<strong>Weishaupt</strong> industrial burners<br />

WK40 to WK70<br />

for combustion air temperatures up to 250°C<br />

1/2000 CA


General<br />

<strong>Weishaupt</strong> WK type industrial<br />

burners were developed to meet<br />

special industrial and commercial<br />

requirements. The burners are<br />

suited for operation with or<br />

without preheated combustion air<br />

as required. Very high flue gas<br />

temperatures occur on many<br />

industrial processes (e.g. thermal<br />

fluid boilers) due to the high<br />

media temperatures. A<br />

considerable amount of energy<br />

can be recovered from the hot flue<br />

gases by using a heat exchanger<br />

in the flue gas system to recover<br />

the heat. This technology can<br />

result in improvements in<br />

efficiency of up to 8%.<br />

The burners are also often used on<br />

installations without preheated<br />

combustion air. Reasons for this could be<br />

as follows:<br />

● The customer requires a separate<br />

combustion air fan.<br />

● An industrial burner is specified.<br />

● The resistances in the heat exchanger<br />

are too high to use a monobloc burner.<br />

● The combustion rating is too high to<br />

use a monobloc burner.<br />

Burner types WK40 and WK50<br />

Burners operating with preheated<br />

combustion air are supplied with an<br />

insulated burner housing and a coolingair<br />

fan unit, for which a separate coolingair<br />

fan is supplied. An oil pump is fitted<br />

on oil and dual fuel (oil/gas) burners and<br />

residual oil burners are further equipped<br />

with an electric preheater. On request,<br />

the WK 40 burner can be supplied with a<br />

separate pump and preheater assembly -<br />

this is often the case with industrial<br />

installations. The burner housing is not<br />

insulated for burners operating at normal<br />

combustion air temperatures.<br />

Burner type WK70<br />

Burners operating either at normal<br />

combustion air temperatures or with<br />

preheated combustion air are both fitted<br />

with internal insulation as standard. For<br />

burners operating at normal combustion<br />

air temperatures the internal insulation<br />

serves as a sound absorber and<br />

consequently the burner noise level is<br />

below 85 dB(A). The pump and<br />

preheater assembly is supplied<br />

separately.<br />

Combustion air<br />

max. 250° C<br />

Picture showing boiler, heat exchanger and <strong>Weishaupt</strong> Industrial Burner<br />

