Vacuum Circuit Breakers

Vacuum Circuit Breakers Vacuum Circuit Breakers

05.11.2012 Views

Leader in Electrics & Automation Pro-MEC Vacuum Circuit Breakers Electric Equipment

Leader in Electrics & Automation<br />

Pro-MEC<br />

<strong>Vacuum</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />

Electric Equipment


2<br />

<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

LG Pro-MEC VCB is user-friendly to give more convenience<br />

and safety by providing high speed interrupting time (3cycles),<br />

adopting the rapid auto-reclosing method, and having<br />

wide range of accessories.<br />

7.2kV Draw-out (F class)<br />

<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Ratings 4<br />

Constructional and operating characteristics 10<br />

Control circuit diagram 11<br />

7.2kV dimension 12<br />

12kV dimension 23<br />

17.5kV dimension 24<br />

24kV dimension 33<br />

Accessories 41<br />

Types and ordering information 46<br />

24kV Draw-out (F class)<br />

<strong>Vacuum</strong> Interrupter<br />

Features & Ordering information 48<br />

Structure 49<br />

Operating characteristics 50<br />

Ratings and Specifications 51<br />

Dimensions 54


[ Compasion table for VCB (Short circuit test) ]<br />

Wide range of accessories (optional)<br />

� Key Lock<br />

� Padlock of earthing switch<br />

� Button padlock<br />

� Position switch of the earthing switch<br />

� Button cover<br />

� Locking coil of earthing switch<br />

� Position switch (Cell switch)<br />

� Shutter padlock<br />

� Preparatory trip coil (Secondary trip coil)<br />

� MOC (Mechanically operated cell switch)<br />

High reliability of the operating mechanism<br />

- Separate design of the main circuit from the<br />

operating mechanism.<br />

- Adopt the toggle link method.<br />

- Improved the reliability of electric circuit.<br />

- Adopt the rapid auto-reclosing method as a<br />

standard option. (O-0.3sec.-CO-3min.-CO)<br />

High interrupting performance<br />

- Make short of the interrupting time. (3cycles)<br />

- Increase the rated short-circuit withstand<br />

characteristics. (1sec. to 3sec.)<br />

Great operational safety<br />

- Reinforce the insulation in the conduct, by<br />

adopting the molded housing in each phase.<br />

- Built in the device making the contacts open first<br />

when draw in and out.<br />

- Adopt the tulip-shape connection between the<br />

cradle and the VCB.<br />

Compasion table for VCB (Short circuit test)<br />

� Latch checking switch<br />

� TOC (Truck operated cell switch)<br />

� Charge indicator<br />

� Code plate (Miss insertion prevention)<br />

� Position padlock<br />

� Capacitor trip device<br />

� Earthing switch Note 1)<br />

� Rectifier<br />

Note 1) The earthing switch is not available for 17.5kV VCB.<br />

VACUUM CIRCUIT BREAKER<br />

3


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Ratings<br />

Type LVB-06��-20D LVB-06��-25D<br />

Rated voltage (kV) 7.2 7.2<br />

Rated normal current (A) 630 1250 2000 630 1250 2000<br />

Rated frequency (Hz) 50/60 50/60<br />

Rated short-circuit breaking current (kA) 20 25<br />

Rated short-circuit breaking capacity (MVA) 250 310<br />

Rated short-time withstand current (kA/3sec) 20 25<br />

Rated short-circuit making current (kAp) 52 65<br />

Rated breaking time (Cycle) 3 3<br />

Rated opening time (sec) ≤ 0.04 ≤ 0.04<br />

No-load closing time (sec) ≤ 0.06 ≤ 0.06<br />

Withstand Power frequency (kV/min) 20 20<br />

voltage Impulse (kV/1.2×50㎲) 60 60<br />

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO<br />

Mechanical M2 (10,000 times) M2 (10,000 times)<br />

Type<br />

test<br />

Electrical E2 (List1) E2 (List1)<br />

Capacitive current switching Note 1) C2 C2<br />

Lifetime<br />

Without maintenance (Time)<br />

Mechanical<br />

Maintenance (Time)<br />

Without maintenance (Time)<br />

Electrical<br />

Maintenance (Time)<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b<br />

Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed<br />

E-type Visible, Clip Visible, Tulip Visible, Clip Visible, Tulip<br />

Installing<br />

method<br />

Draw-out<br />

type<br />

F-type<br />

G-type Note 2)<br />

-<br />

T<br />

Visible, Clip<br />

Visible, Clip<br />

Enclosed, Tulip<br />

Visible, Tulip<br />

Visible, Tulip<br />

Enclosed, Tulip<br />

Visible, Clip<br />

Visible, Clip<br />

Enclosed, Tulip<br />

Visible, Tulip<br />

Visible, Tulip<br />

Enclosed, Tulip<br />

M-type Note 2) Enclosed, Tulip Enclosed, Tulip<br />

E-type (kg) 94 99 134.5 94 99 134.5<br />

VCB F-type (kg) 95 100 135.5 95 100 135.5<br />

Weight G, M-type (kg) 95 (137) 100 (147) 135.5 (163.5) 95(137) 100(147) 135.5(163.5)<br />

Note 3) E-type (kg) 37 39.5 60 37 39.5 60<br />

Cradle F-type (kg) 39 41.5 62.5 39 41.5 62.5<br />

G-type (kg) 39(103) 41.5(107) 62.5(117) 39(103) 41.5(107) 62.5(117)<br />

Applied standard IEC 62271-100 IEC 62271-100<br />

Test laboratory KERI Note 4) � �<br />

Note 1) Applied cable-charging current switching test<br />

2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T”in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)<br />

3) ( )* indicates the weight of Enclosed Tulip installing method VCB.<br />

4) KERI: Korea Electrotechnology Research Institute.<br />

4<br />

▲ Visible VCB<br />

(Draw-out type)<br />

▲ E-type cradle<br />

(Visible, Clip contact)<br />

▲ E-type cradle<br />

(Visible, Tulip contact)<br />

▲ F -type cradle<br />

(Visible, Clip contact)<br />

▲ G-type cradle<br />

(Visible, Tulip contact)


Type LVB-06��-32D LVB-06��-40D<br />

Rated voltage (kV) 7.2 7.2<br />

Rated normal current (A) 1250 2000 3150 1250 2000 3150<br />

Rated frequency (Hz) 50/60 50/60<br />

Rated short-circuit breaking current (kA) 31.5 40<br />

Rated short-circuit breaking capacity (MVA) 390 500<br />

Rated short-time withstand current (kA/3sec) 31.5 40<br />

Rated short-circuit making current (kAp) 82 104<br />

Rated breaking time (Cycle) 3 3<br />

Rated opening time (sec) ≤ 0.04 ≤ 0.04<br />

No-load closing time (sec) ≤ 0.06 ≤ 0.06<br />

Withstand Power frequency (kV/min) 20 20<br />

voltage Impulse (kV/1.2×50㎲) 60 60<br />

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO<br />

Mechanical M2 (10,000 times) M2 (10,000 times)<br />

Type<br />

test<br />

Electrical E2 (List1) E2 (List1)<br />

Capacitive current switching Note 1) C2 C2<br />

Lifetime<br />

Without maintenance (Time)<br />

Mechanical<br />

Maintenance (Time)<br />

Without maintenance (Time)<br />

Electrical<br />

Maintenance (Time)<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b<br />

Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed<br />

E-type Visible, Tulip Visible, Clip Visible, Tulip Visible, Tulip<br />

Installing<br />

method<br />

Draw-out<br />

type<br />

F-type<br />

G-type Note 2)<br />

-<br />

T<br />

Visible, Tulip<br />

Visible, Tulip<br />

Enclosed, Tulip<br />

Visible, Tulip<br />

Visible, Tulip<br />

-<br />

Visible, Tulip<br />

Visible, Tulip<br />

Enclosed, Tulip<br />

Visible, Tulip<br />

Visible, Tulip<br />

-<br />

M-type Enclosed, Tulip - Enclosed, Tulip -<br />

E-type (kg) 131.5 134.5 210 135 138 210<br />

VCB F-type (kg) 132.5 135.5 211 136 139 211<br />

Weight G, M-type (kg) 132.5(159) 135.5(160) 220 136(162.5) 139(163.5) 220<br />

Note 3) E-type (kg) 52 60 131 52 60 131<br />

Cradle F-type (kg) 54.5 62.5 135 54.5 62.5 135<br />

G-type (kg) 62.5(110) 135(117) 155 62.5(110) 135(117) 155<br />

Applied standard IEC 62271-100 IEC 62271-100<br />

Test laboratory KERI Note 4) � �<br />

Note 1) Applied cable-charging current switching test<br />

2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T”in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)<br />

