Figure 3 Functional diagram: QMR architecture<br />
QPP Control Processor 1<br />
SD<br />
Watchdog<br />
Input<br />
Module<br />
Processor<br />
Processor<br />
SMOD<br />
Output<br />
Module<br />
Sensor<br />
xx<br />
yyy<br />
Input<br />
Module<br />
Processor<br />
Processor<br />
SMOD<br />
Output<br />
Module<br />
Quad<br />
Voter<br />
Watchdog<br />
Input Interfaces<br />
QPP Control Processor 2<br />
Output Interfaces<br />
Final Element<br />
In redundant IO configurations, each path is controlled by one of the Control<br />
Processors and an independent switch (Secondary Means of De-energization,<br />
SMOD), which is controlled by the diagnostic software and an independent<br />
watchdog.<br />
Furthermore, each Control Processor is able to switch off the output channels of<br />
the other Control Processor.<br />
Watchdog architecture in mixed IO configurations<br />
In a system with <strong>com</strong>bined redundant and non redundant IO 3 watchdog lines are<br />
active:<br />
• WD1<br />
This is the Watchdog line dedicated for Control Processor 1.<br />
- De-energizes upon a safety related fault in Control Processor 1 or an<br />
output module of Control Processor 1.<br />
- When de-energized, Control Processor 1 and the related outputs are halted.<br />
• WD2<br />
This is the Watchdog line dedicated for Control Processor 2.<br />
<strong>Safety</strong> <strong>Manager</strong> <strong>Safety</strong> <strong>Manual</strong> 11