SM Controller faults<br />

Table 4 Controller response to QPP faults (continued)<br />

QPP faults<br />

Non redundant Redundant Controller response<br />

related to diagnostics report includes<br />

Controller<br />

response<br />

CP X( faulty) CP Y (not faulty)<br />

repair timer<br />

running none -continue none -continue<br />

(user configurable) expired halt Controller halt CP none -continue<br />

software corrupted halt Controller halt CP none -continue<br />

intervention<br />

QPP key switch to IDLE halt Controller halt CP none -continue<br />

position<br />

Spurious watchdog<br />

interrupt<br />

safe state initiated<br />

SD input de-energized<br />

halt Controller<br />

synchronization QPP n.a. halt CP none -continue<br />

system software<br />

halted CP does none -continue<br />

not start<br />

base timer halt CP none -continue<br />

IO <strong>com</strong>pare error<br />

apply FR state<br />

time sync<br />

(user configurable)<br />

source unavailable switch to other<br />

source<br />

switch to other source<br />

internal <strong>com</strong>munication n.a. halt CP none -continue<br />

USI faults<br />

Table 5 on page 24 provides an overview of detected faults in relation to the USI<br />

and the response to these faults.<br />

A fault in the USI also means that the <strong>com</strong>munication channels of that USI are<br />

down.<br />