Safety Manager Safety Manual - Tuv-fs.com
Safety Manager Safety Manual - Tuv-fs.com
Safety Manager Safety Manual - Tuv-fs.com
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SM Controller faults<br />
Table 7 Controller response to PSU faults<br />
PSU faults<br />
Non redundant Redundant Controller response<br />
related to diagnostics report includes<br />
Controller<br />
response<br />
CP X( faulty) CP Y (not faulty)<br />
Voltage monitoring spurious watchdog interrupt halt Controller halt CP none -continue<br />
module faulty PSU module<br />
Communication faults<br />
Note<br />
Please note that a fault in the <strong>com</strong>munication links may be caused by USI modules.<br />
<strong>com</strong>munication faults<br />
Related to<br />
broken link<br />
wrong protocol assigned<br />
time-out<br />
Table 9 on page 27 provides an overview of faults that can be detected in relation<br />
to <strong>com</strong>munication and the response to these faults.<br />
Table 8 Controller response to <strong>com</strong>munication faults<br />
Diagnostic message<br />
reports<br />
<strong>com</strong>munication<br />
fault<br />
Non redundant<br />
<strong>com</strong>munication or<br />
“shared CP”<br />
Controller<br />
response *<br />
apply FR state to<br />
COM & FSC inputs<br />
of that channel<br />
if channel belongs<br />
to active clock<br />
source, switch to<br />
other clock source<br />
too many data requests USI module faulty apply FR state to<br />
COM & FSC inputs<br />
of that USI<br />
data mismatch between<br />
inputs ****<br />
(SafeNet redundant)<br />
data mismatch between<br />
inputs****<br />
(redundant Experion or<br />
Modbus)<br />
Redundant <strong>com</strong>munication<br />
Controller response<br />
CP X(faulty)<br />
CP Y(not faulty<br />
continue<br />
<strong>com</strong>munication via<br />
healthy link **<br />
use values from<br />
CP Y for affected<br />
COM and FSC<br />
inputs ***<br />
<strong>com</strong>pare error n.a. apply FR state<br />
n.a.<br />
none -continue<br />
values received by CP2 prevail.<br />
<strong>Safety</strong> <strong>Manager</strong> <strong>Safety</strong> <strong>Manual</strong> 25