3) ( )* indicates the weight of Enclosed Tulip installing method VCB.<br />

4) KERI: Korea Electrotechnology Research Institute<br />

▲ Enclosed VCB<br />

(Draw-out type, G-type)<br />

▲ G-type Cradle<br />

(Enclosed, Tulip contact)<br />

▲ Visible, Clip contact ▲ Visible, Tulip contact ▲ Enclosed, Tulip contact<br />

5


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Ratings<br />

Type LVB-12��-25D/06, 12, 20-T LVB-12��-32D/12, 20-T<br />

Rated voltage (kV) 12 12<br />

Rated normal current (A) 630 1250 2000 1250 2000<br />

Rated frequency (Hz) 50(E1,C2: KEMA), 60(E2: PT & T) 60(E1,E2,C2: PT & T)<br />

Rated short-circuit breaking current (kA) 25 31.5<br />

Rated short-circuit breaking capacity (MVA) 500 650<br />

Rated short-time withstand current (kA/sec) 25/3 31.5/3<br />

Rated short-circuit making current (kAp) 62.5 81.9<br />

Rated breaking time (Cycle) 3<br />

Rated opening time (sec) 0.04<br />

No-load closing time (sec) 0.06<br />

Withstand Power frequency (kV/min) 28<br />

voltage Impulse (kV/1.2×50㎲) 75<br />

Rated operating sequence O-0.3s-CO-3min-CO<br />

Type<br />

test<br />

Mechanical<br />

Electrical<br />

M2 (10,000 times)<br />

E2 (List 1)<br />

Capacitive current switching Note 1) C2<br />

Lifetime<br />

Without maintenance (Time)<br />

Mechanical<br />

Maintenance (Time)<br />

Without maintenance (Time)<br />

Electrical<br />

Maintenance (Time)<br />

20,000<br />

30,000<br />

20,000<br />

30,000<br />

Auxiliary switch 4a4b, 10a10b<br />

Fixed -<br />

E-TYPE -<br />

Installing<br />

Method Draw-out<br />

type<br />

F-TYPE<br />

G-TYPE<br />

-<br />

Enclosed, Tulip<br />

M-TYPE Enclosed, Tulip<br />

E-TYPE (kg) -<br />

VCB F-TYPE (kg) -<br />

Weight<br />

G, M-TYPE<br />

E-TYPE<br />

(kg)<br />

(kg)<br />

137<br />

-<br />

147<br />

-<br />

163.5<br />

-<br />

159<br />

-<br />

160<br />

-<br />

Cradle F-TYPE (kg) - - - - -<br />

G, M-TYPE (kg) 103 107 117 110 117<br />

Applied standard IEC 62271-100<br />

Test laboratory KEMA: E1, C2 PT & T: E2 Note 2) PT & T: E1, E2, C2, M2<br />

Note 1) Applied cable-charging current switching test<br />

2) PT&T: Power Testing & Technology Institute (LGIS high-power laboratory)<br />

6


Type LVB-17��-25D/06, 12, 20, 25<br />

Rated voltage (kV) 17.5<br />

Rated normal current (A) 630 1250 2000 2500<br />

Rated frequency (Hz) 50/60<br />

Rated short-circuit breaking current (kA) 25<br />

Rated short-circuit breaking capacity (MVA) 750<br />

Rated short-time withstand current (kA/sec) 25/3sec<br />

Rated short-circuit making current (kAp) 65<br />

Rated breaking time (Cycle) 3<br />

Rated opening time (sec) ≤0.04<br />

No-load closing time (sec) ≤0.06<br />

Withstand Power frequency (kV/min) 38<br />

voltage Impulse (kV/1.2×50㎲) 95<br />

Rated operating sequence O-0.3s-CO-3min-CO<br />

Mechanical M2 (10,000 times)<br />

Type<br />

test<br />

Electrical E2 (List1)<br />

Capacitive current switching Note 1) C2<br />

Lifetime<br />

Without maintenance (Time)<br />

Mechanical<br />

Maintenance (Time)<br />

Without maintenance (Time)<br />

Electrical<br />

Maintenance (Time)<br />

20000<br />

30000<br />

20000<br />

30000<br />

Auxiliary switch 4a4b,10a10b<br />

Fixed Visible, Fixed<br />

Installing E-TYPE Visible, Tulip<br />

method<br />

Draw-out<br />

type<br />

F-TYPE Visible, Tulip<br />

G-TYPE Visible, Tulip<br />

Fixed type VCB (kg) 115 125 135 165<br />

E-TYPE (kg) 130 140 155 195<br />

VCB F-TYPE (kg) 130 140 155 195<br />

Weight<br />

G-TYPE<br />

E-TYPE<br />

(kg)<br />

(kg)<br />

160<br />

65<br />

170<br />

67<br />

190<br />

78<br />

220<br />

165<br />

Cradle F-TYPE (kg) 75 77 88 172<br />

G-TYPE (kg) 100 105 115 185<br />

Applied standard IEC 62271-100<br />

Test laboratory KEMA , PT&T �<br />

Note 1) Applied cable-charging current switching test.<br />

7


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Ratings<br />

Type LVB-20��-13D LVB-20��-13D/T LVB-20��-16D LVB-20��-16D/T LVB-20��-25D LVB-20��-25D/T<br />

Rated voltage (kV) 24 24 24<br />

Rated normal current (A) 630 630 630<br />

1250 1250 1250<br />

2000<br />

Rated frequency (Hz) 50/60 50/60 50/60<br />

Rated short-circuit breaking current (kA) 12.5 16 25<br />

Rated short-circuit breaking capacity (MVA) 520 665 1000<br />

Rated short-time withstand current (kA/3sec) 12.5 16 25<br />

Rated short-circuit making current (kAp) 32.5 40 65<br />

Rated breaking time (Cycle) 3 3 3<br />

Rated opening time (sec) ≤ 0.04 ≤ 0.04 ≤ 0.04<br />

No-load closing time (sec) ≤ 0.06 ≤ 0.06 ≤ 0.06<br />

Withstand Power frequency (kV/min) 50 50 50<br />

voltage Impulse (kV/1.2×50㎲) 125 125 125<br />

Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO<br />

Type<br />

test<br />

Mechanical<br />

Electrical<br />

Capacitive current switching Note 1)<br />

M2(10,000 times)<br />

E2 (List1)<br />

C2<br />

M2(10,000 times)<br />

E2 (List1)<br />

C2<br />

M2(10,000 times)<br />

E2 (List1)<br />

C2<br />

Lifetime<br />

Without maintenance (Time)<br />

Mechanical<br />

Maintenance (Time)<br />

Without maintenance (Time)<br />

Electrical<br />

Maintenance (Time)<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

20000<br />

30000<br />

Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b 4a4b, 10a10b<br />

Fixed Visible, Fixed - Visible, Fixed - Visible, Fixed -<br />

Installing<br />

Draw-out<br />

E-type<br />

F-type<br />

Visible, Clip<br />

Visible, Clip<br />

Enclosed, Tulip<br />

Enclosed, Tulip<br />

Visible, Clip<br />

Visible, Clip<br />

Enclosed, Tulip<br />

Enclosed, Tulip<br />

Visible, Clip<br />

Visible, Clip<br />

Enclosed, Tulip<br />

Enclosed, Tulip<br />

8<br />

method<br />

type G-type Note 2) Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, Tulip Visible, Tulip Enclosed, Tulip<br />

