3 – <strong>Safety</strong> <strong>Manager</strong> fault detection and response<br />

Analog input faults<br />

Analog input faults<br />

Related to<br />

analog input value<br />

loop power<br />

(SAI-1620m)<br />

Table 10 on page 28 provides an overview of faults that can be detected in<br />

relation to analog inputs and the response to these faults.<br />

Table 10 Controller response to analog input faults<br />

Diagnostic message<br />

reports<br />

below low transmitter<br />

alarm level per range<br />

above high transmitter<br />

alarm level all ranges<br />

External voltage<br />

monitoring fault<br />

Non redundant input Redundant input, Controller response<br />

Controller response * CP X (faulty input) CP Y (healthy input)<br />

none- continue for<br />

0-20mA, 0-10V<br />

bottom scale for<br />

4-20mA, 2-10V<br />

none- continue<br />

none- continue<br />

none- continue for 0-20mA, 0-10V<br />

bottom scale for 4-20mA, 2-10V<br />

none- continue<br />

none- continue<br />

channel module faulty apply FR state use values from<br />

CP **<br />

Y<br />

module module faulty apply FR state use values from<br />

Internal power down<br />

CP Y***<br />

<strong>com</strong>pare *** input <strong>com</strong>pare error apply FR state apply FR state<br />

none- continue<br />

none- continue<br />

* If the Controller is redundant, both CPs respond the same.<br />

** If values are not available via CP Y apply FR state to affected inputs.<br />

*** Occurs when detecting a deviation of >2% in the input values persists for more than 2 application cycles.<br />

Digital output faults<br />

Table 11 on page 28 provides an overview of faults that can be detected in<br />

relation to digital outputs and the response to these faults.<br />

Table 11 Controller response to digital output faults<br />

Digital output faults<br />

Related to<br />

digital output loop **<br />

(line monitored)<br />

default voting<br />

Diagnostic message<br />

reports<br />

Non redundant output<br />

Controller response *<br />

current detected Apply FR state apply FR state<br />

Redundant output, Controller response<br />

CP X (faulty output) CP Y (healthy output)<br />

28 Release 131, Issue 4.2