3 – <strong>Safety</strong> <strong>Manager</strong> fault detection and response<br />
Analog input faults<br />
Analog input faults<br />
Related to<br />
analog input value<br />
loop power<br />
(SAI-1620m)<br />
Table 10 on page 28 provides an overview of faults that can be detected in<br />
relation to analog inputs and the response to these faults.<br />
Table 10 Controller response to analog input faults<br />
Diagnostic message<br />
reports<br />
below low transmitter<br />
alarm level per range<br />
above high transmitter<br />
alarm level all ranges<br />
External voltage<br />
monitoring fault<br />
Non redundant input Redundant input, Controller response<br />
Controller response * CP X (faulty input) CP Y (healthy input)<br />
none- continue for<br />
0-20mA, 0-10V<br />
bottom scale for<br />
4-20mA, 2-10V<br />
none- continue<br />
none- continue<br />
none- continue for 0-20mA, 0-10V<br />
bottom scale for 4-20mA, 2-10V<br />
none- continue<br />
none- continue<br />
channel module faulty apply FR state use values from<br />
CP **<br />
Y<br />
module module faulty apply FR state use values from<br />
Internal power down<br />
CP Y***<br />
<strong>com</strong>pare *** input <strong>com</strong>pare error apply FR state apply FR state<br />
none- continue<br />
none- continue<br />
* If the Controller is redundant, both CPs respond the same.<br />
** If values are not available via CP Y apply FR state to affected inputs.<br />
*** Occurs when detecting a deviation of >2% in the input values persists for more than 2 application cycles.<br />
Digital output faults<br />
Table 11 on page 28 provides an overview of faults that can be detected in<br />
relation to digital outputs and the response to these faults.<br />
Table 11 Controller response to digital output faults<br />
Digital output faults<br />
Related to<br />
digital output loop **<br />
(line monitored)<br />
default voting<br />
Diagnostic message<br />
reports<br />
Non redundant output<br />
Controller response *<br />
current detected Apply FR state apply FR state<br />
Redundant output, Controller response<br />
CP X (faulty output) CP Y (healthy output)<br />
28 Release 131, Issue 4.2