M-type - Enclosed, Tulip - Enclosed, Tulip - Enclosed, Tulip<br />

E-type (kg) 145 145 145 145 145 145<br />

VCB F-type (kg) 145 145 145 145 145 145<br />

Weight<br />

G, M-type<br />

E-type<br />

(kg)<br />

(kg)<br />

155<br />

80<br />

187<br />

80<br />

155<br />

80<br />

187<br />

80<br />

155<br />

80<br />

187/218 (2000A)<br />

80<br />

Cradle F-type (kg) 82 82 82 82 82 82<br />

G-type (kg) 110 120 110 120 110 120<br />

Applied standard IEC 62271-100 IEC 62271-100 IEC 62271-100<br />

Test laboratory<br />

KERI � - �<br />

KEMA - � �<br />

Note 1) Applied cable-charging breaking current<br />

2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T”in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)<br />

▲ Fixed type VCB ▲ E-type cradle ▲ F-type cradle ▲ G-type cradle<br />

▲ G-type cradle<br />

(Withdrawable by lever) (Withdrawable by screw)


Motor<br />

When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.<br />

Closing Coil (C)<br />

The coil operated only when the power is applied continuously<br />

over 45ms. It has built-in electrically anti-pumping circuit.<br />

Note 1)Range of the normal operating voltage: 85~110%<br />

2) DC 24V is the underdeveloped rating.<br />

Auxiliary switch<br />

Standard 4a4b / Optional 10a10b<br />

Charge indicator of<br />

the closing spring<br />

Indicating the condition of the closing spring.<br />

Charged Discharged<br />

Counter<br />

Rated voltage<br />

Note 1) Range of the normal operating voltage: 85~110%<br />

2) DC 24V is the underdeveloped rating.<br />

The peak value of the Consumption Charging time<br />

Rated current (A)<br />

inrush current (A)<br />

power (W) (Sec.)<br />

DC 24V 30 15 350 12<br />

DC 110V 20 5 330 12<br />

Rated voltage Rated current (A)<br />

DC 24V 10<br />

DC 110V 2.5<br />

Classification<br />

AC<br />

250V<br />

125V<br />

10<br />

10<br />

5<br />

5<br />

Contact Ratings 250V 10 5<br />

DC 125V 10 5<br />

30V 10 5<br />

Shunt coil (TC)<br />

General Inductive Contact<br />

load (A) load (A) configuration<br />

Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing spring<br />

contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch,<br />

Truck operated cell switch.<br />

When the VCB is 'ON' position, even though the control power<br />

of a shunt coil is 'OFF', the VCB maintains the 'ON' position.<br />

Note 1)Range of the normal operating voltage: 70~110%<br />

2) DC 24V is the underdeveloped rating.<br />

Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option)<br />

4a4b<br />

10a10b<br />

Rated voltage Rated current (A)<br />

DC 24V 10<br />

DC 110V 2.5<br />

��Position of the Aux.contact switch<br />

VCB<br />

ON<br />

OFF<br />

“a” contact<br />

ON<br />

OFF<br />

Position indicator of the<br />

main contacts<br />

Indicating the 'Close' or the 'Open' of the main contacts.<br />

Close position: ��ON�� Open position: ��OFF��<br />

Close position Open position<br />

“b” contact<br />

OFF<br />

ON<br />

9


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Constructional and operating characteristics<br />

10<br />

①<br />

②<br />

③<br />

④<br />

⑥<br />

⑦<br />

⑩<br />

Manual charge<br />

Insert the charge handle into the manual charge hole in the front of a<br />

VCB, and rotate it to clockwise over 40times and the charge<br />

complete with a metal sound.<br />

Motor charge<br />

⑧<br />

If you apply the control power to a VCB, the closing spring will be<br />

charged automatically by a motor and then the control power will be<br />

turned off by the built-in limit s/w. Please use the same control<br />

voltage for motor, Closing coil, Trip coil.<br />

Sequence of the switching mechanism<br />

⑤<br />

⑪<br />

⑨<br />

① Charge Indicator<br />

of the closing spring<br />

② Close button<br />

③ Key lock (Optional)<br />

④ Trip button<br />

⑤ Manual charge hole<br />

⑥ Position indicator<br />

of the main contacts<br />

⑦ Counter<br />

⑧ Screw hole for draw-in<br />

and draw-out<br />

⑨ Nameplate<br />

⑩ Mounting hole<br />

⑪ Safety cover


Control circuit diagram<br />

52b: Auxiliary switch (NC)<br />

LS1: Closing interlock limit switch (only withdrawable type)<br />

LS2: Motor stopping, closing spring charged indication<br />

LS3: Anti-closing, anti-pumping limit switch<br />

LCS1: Opening latch checking switch(preventing closing<br />

unless the trip latch is properly reset)<br />

LS4, LS5: Position s/w (close in test position)<br />

LS6, LS7: Position s/w (close in run position)<br />

∅: External terminal of VCB<br />

52: <strong>Vacuum</strong> circuit breaker<br />

M: Spring charging motor<br />

TC: Trip coil<br />

TC1: Secondary Trip coil<br />

C: Closing coil<br />

Y: Anti-pump relay<br />

52a: Auxiliary switch (NO)<br />

Note 1) LCS1: Latch checking switch<br />

2) Trip coil supervision (Trip coil monitoring contact)<br />

Optional accessories<br />

3) Position switch: 4a (Terminal No.: 1, 2, 3, 4, 5, 6, 7, 8)<br />

4) TC1: Secondary trip coil (Preparatory trip coil Terminal No.: 82,83)<br />

5) In fixed type VCB, LS1 (Closing-coil limit switch) is not available.<br />

※ Above circuit diagram is based on ‘OFF’ status of VCB. and closing spring is charged.<br />

11


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (VCB)<br />

LVB-06P-20D, 25D, 32D, 40D (Visible, Fixed) - (630/1250/2000A)<br />

��Top<br />

LVB-06P-32D, 40D (Visible, Fixed) - (3150A)<br />

12<br />

*125.5 applied to all 7.2kV VCB.<br />

��Front<br />

��Front<br />

31.5/40kA 3150A<br />

<br />

��Side<br />

��Side<br />

Rated 630A 1250A<br />

A 6 10<br />

��Top<br />

(Unit: mm)


LVB-06E, F, G-20D, 25D, 32D, 40D E, F, G class - (630/1250/2000A)<br />

��Top<br />

��Front<br />

��Side<br />

Rated 630A 1250A<br />

A 6 10<br />

LVB-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front<br />

��Side<br />

<br />

(Unit: mm)<br />

13


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (VCB)<br />

LVB-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)<br />

��Front<br />

14<br />

��Side<br />

LVB-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)<br />

��Front<br />

��Side<br />

��Top<br />

��Top<br />

(Unit: mm)


LVB-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)<br />

��Front<br />

��Top<br />

��Side<br />

(Unit: mm)<br />

15


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (Cradle)<br />

LCL-06E-20D, 25D E class (Visible, Clip contact) - (630/1250A)<br />

��Front<br />

16<br />

Rated 630A 1250A<br />

A 6 10<br />

B 55 60<br />

C 95 90<br />

��Side<br />

��Top<br />

(Mounting hole)<br />

20/25kA 630/1250A E class<br />

(Unit: mm)<br />

(Earthing hole)


LCL-06E-20D, 25D, 32D, 40D E class (Visible, Tulip contact)<br />

��Front<br />

��Top<br />

(Mounting hole)<br />

LCL-06E-32D, 40D E class (Visible, Tulip contact) - (3150A)<br />

��Front<br />

ST: 175<br />

��Side<br />

Rated 1250A 2000A<br />

A 10 20<br />

class<br />

class<br />

(Earthing hole)<br />

<br />

��Side ��Top<br />

class<br />

(Mounting hole)<br />

ST: 175<br />

(Unit: mm)<br />

(Earthing hole)<br />

17


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (Cradle)<br />

LCL-06F-20D, 25D F class (Visible, Clip contact) - (630/1250A)<br />

��Front<br />

18<br />

Rated 630A 1250A<br />

A 6 10<br />

B 55 60<br />

C 95 90<br />

(Mounting hole)<br />

ST: 175<br />

��Top<br />

class<br />

(Mounting hole)<br />

(Earthing hole)<br />

class<br />

��Side<br />

LCL-06F-20D, 25D F class (Visible, Tulip contact) - (2000A)<br />

��Front<br />

��Top<br />

��Side<br />

<br />

class<br />

Insulation barrier<br />

(Earthing hole)<br />

(Unit: mm)


