Safety Manager Safety Manual - Tuv-fs.com
Safety Manager Safety Manual - Tuv-fs.com
Safety Manager Safety Manual - Tuv-fs.com
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3 – <strong>Safety</strong> <strong>Manager</strong> fault detection and response<br />
SM Controller faults<br />
Below topics provide an overview of detected Controller faults and the Controller<br />
response to these faults.<br />
QPP faults<br />
Table 4 on page 22 provides an overview of faults that the Controller detects<br />
related to the QPP and the response to these faults.<br />
Table 4 Controller response to QPP faults<br />
QPP faults<br />
Non redundant Redundant Controller response<br />
related to diagnostics report includes<br />
Controller<br />
response<br />
CP X( faulty) CP Y (not faulty)<br />
temperature monitoring high alarm or low alarm none -continue none -continue<br />
(set points user<br />
configurable)<br />
high-high alarm or<br />
low-low alarm<br />
1 sensor faulty and temp.<br />
more than 3 degrees from<br />
shutdown limits<br />
1 sensor faulty and temp.<br />
less than 3 degrees from<br />
shutdown limits<br />
halt Controller halt CP none -continue<br />
none -continue<br />
none -continue<br />
halt Controller halt CP none -continue<br />
Memory QPP memory halt Controller halt CP none -continue<br />
Execution<br />
execution time out of halt Controller halt CP none -continue<br />
range / failure<br />
error on logical sheet<br />
halt Controller<br />
Watchdog output shorted halt Controller halt CP none -continue<br />
de-energized watchdog<br />
line for redundant outputs<br />
halt Controller halt CP none -continue<br />
de-energized watchdog<br />
line for non-redundant<br />
outputs<br />
halt Controller<br />
de-energize non redundant outputs,<br />
continue operation on redundant<br />
outputs<br />
Watchdog faulty halt Controller halt CP none -continue<br />
Bus drivers<br />
Internal link<br />
QPP module<br />
secondary switch-off faulty halt Controller halt CP none -continue<br />
22 Release 131, Issue 4.2