2 – Architectural principle and standards of <strong>Safety</strong> <strong>Manager</strong><br />
UL 991<br />
Test for safety-related controls<br />
employing solid-state devices,<br />
second edition.<br />
FM3600, FM 3611 Electrical equipment for use in<br />
Class I, Division 2, • Class I, Division 2,<br />
Groups A, B, C &<br />
• Class II, Division 2, and<br />
D<br />
• Class III, Division 1 and 2,<br />
Class II,<br />
hazardous locations.<br />
Division 2,<br />
Groups F & G<br />
CSA C22.2<br />
IEC 60068-1<br />
Table 3 <strong>Safety</strong> <strong>Manager</strong> <strong>com</strong>pliance to standards<br />
Standard Title Remarks<br />
Process control equipment.<br />
Industrial products.<br />
Basic environmental testing<br />
procedures.<br />
Underwriters Laboratories.<br />
Factory Mutual Research.<br />
Applies to the field wiring<br />
circuits of the following<br />
modules:<br />
SDI-1624, SAI-0410,<br />
SAI-1620m, SDIL-1608 and<br />
SAO-0220m, and installation of<br />
the Controller in these<br />
environments.<br />
Canadian Standards Association<br />
No. 142 (R1993).<br />
IEC 60068-2-1 Cold test. 0°C (32°F); 16 hours; system in<br />
operation; reduced power supply<br />
voltage:<br />
(–15%): U=20.4 Vdc or<br />
(–10%): U=198 Vac.<br />
IEC 60068-2-1 Cold test. –10°C (14°F); 16 hours; system<br />
in operation.<br />
IEC 60068-2-2 Dry heat test. up to 65°C (149°F); 16 hours;<br />
system in operation; increased<br />
power supply voltage:<br />
(+15%): U=27.6 Vdc or<br />
(+10%): U=242 Vac.<br />
IEC 60068-2-3 Test Ca: damp heat, steady state. 21 days at +40°C (104°F), 93%<br />
relative humidity; function test<br />
after cooling.<br />
IEC 60068-2-3 Test Ca: damp heat, steady state. 96 hours at +40°C (104°F), 93%<br />
relative humidity; system in<br />
operation.<br />
IEC 60068-2-14 Test Na: change of temperature –<br />
withstand test.<br />
–25°C—+55°C (–13°F—<br />
+131°F), 12 hours, 95% relative<br />
humidity, recovery time: max. 2<br />
hours.<br />