LCL-06F-32D, 40D F class (Visible, Tulip contact) - (1250/2000A)<br />

��Front<br />

��Top<br />

(Mounting hole)<br />

(Earthing hole)<br />

class<br />

(Mounting hole)<br />

class<br />

LCL-06F-32D, 40D F class (Visible, Tulip contact) - (3150A)<br />

��Front<br />

��Top<br />

��Side<br />

��Side<br />

Rated 1250A 2000A<br />

A 10 20<br />

ST: 175<br />

<br />

class<br />

(Earthing hole)<br />

(Unit: mm)<br />

class<br />

19


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (Cradle)<br />

LCL-06G-20D, 25D, 32D, 40D G class (Visible, Clip contact) - (630/1250/2000A)<br />

��Front<br />

<br />

20<br />

��Top<br />

��Side<br />

Rated 630A 1250A 2000A<br />

A 6 10 20<br />

(Mounting hole)<br />

class<br />

ST: 175<br />

(Earthing hole)<br />

class class<br />

class class<br />

(Unit: mm)


LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front<br />

��Top<br />

��Side<br />

(Earthing hole)<br />

class<br />

ST: 225<br />

<br />

(Unit: mm)<br />

ST: 225<br />

class<br />

class<br />

Rated<br />

630A<br />

20/25kA<br />

1250A 2000A<br />

31.5/40kA<br />

1250A 2000A<br />

A 6 12 25 12 25<br />

B ∅29 ∅48 ∅48<br />

21


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

7.2kV dimension (Cradle)<br />

LCL-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)<br />

��Side<br />

��Top<br />

22<br />

(Mounting hole)<br />

(Earthing hole)<br />

class<br />

<br />

(Unit: mm)


12kV dimension (VCB & Cradle)<br />

LVB-12G-25D/T, 32D/T G class - (630/1250/2000A)<br />

��Front<br />

130<br />

320.1<br />

470<br />

150 150<br />

115.5<br />

103<br />

522<br />

549<br />

S<br />

1235<br />

55.2 191<br />

706.7<br />

88 528.2<br />

288<br />

388.5<br />

(668)<br />

330 330<br />

345 295<br />

25kA 630/1250A G class 31.5kA 1250/2000A G class<br />

25kA 2000A G class<br />

LCL-12G-25D/T, 32D/T G class - (630/1250/2000A)<br />

��Front<br />

��Top<br />

ST: 225<br />

S<br />

600 (12) 100 660<br />

731.5<br />

(946)<br />

Section S-S<br />

156<br />

560<br />

660<br />

100<br />

4-∅14<br />

(Mounting hole)<br />

��Side<br />

��Side<br />

25kA 630/1250A G class<br />

A<br />

B<br />

29<br />

285 345<br />

295<br />

Rating<br />

630A<br />

25kA<br />

1250A 2000A<br />

31.5kA<br />

1250A 2000A<br />

A 12 25 12 25<br />

B ∅29 ∅48<br />

A<br />

88 528.2<br />

288<br />

388.5<br />

(668)<br />

ST: 225<br />

345 295<br />

31.5kA 1250/2000A G class<br />

25kA 2000A G class<br />

<br />

2-∅13<br />

VIEW "A"<br />

150 150<br />

26<br />

26<br />

83<br />

295<br />

(Unit: mm)<br />

48<br />

23


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

17.5kV dimension (VCB)<br />

LVB-17P-25D Fixed - (630/1250/2000A)<br />

��Front<br />

24<br />

285 130<br />

��Top<br />

4-∅ 13<br />

280.5<br />

22.5<br />

210<br />

115.5<br />

670<br />

750<br />

789<br />

125.5<br />

LVB-17P-25D Fixed - (2500A)<br />

��Front<br />

285 130<br />

254<br />

115.5<br />

770<br />

850<br />

889<br />

254<br />

210<br />

750<br />

670<br />

��Side<br />

2-∅ 14 60<br />

325.5<br />

630/1250A<br />

529<br />

130 40<br />

25kA 630/1250/2000A Fixed type<br />

397.5<br />

579<br />

240<br />

133.5<br />

20<br />

20<br />

25kA 2500A Fixed type<br />

190<br />

155.5<br />

A<br />

A<br />

<br />

��Side ��Top<br />

350<br />

318.5<br />

80<br />

4-∅ 14 40<br />

2000A<br />

295<br />

320<br />

40<br />

130<br />

670<br />

850<br />

6-∅14<br />

125.5<br />

120<br />

80<br />

(Unit: mm)<br />

Rating 630A 1250A/2000A<br />

A 6 20<br />

49 300 40 40<br />

4-∅13


LVB-17E, F-25D E, F class - (630/1250/2000A)<br />

��Front<br />

��Top<br />

285 130<br />

210 210<br />

115.5<br />

103<br />

710<br />

210 210<br />

202<br />

125.5<br />

LVB-17E, F-25D E, F class - (2500A)<br />

��Front<br />

285 130<br />

254<br />

115.5<br />

103<br />

811<br />

254<br />

109<br />

750<br />

169.5<br />

325.5<br />

670<br />

��Side<br />

94.5 77<br />

25kA 630/1250/2000A E, F class<br />

287<br />

630/1250A<br />

655.5<br />

484<br />

270<br />

<br />

∅29 ∅48<br />

60 80<br />

��Side ��Top<br />

359<br />

397.5<br />

551<br />

722.5<br />

337<br />

25kA 2500A E, F class<br />

360<br />

303.5<br />

2000A<br />

254<br />

295<br />

310<br />

202 125.5<br />

254<br />

(Unit: mm)<br />

25


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

17.5kV dimension (Cradle)<br />

LVB-17G-25D G class - (630/1250/2000A)<br />

��Front<br />

��Top<br />

LVB-17G-25D G class - (2500A)<br />

340 130<br />

26<br />

130<br />

340<br />

254<br />

770<br />

670<br />

210 210<br />

115.5<br />

103 103<br />

719<br />

749<br />

210 210<br />

254<br />

125.5<br />

��Front ��Side<br />

��Top<br />

138<br />

75<br />

302<br />

805<br />

103 103<br />

83.7(Interlock)<br />

810<br />

840<br />

142(MOC)<br />

144<br />

75<br />

263<br />

725<br />

83.7(Interlock)<br />

301<br />

493<br />

345<br />

635<br />

688<br />

142(MOC)<br />

337<br />

��Side<br />

25kA 630/1250/2000A G class<br />

17.5kV 25kA 2500A G class<br />

<br />

360<br />

359<br />

290<br />

251<br />

668<br />

721<br />

526<br />

370<br />

∅29 ∅48<br />

630/1250A 2000A<br />

254 254<br />

125.5<br />

295<br />

365<br />

(Unit: mm)


LCL-17E-25D E class - (630/1250/2000A)<br />

��Front<br />

800<br />

210 210<br />

<br />

40<br />

20<br />

2-∅14<br />

50<br />

160<br />

50<br />

50 160<br />

��Side<br />

87.2<br />

25kA 630/1250/2000A E class<br />

��Top<br />

725<br />

690<br />

340 340<br />

Rating 630A 1250A 2000A<br />

A 6 10 20<br />

166 ST: 182<br />

270<br />

40<br />

20<br />

2-∅14<br />

860 40<br />

1050<br />

630A 1250A 2000A<br />

60<br />

150<br />

60<br />

60 150<br />

440<br />

340<br />

A<br />

6-∅12<br />

(Mounting hole)<br />

A<br />

80<br />

295<br />

326<br />

∅14<br />

(Earth hole)<br />

40<br />

20<br />

4-∅14<br />

80<br />

130<br />

130 80<br />

80<br />

720<br />

139<br />

(Unit: mm)<br />

27


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

17.5kV dimension (Cradle)<br />

LCL-17E-25D E class - (2500A)<br />

��Front ��Side<br />

28<br />

254<br />

900<br />

254<br />

25kA 2500A E class<br />

��Top<br />

825<br />

790<br />

290<br />

910<br />

166 ST: 202 377<br />

254<br />

530<br />

1039<br />

<br />

VIEW "A"<br />

4-∅12<br />

254<br />

35<br />

∅50<br />

129<br />

310 360<br />

6-∅12<br />

(Mounting hole)<br />

360<br />

139<br />

940<br />

∅14<br />

(Earth hole)<br />

VIEW "A"<br />

(Unit: mm)


