Internal Use Only<br />

http://biz.lgservice.com<br />

Multi Air Conditioner<br />

SVC MANUAL(Exploded View)<br />

MODEL : A2UW183FA0(<strong>LMU185HV</strong>)<br />

CAUTION<br />

Before Servicing the unit, read the safety precautions in General SVC manual.<br />

Only for authorized service personnel.


1. Specification<br />

Outdoor Unit<br />

Capacity(*)<br />

Btu/h Class<br />

Power Input Cooling kW<br />

(Min._Rated~ Max.) <strong>Heat</strong>ing kW<br />

Running Current (Rated) Cooling A<br />

<strong>Heat</strong>ing<br />

A<br />

Starting Current Cooling/<strong>Heat</strong>ing A<br />

Power Supply<br />

Ø / V / Hz<br />

Power Supply Cable (Outdoor)<br />

No.x AWG<br />

Transmission Cable (Outdoor to Indoor unit )<br />

No.x AWG<br />

Dimensions W x H x D mm(inch)<br />

Net Weight<br />

kg(lbs)<br />

Max. Number of Connectable Indoor Units<br />

Type<br />

Qty x Model<br />

Compressor<br />

Motor type<br />

Oil charge volume<br />

cc<br />

Oil Type<br />

Cycle A Charge (at 7.5m)<br />

g(oz)<br />

Refrigerant Cycle B Charge (at 7.5m) g(oz)<br />

Type<br />

Control<br />

<strong>Heat</strong> Exchanger<br />

(Rows x Column x FPI) x No.<br />

Coil tube dia.<br />

mm(inch)<br />

Defrosting Method<br />

Capacitor<br />

µ/Vac<br />

Fan motor<br />

Drive<br />

Discharge Direction(Side/Top)<br />

Air Flow RateÅ~No. of Fan<br />

CMM(CFM)<br />

Sound Level(H/L) Sound Pressure dB(A)+3<br />

Liquid(Cycle A)<br />

mm(inch)<br />

Piping Connections Gas(Cycle A) mm(inch)<br />

Liquid(Cycle B)<br />

mm(inch)<br />

Gas(Cycle B)<br />

mm(inch)<br />

Max. total piping<br />

m(ft.)<br />

Piping length spec. Max. OD~ID piping m(ft.)<br />

Piping Lengh(no add'l refrigerant) m(ft.)<br />

Max. Elevation Outdoor Unit~Indoor Unit m(ft.)<br />

Difference Indoor Unit~Indoor Unit m(ft.)<br />

Operation Range Cooling ˚C(˚F)<br />

(Outdoor) <strong>Heat</strong>ing ˚C(˚F)<br />

A2UW183FA0(<strong>LMU185HV</strong>)<br />

18,000<br />

0.52~1.26~2.05<br />

0.77~1.63~2.18<br />

2.3~5.7~9.5<br />

3.4~7.2~9.6<br />

-<br />

1/208~230/60<br />

3 x 14<br />

4 x 18 (Including Earth)<br />

870x655x320 (34 1/4x25 25/32x12 9/16)<br />

52(1<strong>15</strong>)<br />

2<br />

e-Scroll<br />

1 x 5CS130XCC03<br />

BLDC<br />

480<br />

RB68A<br />

1,650(59.97)<br />

-<br />

R410A<br />

EEV<br />

(2R x 28C x 18) x1<br />

7(0.276)<br />

Reversing cycle<br />

6/370<br />

Direct (AC)<br />

Side<br />

53(1,871)<br />

51/45<br />

6.35(1/4) x 2EA<br />

9.52(3/8) x 2EA<br />

-<br />

-<br />

50(164.0)<br />

25(82.0)<br />

22.5(73.8)<br />

<strong>15</strong>(49.2)<br />

7.5(24.6)<br />

-10~46 (14 ~114.8 )<br />

-<strong>15</strong> ~ 24 (5~ 75.2)<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 26.7°C(80°F) DB/19.4°C(67°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB/23.9°C(75°F) WB<br />

<strong>Heat</strong>ing: - Indoor Temperature 21.1°C(70°F) DB/<strong>15</strong>.6°C(60°F) WB<br />

- Outdoor Temperature 8.3°C(47°F) DB/6.1°C(43°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)<br />

