Unit shutdown outputs<br />
The unit shutdown outputs must:<br />
• Be allocated on safe modules (such as a SDO-0824 or SDOL-0424 module)<br />
• Have their fault reaction state set to Low.<br />
This guarantees that <strong>Safety</strong> <strong>Manager</strong> directs the process to its safe state if a<br />
fault occurs which affects this output.<br />
• Have set the power-up status of the unit shutdown output to ON.<br />
This allows a correct start-up of <strong>Safety</strong> <strong>Manager</strong> with activated unit relays.<br />
For optimal availability it is re<strong>com</strong>mended that unit shutdown outputs are<br />
allocated to redundant output modules.<br />
Process outputs (safety related)<br />
The process outputs must be allocated to a <strong>Safety</strong> <strong>Manager</strong> output module of the<br />
type:<br />
• SDO-0824 <strong>Safety</strong>-related digital output module<br />
(24 Vdc, 0.55 A, 8 channels)<br />
• SAO-0220m <strong>Safety</strong>-related analog output module<br />
(0(4)-20 mA, 2 channels)<br />
• SDO-04110 <strong>Safety</strong>-related digital output module<br />
(110 Vdc, 0.32 A, 4 channels)<br />
• SDO-0448 <strong>Safety</strong>-related digital output module<br />
(48 Vdc, 0.75 A, 4 channels)<br />
• SDO-0424 <strong>Safety</strong>-related digital output module<br />
(24 Vdc, 2 A, 4 channels)<br />
• SDOL-0424 <strong>Safety</strong>-related loop-monitored digital output module<br />
(24 Vdc, 1 A, 4 channels)<br />
• SDOL-0448 <strong>Safety</strong>-related loop-monitored digital output module<br />
(48 Vdc, 0.5A, 4 channels<br />
To allow the programming of the response via the application, the fault reaction<br />
of these outputs must be set to Appl. This disables the automatic response of<br />
<strong>Safety</strong> <strong>Manager</strong> in case a fault occurs at safety-related output modules.<br />
Application programming<br />
To realize unit shutdown in the functional logic diagrams, all diagnostic inputs<br />
related to output modules of each process unit are connected to an AND gate.<br />
<strong>Safety</strong> <strong>Manager</strong> <strong>Safety</strong> <strong>Manual</strong> 39