LCL-17F-25D F class - (630/1250/2000A)<br />

��Front<br />

800<br />

<br />

40<br />

725<br />

690<br />

166<br />

ST: 182<br />

860<br />

270 440<br />

20 2-∅14 20 2-∅14<br />

50<br />

50 160 50 160<br />

210<br />

210<br />

25kA 630/1250/2000A F class<br />

��Top<br />

��Side<br />

340 340<br />

Rating 630A 1250A 2000A<br />

A 6 10 20<br />

87.2<br />

40<br />

60<br />

60 150 60 150<br />

210 210<br />

1050<br />

40<br />

A<br />

A<br />

326 295<br />

6-∅12 (Mounting hole)<br />

340<br />

40<br />

20<br />

∅14<br />

(Earth hole)<br />

40<br />

40<br />

720<br />

4-∅14<br />

20 4-∅14<br />

80<br />

80 130 80 130<br />

210<br />

210<br />

139<br />

(Unit: mm)<br />

29


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

17.5kV dimension (Cradle)<br />

LCL-17F-25D F class - (2500A)<br />

��Front ��Side<br />

30<br />

254<br />

900<br />

254<br />

��Top<br />

25kA 2500A F class<br />

876<br />

825<br />

166 ST: 202 377<br />

35<br />

910 129<br />

360<br />

310<br />

139<br />

290 530 6-∅12<br />

(Mounting hole)<br />

<br />

254 254<br />

VIEW "A"<br />

4-M12<br />

∅50<br />

360<br />

940<br />

∅14<br />

(Earth hole)<br />

VIEW "A"<br />

(Unit: mm)


LCL-17G-25D G class - (630/1250/2000A)<br />

��Front<br />

800<br />

<br />

210<br />

295<br />

445<br />

1050<br />

210 2-∅15<br />

210<br />

295 162 40<br />

��Side<br />

797<br />

25kA 630/1250/2000A G class<br />

Rating 630A 1250A 2000A<br />

A 6 10 20<br />

295 162 40<br />

A<br />

30<br />

192<br />

250<br />

��Top<br />

A<br />

ST: 240<br />

210 2-∅15<br />

210<br />

736<br />

760<br />

210<br />

40<br />

1047<br />

175 (Earth hole)<br />

4-∅15<br />

295 162 40<br />

100 625<br />

(Unit: mm)<br />

A<br />

4-∅14<br />

(Mounting hole)<br />

31


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

17.5kV dimension (Cradle)<br />

LCL-17G-25D G class - (2500A)<br />

��Front<br />

32<br />

1180<br />

��Side<br />

25kA 2500A G class<br />

��Top<br />

∅79<br />

28<br />

774 172<br />

900<br />

860<br />

790<br />

175<br />

<br />

55<br />

20<br />

439<br />

ST: 240<br />

100 600<br />

134<br />

254<br />

254<br />

125<br />

70<br />

1024<br />

32<br />

∅14<br />

(Earth hole)<br />

254<br />

254<br />

6-∅14<br />

(Mounting hole)<br />

40<br />

80<br />

162<br />

360<br />

VIEW "A"<br />

(Unit: mm)


24kV dimension (VCB)<br />

LVB-20P-13D, 16D, 25D (Fixed) - (630/1250/2000A)<br />

��Front ��Side<br />

<br />

630A 1250A 2000A<br />

∅<br />

(Mounting hole)<br />

LVB-20E, F-13D/(T), 16D/(T), 25D/(T) E, F class - (630/1250/2000A)<br />

��Front ��Side<br />

<br />

Note 1) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.<br />

(Unit: mm)<br />

33


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

24kV dimension (Cradle)<br />

LVB-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)<br />

��Front ��Side<br />

LVB-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front ��Side<br />

34<br />

Note 1) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,<br />

LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.<br />

(Unit: mm)


24kV dimension (Cradle)<br />

LCL-20E-13D, 16D, 25D E class (Visible, Clip contact) - (630/1250/2000A)<br />

��Front ��Side<br />

��Top<br />

(Mounting hole)<br />

Rated A B T<br />

630, 1250A 768 190.5 10<br />

2000A 778 185.5 20<br />

12.5kA 630A 25kA 630A<br />

Insulation barrier<br />

(Earthing)<br />

<br />

12.5kA 1250A<br />

25kA 1250, 2000A<br />

(Unit: mm)<br />

<br />

35


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

24kV dimension (Cradle)<br />

LCL-20E-13D/T, 16D/T, 25D/T E class (Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front ��Side<br />

��Top<br />

36<br />

(Mounting hole)<br />

Rated A B T<br />

630, 1250A 768 190.5 10<br />

2000A 778 185.5 20<br />

ST: 260<br />

630A<br />

Insulation barrier<br />

1250A 2000A<br />

(Earthing)<br />

<br />

<br />

(Unit: mm)


LCL-20F-13D, 16D, 25D F class (Visible, Clip contact) - (630/1250/2000A)<br />

��Front<br />

��Top<br />

(Mounting hole)<br />

��Side<br />

Rated A B T<br />

630, 1250A 768 190.5 10<br />

2000A 778 185.5 20<br />

12.5kA 630A 25kA 630A 12.5kA 1250A<br />

25kA 1250, 2000A<br />

Insulation barrier<br />

(Earthing)<br />

<br />

<br />

(Unit: mm)<br />

Insulation barrier<br />

37


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

24kV dimension (Cradle)<br />

LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front ��Side<br />

��Top<br />

38<br />

(Mounting hole)<br />

Rated A B T<br />

630, 1250A 768 190.5 10<br />

2000A 778 185.5 20<br />

630A<br />

Insulation barrier<br />

1250A 2000A<br />

(Earthing)<br />

<br />

<br />

(Unit: mm)<br />

Insulation barrier


LCL-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)<br />

��Front ��Side<br />

��Top<br />

(Mounting hole)<br />

<br />

(Unit: mm)<br />

39


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

24kV dimension (Cradle)<br />

LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)<br />

��Front ��Side<br />

��Top<br />

40<br />

Note 1) ( ): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,<br />

LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.<br />

��Earthing Switch<br />

<br />

(Unit: mm)