- Level Difference of Zero<br />

2. Wiring cable size must comply with the applicable local and national code.<br />

3. The specification may be subject to change without prior notice for purpose of improvement.<br />

4. At least two indoor units should be connected.<br />

5. For more Capacity(*),refer to the combination table<br />

Conversion Formula<br />

kW = Btu/h class X 0.0002931<br />

cfm = CMM × 35.3<br />

Copyright ©2009 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 2 -<br />

<strong>LG</strong>E Internal Use Only


2. List of Functions<br />

Category<br />

Reliability<br />

Convenience<br />

CAC Network<br />

Function<br />

Special Function Kit<br />

Others<br />

Function<br />

Defrost / Deicing<br />

High pressure switch<br />

Low pressure switch<br />

Phase protection<br />

Restart delay (3-minutes)<br />

Self diagnosis<br />

Soft start<br />

Test function<br />

Auto operation(Artificial intelligence)<br />

Auto restart operation<br />

Central control(<strong>LG</strong>AP)<br />

PDI(Power Distribution Indicator)<br />

PI485<br />

Low ambient operation<br />

Thermistor<br />

A2UW183FA0[<strong>LMU185HV</strong>]<br />

O<br />

X<br />

X<br />

X<br />

O<br />

O<br />

O<br />

X<br />

O<br />

O<br />

X<br />

X<br />

X<br />

O<br />

-<br />

O : Applied X : Not applied - : No relation<br />

Option : Model name & price are different according to options, and assembled in factory with main unit.<br />

Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied<br />

with separate package<br />

★ : These safety switcher are standard or optional features defending on region & country.<br />

Copyright ©2009 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 3 -<br />

<strong>LG</strong>E Internal Use Only


3. Piping Diagrams<br />

Outdoor Unit<br />

Reversing<br />

Valve<br />

Th1<br />

Accumulator<br />

Field piping<br />

Gas(Ø9.52)<br />

Room B<br />

Room A<br />

Th4<br />

Th3<br />

<strong>Heat</strong><br />

Exchanger<br />

Field piping<br />

Liquid(Ø6.35)<br />

Room B<br />

Room A<br />

EEV-B<br />

EEV-A<br />

Compressor<br />

Drier<br />

Th2<br />

REFRIGERANT FLOW<br />

COOLING<br />

HEATING<br />

LOC. Description PCB Connector<br />

TH1 Thermistor for outdoor air temperature CN_TH2<br />

TH2 Thermistor for condensing temperature CN_TH2<br />

TH3 Thermistor for discharge pipe temperature CN_TH3<br />

TH4 Thermistor for suction pipe temperature CN_TH3<br />

Copyright ©2009 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 4 -<br />

<strong>LG</strong>E Internal Use Only


4. Wiring Diagrams<br />

1.Wiring Diagram<br />

2.PCB<br />

CN_PSC2<br />

CN_PSC1<br />

CN_4WAY<br />

CN_FAN(A)<br />

CN_TH3<br />

CN_TH2<br />

CN_EEV1<br />

CN_EEV2<br />

CN_COM<br />

Copyright ©2009 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 5 -<br />

<strong>LG</strong>E Internal Use Only


5. Exploded View<br />

554031<br />

Outdoor Air, Condenser<br />

Thermistor<br />

567480D<br />

437212<br />

435511<br />

435512<br />

W5210B<br />

552113A<br />

349600<br />

268711<br />

558511<br />

552112<br />

649950<br />

559010<br />

W6640<br />

546810<br />

W0CZZ<br />

437211<br />

567480E<br />

S-pipe, D-pipe<br />

Thermistor<br />

552202<br />

552116<br />

447910<br />

261704<br />

561410<br />

550140<br />

554160<br />

661400A<br />

661400B<br />

435301<br />

430411<br />

552200<br />

552203A<br />

552203B<br />

552203A<br />

552203B<br />

349480<br />

437210<br />

552113B<br />

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.<br />

Please check the correct parts in View RPL(Replacement Part List) on GCSC.<br />

(GCSC Website http://biz.Lgservice.com,)<br />

Copyright ©2009 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 6 -<br />

<strong>LG</strong>E Internal Use Only


P/NO : MFL61777601 FEBRUARY, 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!