Shutdown at assertion of <strong>Safety</strong> <strong>Manager</strong> alarm markers<br />
If the normal system response of <strong>Safety</strong> <strong>Manager</strong> is not enough when <strong>Safety</strong><br />
<strong>Manager</strong> detects a fault and more stringent system response is required, the <strong>Safety</strong><br />
<strong>Manager</strong> alarm markers can be used to shut down the system via the application.<br />
Figure 5 on page 21 shows an example of how to shut down the system in case of<br />
an IO <strong>com</strong>pare error. An additional manual shutdown input is provided by which<br />
the operator can initiate a shutdown by hand.<br />
Figure 5 Diagram to shut down system in case of output <strong>com</strong>pare error<br />
If an IO <strong>com</strong>pare error is detected or a manual shutdown is initiated, a<br />
divide-by-zero is forced and <strong>Safety</strong> <strong>Manager</strong> shuts down. Other alarm markers<br />
can be used in a similar way.<br />
Note:<br />
A manual shutdown can also be realized via the shutdown (SD) input of the<br />
SM Controller.<br />
With aid of the SD input a tested, hard wired connection can be used. The SD input is<br />
accessible via the SD loop connector at the back of the CP chassis.<br />
Breaking the SD loop causes all outputs to be de-activated!<br />
<strong>Safety</strong> <strong>Manager</strong> <strong>Safety</strong> <strong>Manual</strong> 21