Accessories<br />

Accessories for VCB<br />

Key lock<br />

When it is locked by a key, the closing operation is not available<br />

(electrically and mechanically) without a Key.<br />

Button padlock<br />

Button padlock protects ‘ ON’ or ‘OFF’ button when accident is occurred<br />

by operation at discretion.<br />

It is available to operate after release button padlock.<br />

Button cover<br />

Button cover protects ‘ON’ of ‘OFF’ button when accident is<br />

occurred by operation at discretion. It is available to operate by push<br />

bar.<br />

<br />

Position switch (Cell switch)<br />

Indicating the position (Run or Test) of a VCB, by mechanically<br />

pressing the switch when a VCB change the position.<br />

- RUN: 2a<br />

- TEST: 2a<br />

Note) In case that position of VCB<br />

changed to “Run” or “Test” position,<br />

“a” contact will be closed.<br />

<br />

41


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Accessories<br />

Accessories for VCB<br />

Secondary coil (Preparatory trip coil)<br />

The main coil and the preparatory coil is connected in parallel. So<br />

even though there happens a fault in the trip coil, the VCB can be<br />

tripped by one of the two trip coils.<br />

Latch checking switch<br />

When the Latch is in abnormal position, the Latch checking switch<br />

prevents the closing operation even though there is the 'Closing'<br />

signal.<br />

Charge indicator<br />

Remotely indicates the charging is completed.<br />

(Standard Feature)<br />

- Terminal No.: 9, 10<br />

Position padlock<br />

The hole to prevent the draw-in and out of a VCB from the present<br />

position.('Run' or 'Test')<br />

Standard option in the interlock lever of the E, F class draw-out type<br />

VCB. (Hole size = ∅ 8)<br />

42


Accessories for Cradle<br />

Earthing switch (for G class draw-out type only)<br />

For the safety during the maintenance of a VCB panel, discharge the<br />

charging current in the load side of a VCB with this earthing switch.<br />

Padlock of earthing switch<br />

(for G class draw-out type only)<br />

The hole to prevent the accident through carelessness earthing<br />

switch operation, the locking of the earthing switch is available when<br />

the switch is in 'OFF' position.<br />

(Hole size = ∅8)<br />

Position switch of the earthing switch<br />

(for G class draw-out type only)<br />

Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)<br />

Locking coil of earthing switch<br />

(for G class draw-out type only)<br />

To prevent the accident through carelessness earthing switch<br />

operation, the earthing switch can be changed to 'ON' position after<br />

releasing the lock by magnetizing the coils.<br />

<br />

<br />

43


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Accessories<br />

Accessories for Cradle<br />

Shutter padlock<br />

The hole to lock the shutters (load and line side) in close position, to<br />

increase the safety during the maintenance of a VCB draw-out<br />

position.<br />

(Hole size = ∅8)<br />

Mechanically operated cell switch (MOC)<br />

-for G class draw-out type only<br />

The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition<br />

of a VCB, but operated only when the VCB is in 'Run' state. (Installed<br />

in the bottom of a cradle)<br />

Truck operated cell switch (TOC)<br />

-for G class draw-out type only<br />

The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB<br />

and is operated by the movement of a VCB frame. (Installed in the<br />

bottom of a cradle)<br />

Code plate (Miss insertion prevention)<br />

-for E, F class draw-out type only<br />

To prevent the insert a VCB to a cradle, when the ratings of VCB and<br />

cradle are different.<br />

Padlock<br />

To prevent the insert draw-in/out handle to a screw hole by operating<br />

G class VCB temporarily<br />

44<br />

Note) #11, 21 are Early “b” contact<br />

Note) #11, 21 are Early “b” contact


Optional accessories<br />

Capacitor trip device (CTD)<br />

When the control power is off, the CTD supply the power for<br />

tripping a VCB.<br />

Type VCB-T1 VCB-T2<br />

Rated input voltage AC100/110V AC200/220V<br />

Tripping time Within 30 Sec. after the AC power off<br />

Voltage of the CTD DC100/110V DC200/220V<br />

��Dimension<br />

8-∅7<br />

Mounting<br />

hole<br />

90<br />

80<br />

22.5<br />

20 22.5<br />

165<br />

250<br />

��Connection circuit diagram<br />

Standard tool<br />

Pilot lamp<br />

145 11 124<br />

E, F class G class<br />

Handle for draw-in and out<br />

Handle for draw-in and out the VCB<br />

(Standard feature in the draw-out type)<br />

55<br />

2-∅35<br />

52<br />

Rectifier<br />

When the DC power is not available, rectify the AC power and<br />

get the DC power for closing coil.<br />

Type AC Input voltage Output current Rating time<br />

VCB-X<br />

��Dimension<br />

2-∅7<br />

Mounting<br />

hole<br />

100 20<br />

1∅ 100/110V<br />

1∅ 200/220V<br />

150<br />

90 94<br />

��Connection diagram<br />

40A DC 10 sec.<br />

Manual charging handle<br />

Handle for charging the spring manually.<br />

(Standard feature)<br />

35<br />

25 2-∅20<br />

45


<strong>Vacuum</strong> <strong>Circuit</strong> Breaker<br />

Types and ordering information<br />

7.2kV & 24kV<br />

Cradle<br />

46<br />

LVB 20 G 13 D 06 1A 2B B, C1, D1<br />

LG VCB<br />

Rated voltage<br />

06 7.2kV<br />

20 24kV<br />

LG Cradle<br />

Installation method<br />

P Fixed type<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

M<br />

G class draw-out type<br />

+ Bushing<br />

Breaking current<br />

13 12.5kA<br />

16 16kA<br />

20 20kA<br />

25 25kA<br />

32 31.5kA<br />

40 40kA<br />

Note) In case 24kV, only<br />

both of 12.5kA,<br />

16kA, 25kA and<br />

25kA are available.<br />

Revision No.<br />

A Conventional<br />

D Pro-MEC<br />

E Pro-MEC<br />

(Minimized type)<br />

Note) E type is available for<br />

24kV enclosed type G<br />

class only. (Distance<br />

between phase and<br />

phase is 210mm.)<br />

Breaking current<br />

8 8kA<br />

13 12.5kA<br />

16 16kA<br />

20 20kA<br />

25 25kA<br />

32 31.5kA<br />

40 40kA<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

30 3150A<br />

Note) In case 24kV, only<br />

