2 – Architectural principle and standards of <strong>Safety</strong> <strong>Manager</strong><br />

UL 991<br />

Test for safety-related controls<br />

employing solid-state devices,<br />

second edition.<br />

FM3600, FM 3611 Electrical equipment for use in<br />

Class I, Division 2, • Class I, Division 2,<br />

Groups A, B, C &<br />

• Class II, Division 2, and<br />

D<br />

• Class III, Division 1 and 2,<br />

Class II,<br />

hazardous locations.<br />

Division 2,<br />

Groups F & G<br />

CSA C22.2<br />

IEC 60068-1<br />

Table 3 <strong>Safety</strong> <strong>Manager</strong> <strong>com</strong>pliance to standards<br />

Standard Title Remarks<br />

Process control equipment.<br />

Industrial products.<br />

Basic environmental testing<br />

procedures.<br />

Underwriters Laboratories.<br />

Factory Mutual Research.<br />

Applies to the field wiring<br />

circuits of the following<br />

modules:<br />

SDI-1624, SAI-0410,<br />

SAI-1620m, SDIL-1608 and<br />

SAO-0220m, and installation of<br />

the Controller in these<br />

environments.<br />

Canadian Standards Association<br />

No. 142 (R1993).<br />

IEC 60068-2-1 Cold test. 0°C (32°F); 16 hours; system in<br />

operation; reduced power supply<br />

voltage:<br />

(–15%): U=20.4 Vdc or<br />

(–10%): U=198 Vac.<br />

IEC 60068-2-1 Cold test. –10°C (14°F); 16 hours; system<br />

in operation.<br />

IEC 60068-2-2 Dry heat test. up to 65°C (149°F); 16 hours;<br />

system in operation; increased<br />

power supply voltage:<br />

(+15%): U=27.6 Vdc or<br />

(+10%): U=242 Vac.<br />

IEC 60068-2-3 Test Ca: damp heat, steady state. 21 days at +40°C (104°F), 93%<br />

relative humidity; function test<br />

after cooling.<br />

IEC 60068-2-3 Test Ca: damp heat, steady state. 96 hours at +40°C (104°F), 93%<br />

relative humidity; system in<br />

operation.<br />

IEC 60068-2-14 Test Na: change of temperature –<br />

withstand test.<br />

–25°C—+55°C (–13°F—<br />

+131°F), 12 hours, 95% relative<br />

humidity, recovery time: max. 2<br />

hours.<br />