525-DL()A<br />

Outdoor - Propeller Fan<br />

Remote <strong>Air</strong> Cooled Condenser<br />

A<br />

B<br />

D<br />

C<br />

DIMENSIONAL DATA<br />

M ODEL<br />

“ A”<br />

“ B”<br />

“ C”<br />

“ D”<br />

Approx. Wt.<br />

H ES-1<strong>20</strong>-DLSA & DLFA 69.75"<br />

43.0"<br />

41.0"<br />

60.0"<br />

450 lbs.<br />

H ES-168-DLSA & DLFA 89.75"<br />

43.0"<br />

41.0"<br />

80.0"<br />

510 lbs.<br />

H ES-192-DLSA & DLFA 89.75"<br />

43.0"<br />

41.0"<br />

80.0"<br />

530 lbs.<br />

H ES-339-DLSA & DLFA 1<strong>20</strong>.5"<br />

45.5"<br />

50.0"<br />

114.0"<br />

730 lbs.<br />

H ES-399-DLSA & DLFA 1<strong>20</strong>.5"<br />

45.5"<br />

50.0"<br />

114.0"<br />

770 lbs.<br />

H ES-525-DLSA & DLFA 1<strong>20</strong>.5"<br />

45.5"<br />

50.0"<br />

114.0"<br />

880 lbs.<br />

6-5


1572 Tilco Drive, Frederick, Maryland 21704, USA Copyright 12/01 - Form L-01-F-140<br />

Phone: (301) 6<strong>20</strong>-<strong>20</strong>33, Facsimile: (301) 662-5487<br />

www.stulz-ats.com<br />

Specifications are subject<br />

to change without notice.