both of 12.5kA,<br />

16kA and 25kA are<br />

available.<br />

Control voltage<br />

00 -<br />

1A DC110V<br />

1B DC220V<br />

1C DC48V<br />

1D DC24V<br />

1E DC125V<br />

Auxiliary switch<br />

00 -<br />

2B 4a4b(AMP Jack)<br />

2E 10a10b(AMP Jack)<br />

2G 4a4b(Phoenix Jack)<br />

2H 10a10b(Phoenix Jack)<br />

Note) “00”is for Earthing<br />

Truck and Dummy VCB.<br />

Accessories<br />

B Position Switch (RUN/TEST:2a2a)<br />

C1 Button Padlock (ON)<br />

C2 Button Padlock (OFF)<br />

C3 Button Padlock (ON/OFF)<br />

D1 Button Cover (ON)<br />

D2 Button Cover (OFF)<br />

D3 Button Cover (ON/OFF)<br />

Button padlock (ON)<br />

E<br />

+ Button cover (OFF)<br />

Button padlock (OFF)<br />

F<br />

+ Button cover (ON)<br />

G Key Lock<br />

Secondary Trip Coil<br />

H<br />

(Preparatory trip coil)<br />

J Fire-endurable wiring cable ass’y<br />

K Opening Latch Checking Switch<br />

P1 Dummy VCB (AMP Jack)<br />

P2 Dummy VCB ( Phoenix Jack)<br />

Q Earthing Truck (Lower)<br />

R Earthing Truck (Upper)<br />

S Pad Lock (G class)<br />

T Enclosed type, Tulip contact<br />

Optional accessories<br />

N CTD (Capacitor Trip Device)<br />

O Rectifier<br />

LCL 20 G 13 D 06 A, B, C<br />

Rated voltage<br />

06 7.2kV<br />

20 24kV<br />

Installation method<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

Revision No.<br />

A Conventional<br />

D Pro-MEC<br />

E<br />

Pro-MEC<br />

(Minimized type)<br />

Note) E type is available for<br />

24kV enclosed type G<br />

class only. (Distance<br />

between phase and<br />

phase is 210mm.)<br />

Rated current<br />

04 400A<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

30 3150A<br />

Accessories<br />

A MOC (3a4b)+ TOC (3a4b)<br />

B Earthing Switch<br />

Earthing Switch Position Switch +<br />

C<br />

Earthing Switch Locking coil<br />

T Enclosed type, Tulip contact<br />

Note) ‘A’, ‘B’, ‘C’ is for ‘G’ class only


12kV<br />

LVB 12 G 25 D 06 1A 2B B, C1, D1<br />

LG VCB<br />

Rated voltage<br />

12 12kV<br />

Cradle<br />

LG Cradle<br />

17.5kV<br />

Cradle<br />

LCL 17 G 25 D 06 A, B, C<br />

LG Cradle<br />

Rated voltage<br />

17 17.5kV<br />

Installation method<br />

G G class draw-out type<br />

M<br />

G class draw-out type<br />

+ Bushing<br />

Breaking current<br />

25 25kA<br />

32 31.5kA<br />

Revision No.<br />

D Pro-MEC<br />

Breaking current<br />

25 25kA<br />

32 31.5kA<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

Auxiliary switch<br />

2B 4a4b(AMP Jack)<br />

2E 10a10b(AMP Jack)<br />

2G 4a4b(Phoenix Jack)<br />

2H 10a10b(Phoenix Jack)<br />

LCL 12 G 25 D 06 A, B, C<br />

Rated voltage<br />

12 12kV<br />

Installation method<br />

G<br />

G class<br />

draw-out type<br />

Revision No.<br />

D Pro-MEC<br />

Control voltage<br />

1A DC110V<br />

1B DC220V<br />

1C DC48V<br />

1D DC24V<br />

1E DC125V<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

LVB 17 G 25 D 06 1E 2B B, C1, D1<br />

LG VCB<br />

Rated voltage<br />

17 17.5kV<br />

Installation method<br />

P Fixed type<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

Breaking current<br />

25 25kA<br />

Installation method<br />

E E class draw-out type<br />

F F class draw-out type<br />

G G class draw-out type<br />

Revision No.<br />

D Pro-MEC<br />

Breaking current<br />

25 25kA<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

25 2500A<br />

Revision No.<br />

D Pro-MEC<br />

Control voltage<br />

1E DC125V<br />

Auxiliary switch<br />

2B 4a4b(AMP Jack)<br />

2E 10a10b(AMP Jack)<br />

2G 4a4b(Phoenix Jack)<br />

2H 10a10b(Phoenix Jack)<br />

Rated current<br />

06 630A<br />

12 1250A<br />

20 2000A<br />

25 2500A<br />

Accessories<br />

B Position Switch (RUN/TEST:2a2a)<br />

C1 Button Padlock (ON)<br />

C2 Button Padlock (OFF)<br />

C3 Button Padlock (ON/OFF)<br />

D1 Button Cover (ON)<br />

D2 Button Cover (OFF)<br />

D3 Button Cover (ON/OFF)<br />

E Button padlock (ON)+ Button cover (OFF)<br />

F Button padlock (OFF)+ Button cover (ON)<br />

G Key Lock<br />

H Secondary Trip Coil(Preparatory trip coil)<br />

J Fire-endurable wiring cable ass’y<br />

K Opening Latch Checking Switch<br />

S Pad Lock (G class)<br />

T Enclosed type, Tulip contact<br />

Accessories<br />

A MOC (3a4b)+ TOC (3a4b)<br />

B Earthing Switch<br />

C<br />

Earthing Switch Position Switch +<br />

Earthing Switch Locking coil<br />

T Enclosed type, Tulip contact<br />

Accessories<br />

B Position Switch (RUN/TEST:2a2a)<br />

C1 Button Padlock (ON)<br />

C2 Button Padlock (OFF)<br />

C3 Button Padlock (ON/OFF)<br />

D1 Button Cover (ON)<br />

D2 Button Cover (OFF)<br />

D3 Button Cover (ON/OFF)<br />

E Button padlock (ON) + Button cover (OFF)<br />

F Button padlock (OFF) + Button cover (ON)<br />

G Key Lock<br />

H Secondary Trip Coil(Preparatory trip coil)<br />

K Opening Latch Checking Switch<br />

S Pad Lock (G class)<br />

Accessories<br />

A MOC (3a4b)+ TOC (3a4b)<br />

Note) ‘A’ is for ‘G’ class only<br />

47


<strong>Vacuum</strong> Interrupter<br />

Features & Ordering information<br />

48<br />

Features<br />

�Small Size and Light Weight<br />

�High performance, reliability, and<br />

long life are assured.<br />

�Maintains High <strong>Vacuum</strong><br />

�High-alumina ceramics provide<br />

superior mechanical strength and<br />

easy degassing.<br />

�High speed interruption and short<br />

arcing time.<br />

�The LG <strong>Vacuum</strong> Interrupter can<br />

meet all IEC, ANSI and NEMA<br />

performance standards.<br />

Ordering Information<br />

LV 07 08 0 A<br />

Basic type<br />

L LG<br />

V <strong>Vacuum</strong><br />

Rated voltage<br />

07 7.2kV<br />

/ 12kV<br />

10 15kV<br />

24 24kV<br />

Rated short<br />

circuit current<br />

04 4.5kA<br />

08 8kA<br />

12 12.5kA<br />

16 16kA<br />

20 20kA<br />

25 25kA<br />

31 31.5kA<br />

40 40kA<br />

50 50kA<br />

Ampere<br />

Below<br />

0<br />

630A<br />

1 1250A<br />

2 2000A<br />

3 3150A<br />

Revision No.


Structure<br />

The internal components of a typical <strong>Vacuum</strong> Interrupter are shown in Figure1.<br />

LG <strong>Vacuum</strong> Interrupter consists of a ceramic insulator, two end plates, arc shield,<br />

