3 – <strong>Safety</strong> <strong>Manager</strong> fault detection and response<br />

SM Controller faults<br />

Below topics provide an overview of detected Controller faults and the Controller<br />

response to these faults.<br />

QPP faults<br />

Table 4 on page 22 provides an overview of faults that the Controller detects<br />

related to the QPP and the response to these faults.<br />

Table 4 Controller response to QPP faults<br />

QPP faults<br />

Non redundant Redundant Controller response<br />

related to diagnostics report includes<br />

Controller<br />

response<br />

CP X( faulty) CP Y (not faulty)<br />

temperature monitoring high alarm or low alarm none -continue none -continue<br />

(set points user<br />

configurable)<br />

high-high alarm or<br />

low-low alarm<br />

1 sensor faulty and temp.<br />

more than 3 degrees from<br />

shutdown limits<br />

1 sensor faulty and temp.<br />

less than 3 degrees from<br />

shutdown limits<br />

halt Controller halt CP none -continue<br />

none -continue<br />

none -continue<br />

halt Controller halt CP none -continue<br />

Memory QPP memory halt Controller halt CP none -continue<br />

Execution<br />

execution time out of halt Controller halt CP none -continue<br />

range / failure<br />

error on logical sheet<br />

halt Controller<br />

Watchdog output shorted halt Controller halt CP none -continue<br />

de-energized watchdog<br />

line for redundant outputs<br />

halt Controller halt CP none -continue<br />

de-energized watchdog<br />

line for non-redundant<br />

outputs<br />

halt Controller<br />

de-energize non redundant outputs,<br />

continue operation on redundant<br />

outputs<br />

Watchdog faulty halt Controller halt CP none -continue<br />

Bus drivers<br />

Internal link<br />

QPP module<br />

secondary switch-off faulty halt Controller halt CP none -continue<br />

22 Release 131, Issue 4.2