bellows, a movable and fixed electrode, and contact set.<br />

The ambient gas pressure within the evacuated tube is<br />

approximately 10-6 torr.<br />

Fixed Electrode<br />

Figure 1. <strong>Vacuum</strong> Interrupter Schematic<br />

Movable electrode<br />

Movable End Plate<br />

Bellows<br />

Bellows shield<br />

Ceramic<br />

Arc shield<br />

Contact<br />

End shield<br />

Fixed End Header<br />

49


<strong>Vacuum</strong> Interrupter<br />

Operating characteristics<br />

50<br />

Figure 2. Current flow and driving force<br />

on arc for spiral contact<br />

Fault<br />

current<br />

(ⅰ) Weld<br />

(ⅱ) Bridge explosion<br />

Arc initiation<br />

Current path<br />

Driving force on<br />

the high current<br />

ARC<br />

ARC<br />

(ⅰ) Contact jets<br />

(ⅱ) Shield involvement<br />

High current arc mode<br />

Figure 3. AC arcing and interruption phenomena in vacuum.<br />

In the closed position, normal current flows through<br />

the interrupter. When a fault occurs and interruption<br />

is required, the contacts are quickly separated.<br />

The arc drawn between the surfaces of contacts is<br />

rapidly moved around the slotted contact surface<br />

by self induced magnetic effects, preventing gross<br />

contact erosion and the formation of hot spot on<br />

the surface.<br />

The arc burns in an ionized metal vapor, which<br />

condenses on the surrounding metal shield. At<br />

current zero the arc extinguishes and vapor<br />

production ceases.<br />

The metal vapor plasma is very rapidly dispersed,<br />

cooled, recombined, and deionized, and the metal<br />

vapor products are quickly condensed so that the<br />

contacts withstand the transient recovery voltage.<br />

(ⅰ) Arc instability<br />

(ⅱ) Interruption<br />

Current<br />

zero<br />

Time (ms) Time (㎲)<br />

Recovery<br />

voltage<br />

Voltage Phenomena<br />

(ⅰ) Arc reignition<br />

(ⅱ) Restrikes<br />

(ⅲ) B. I. L<br />

(ⅳ) AC voltage<br />

withstand


Ratings and Specifications<br />

Electrical ratings<br />

Mechanical data<br />

Mechanical requirements<br />

Type LV-07040A LV-07080 LV-07130 LV-07251B<br />

Outer view<br />

Rated voltage (kV)<br />

Rated power frequency withstand voltage (kV, rms)<br />

Rated impulse withstand voltage (kV, crest)<br />

Rated frequency (Hz)<br />

Rated normal current (Amp)<br />

Rated short circuit current (Sym.) (kA)<br />

Rated short circuit making current (kA, peak)<br />

Rated duration of short-circuit (sec)<br />

Interrupter weight (kg)<br />

Moving part weight (kg)<br />

Outline dimension (mm) a<br />

Contact stroke (mm)<br />

Opening speed, average 0 to 75% of full stroke (m/s)<br />

Overtravel during opening, Max. (mm)<br />

Closing speed, average last 33% of full stroke (m/s)<br />

Contact bounce duration, Max. (sec)<br />

Added force from atmospheric pressure (kg�f)<br />

Contact force from atmospheric pressure (kg�f)<br />

Contact erosion limit (mm)<br />

Mechanical life (×10 4 , Operations)<br />

b<br />

c<br />

3.6 7.2 7.2 7.2 7.2<br />

11.5 20 20 20 20<br />

60 60 60 60<br />

50/60 50/60 50/60 50/60<br />

400 630 630 1,250<br />

4.5 8 12.5 20 25<br />

- 20.8 32.5 52 65<br />

- 3 3 3<br />

0.48 0.83 0.85 1.8<br />

0.19 0.4 0.4 0.6<br />

114 132 132 190<br />

78 92 92 123<br />

62 62 62 79<br />

3 5 6 6 8<br />

0.6 0.7~1.0 0.7~1.0 0.7~1.0<br />

1 2 2 2<br />

0.3 0.7~1.0 0.7~1.0 0.7~1.0<br />

0.002 0.002 0.002 0.002<br />

5 50 80 154 227<br />

9 9.1 9.1 15.9<br />

1 3 3 3<br />

100 3 3 3<br />

51


<strong>Vacuum</strong> Interrupter<br />

Ratings and Specifications<br />

Electrical ratings<br />

Mechanical data<br />

Mechanical requirements<br />

52<br />

Type LV-07251 LV-10252 LV-10312 LV-10403<br />

Outer view<br />

Rated voltage (kV)<br />

Rated power frequency withstand voltage (kV, rms)<br />

Rated impulse withstand voltage (kV, crest)<br />

Rated frequency (Hz)<br />

Rated normal current (Amp)<br />

Rated short circuit current (Sym.) (kA)<br />

Rated short circuit making current (kA, peak)<br />

Rated duration of short-circuit (sec)<br />

Interrupter weight (kg)<br />

Moving part weight (kg)<br />

Outline dimension (mm) a<br />

Contact stroke (mm)<br />

Opening speed, average 0 to 75% of full stroke (m/s)<br />

Overtravel during opening, Max. (mm)<br />

Closing speed, average last 33% of full stroke (m/s)<br />

Contact bounce duration, Max. (sec)<br />

Added force from atmospheric pressure (kg�f)<br />

Contact force from atmospheric pressure (kg�f)<br />

Contact erosion limit (mm)<br />

Mechanical life (×10 4 , Operations)<br />

b<br />

c<br />

12 15 7.2 12 15 17.5 7.2 12 15 17.5<br />

28 36 20 28 36 50 20 28 36 50<br />

95 60 95 95 60 95<br />

50/60 50/60 50/60 50/60<br />

1,250 2,000 2,000 3,150<br />

25 20 25/31.5 31.5 40<br />

65 52 65/81.9 81.9 104<br />

3 3 3 3<br />

1.9 4.1 4.3 6.4<br />

0.7 0.84 0.9 1.7<br />

209 230 230 257(272)<br />

169 181 181 213<br />

79 103 108 135<br />

8 12 8 10 12 8 12<br />

1.0~1.3 0.7~1.0 1.0~1.3 1.2~1.6 0.7~1.0 1.0 1.2<br />

2 2 1.5 3 3 1.5<br />

0.7~1.0 0.7~1.0 0.7~1.0 0.7~1.0<br />

0.002 0.002 0.002 0.002<br />

227 154 227/306 306 367<br />

15.9 16.8 16.8 25<br />

3 3 3 3<br />

3 1 5 3 1 5 2


LV-24120 LV-24121 LV-24252 LV-24403 LV-12503 LV-25000<br />

24 24 24 25.8 24 25.8 4.76 12 25.8<br />

50 50 50 70 19 48 60<br />

125 125 125 150 60 95 125<br />

50/60 50/60 50/60 50/60 50/60 50/60<br />

630 1,250 2,000 3,150 3,150 600<br />

12.5 12.5 16 25 40 31.5 50 0.6<br />

32.5 32.5 41.6 65 101 81.9 130 32.5<br />

3 3 3 3 3 1<br />

1.7 2.6 5.0 6.4 7.6 0.91<br />

0.4 0.7 1 1.7 2.9 0.36<br />

235 235 270 272 272 212<br />

163 174 225 213 213 145<br />

75 95 108 135 135 62<br />

15 15 17 17 10 9.5<br />

1.0~1.3 1.0~1.3 1.0~1.3 1.0~1.3 1.2~1.5 0.9~1.1<br />

2 2 1.5 1.5 3 1.5<br />

0.7~1.0 0.7~1.0 0.7~1.0 1.0~1.3 0.7~1.0 0.76<br />

0.002 0.002 0.002 0.002 0.002 1.002<br />

80 80 120 227 367 306 380 57<br />

9.1 15.9 16.8 25 25 9.1<br />

3 3 3 3 2 2.54<br />

1 1 1 1 2 1<br />

53


<strong>Vacuum</strong> Interrupter<br />

Dimensions<br />

54<br />

LV-07040A LV-07080/LV-07130 LV-07251<br />

LV-07251B LV-10252/LV-10312 LV-10403<br />

Note) LV-10312 ∅108<br />

Note)


LV-12503 LV-24120 LV-24121A<br />

LV-24252A LV-24403 LV-25000<br />

55


�� HEAD OFFICE<br />

2004. AUG-2<br />

Safety Instructions<br />

LG TWIN TOWERS, 20 Yoido-dong, Youngdungpo-gu,<br />

Seoul, 150-721, Korea<br />

Tel. (82-2)3777-4870<br />

Fax. (82-2)3777-4713<br />

http://www.lgis.com<br />

Specifications in this catalog are subject to change without notice due to<br />

continuous product development and improvement.<br />

Leader in Electrics & Automation<br />

�� For your safety, please read user's manual thoroughly before operating.<br />

�� Contact the nearest authorized service facility for examination, repair, or adjustment.<br />

�� Please contact a qualified service technician when you need maintenance.<br />

Do not disassemble or repair by yourself!<br />

�� Any maintenance and inspection shall be performed by the personnel having expertise concerned.<br />

www.lgis.com<br />

�� Global Network<br />

��LG Industrial Systems Tokyo Office Japan<br />

Address: 16F, Higashi-Kan, Akasaka Twin Towers 17-22, 2-chome,<br />

Akasaka, Minato-ku Tokyo 107-8470, Japan<br />

Tel: 81-3-3582-9128 Fax: 81-3-3582-0065 e-mail: dongjins@lgis.com<br />

��LG Industrial Systems Dubai office UAE<br />

Address: P.O.Box-114216, API World Tower, 303B, Sheikh Zayed road, Dubai, UAE.<br />

Tel: 971-4-3328289 Fax: 971-4-3329444 e-mail: hwyim@lgis.com<br />

��LG-VINA Industrial Systems Co., Ltd Vietnam<br />

Address: LGIS VINA Congty che tao may dien Viet-Hung Dong Anh Hanoi, Vietnam<br />

Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@hn.vnn.vn<br />

��LG Industrial Systems Hanoi Office Vietnam<br />

Address: Room C21, 5Th Floor, Horison Hotel, 40 Cat Linh , Hanoi, Vietnam<br />

Tel: 84-4-736-6270/1 Fax: 84-4-736-6269<br />

��Dalian LG Industrial Systems Co., Ltd China<br />

Address: No. 15 Liaohexi 3 Road, economic and technical<br />

development zone, Dalian, China<br />

Tel: 86-411-8731-8210 Fax: 86-411-8730-7560 e-mail: youngeel@lgis.com<br />

��LG Industrial Trading (Shanghai) Co., Ltd China<br />

Address: Room 1705-1707, 17th Floor Xinda Commercial Building No 322,<br />

Xian Xia Road Shanahai, China<br />

Tel: 86-21-6252-4291 Fax: 86-21-6278-4372 e-mail: hgseo@lgis.com<br />

��LG Industrial Systems Beijing Office China<br />

Address: Room 303, 3F North B/D, EAS 21 XIAO YUN ROAD,<br />

Dong San Huan Bei Road, Chao Yang District, Beijing, China<br />

Tel: 86-10-6462-3259/4 Fax: 86-10-6462-3236 e-mail: sclim@mx.cei.gov.cn<br />

��LG Industrial Systems Shanghai Office China<br />

Address: Room 1705-1707, 17th Floor Xinda Commercial Building<br />

No 318, Xian Xia Road Shanahai, China<br />

Tel: 86-21-6278-4370 Fax: 86-21-6278-4301 e-mail: sdhwang@lgis.com<br />

��LG Industrial Systems Guangzhou Office China<br />

Address: Room 303, 3F, Zheng Sheng Building, No 5-6, Tian He<br />

Bei Road, Guangzhou, China<br />

Tel: 86-20-8755-3410 Fax: 86-20-8755-3408<br />

e-mail: lgisgz@public1.guangzhou.gd.cn<br />

<strong>Vacuum</strong> <strong>Circuit</strong> <strong>Breakers</strong>(E) 2004. 08/(01) 2004. 08 Printed in Korea STAFF