Insulated burner housing for<br />

preheated combustion air<br />

The insulation of the burner housing<br />

prevents the emission of temperature<br />

and noise. Even with combustion air<br />

temperatures of 250 C, the surface<br />

temperature of the housing is less than<br />

100 C. On WK40 burners the oil pump<br />

and, where applicable, the oil preheater<br />

are fitted away from the burner housing<br />

and are thus protected from the heat. A<br />

separate cooling air fan is supplied to<br />

cool the control unit and the flame<br />

monitoring device.<br />

Tried and tested components<br />

Sizes 50 to 70 have the same mixing<br />

assembly as is used on the size 50 to 70<br />

Monarch burners.<br />

Simple maintenance<br />

Diffuser, ignition electrodes and the gas<br />

mixing assembly are easily accessible<br />

when the cover is opened. The flame<br />

tube can also be taken out through the<br />

opening in the housing once the mixing<br />

assembly has been removed. The oil, gas<br />

and air regulating components are neatly<br />

arranged and are easily accessible.<br />

Flue gas<br />

Combustion air<br />

fan<br />

Heat exchanger<br />

Boiler<br />

Burner<br />

Fuels<br />

The oil burners fire distillate and residual<br />

fuel oils to DIN 51 603 with a viscosity<br />

up to 6 mm 2 /s at 20°C (distillate oil EL)<br />

or 50 mm 2 /s at 100°C (residual oil S).<br />

The gas and dual fuel burners are tested<br />

for use with the following gases to EN<br />

437 and DVGW Worksheet G260/I:<br />

natural gas E (formerly designated<br />

natural gas H) and natural gas LL<br />

(formerly designated natural gas L), as<br />

well as liquid petroleum gas.<br />

General<br />

Standard execution burners (material,<br />

construction and protection) are<br />

designed for operation indoors within a<br />

temperature range of -10°C to +40°C<br />

(details on special measures for oil<br />

storage in sub-zero temperatures and on<br />

operation outdoors are available on<br />

request). There are various special<br />

executions available on request, such as<br />

additional equipment to comply with TRD<br />

<strong>604</strong> or new technologies such as<br />

electronic compound regulation (ECR),<br />

O 2 trim and speed control.<br />

2


Improvement in<br />

“combustion efficiency”<br />

through heat recovery<br />

Efficiency in % with flue gas temperature at 300°C/400°C in<br />

relation to the combustion air temperature with air factor n = 1.1<br />

250<br />

200<br />

Combustion air preheating °C<br />

150<br />

100<br />

50<br />

t A = 300°C<br />

0<br />

92 91 90 89 88 87 86 85 84 83 82 81<br />

t A = 400°C<br />

Efficiency %<br />

Combustion efficiency without air preheating<br />

Combustion air with air preheating<br />

H u,n – V A,f · n · C¯¯ pA · t A<br />

ηF = ·100 %<br />

H u,n<br />

H u,n – V A,f · n · C¯¯ pA · t A + V L · n · C¯¯ pL · t L<br />

ηF = ·100 %<br />

H u,n<br />

with gas with oil<br />

H u,n = nett calorific value kJ/m 3 kJ/kg<br />

V A,f = combustion volume wet m 3 /m 3 m 3 /kg<br />

V L = theoretical air requirement m 3 /m 3 m 3 /kg<br />

n = air factor<br />

t A = flue gas temperature °C<br />

C¯¯ pA = average specific heat capacity of flue gas kJ/m 3<br />

with gas with oil<br />

H u,n = nett calorific value kJ/m 3 kJ/kg<br />

V A,f = combustion volume wet m 3 /m 3 m 3 /kg<br />

V L = theoretical air requirement m 3 /m 3 m 3 /kg<br />

n = air factor<br />

t A = flue gas temperature °C<br />

t L = combustion air temperature °C<br />

C¯¯ pA = average specific heat capacity of flue gas kJ/m 3<br />

C¯¯ pL = average specific heat capacity of<br />

combustion air kJ/m 3<br />

Example without air preheating:<br />

H u,n = 10.35 kWh/m 3 =ˆ 37 261 kJ/m 3<br />

V A,f = 10.82 m 3 /m 3<br />

V L = 9.91 m 3 /m 3<br />

n = 1.1<br />

t A = 400°C<br />

C¯¯ pA = 1.424 kJ/m 3<br />

ηF =<br />

37 261 – 10.82 · 1.1 · 1.424 · 400<br />

37 261<br />

· 100 %<br />

ηF = 81.8 %<br />

Example with air preheating:<br />

H u,n = 10.35 kWh/m 3 =ˆ 37 261 kJ/m 3<br />

V A,f = 10.82 m 3 /m 3<br />

V L = 9.91 m 3 /m 3<br />

n = 1.1<br />

t A = 400°C<br />

t L = 250°C<br />

C¯¯ pA = 1.424 kJ/m 3<br />

C¯¯ pL = 1.315 kJ/m 3<br />

ηF =<br />

37 261–10.82 ·1.1 ·1.424 · 400 + 9.91·1.315·250<br />

37 261<br />

·100%<br />

ηF = 91.4 %<br />

Result:<br />

Improvement of “combustion efficiency” by 9.6% through air preheating<br />

3


Description<br />

Regulation<br />

The burners alter their capacity<br />

proportionally, depending on the heat<br />

requirement. Depending on the type of<br />

control the burner is either:<br />

■ sliding two stage (basic version)<br />

■ modulating<br />

The servomotor run time between partial<br />

and full load is 42 seconds. With sliding<br />

two stage regulation, the partial and full<br />

load positions are fixed within the<br />

regulating range. Depending on heat<br />

demand, the burner slides to one load<br />

point to the other, thus preventing rapid<br />

cycling.<br />

By fitting a suitable controller into the<br />

control panel the standard sliding two<br />

stage burner can be fully modulating.<br />

Modulating burners operate at any load<br />

point within the burner range, depending<br />

on the heat required.<br />

WKGL40/2-A<br />

Increased safety due to nozzle head<br />

shut off device with nozzle solenoid<br />

A type tested shut off device is fitted in<br />

the nozzle and shuts off the oil flow<br />

directly in the nozzle orifice. No fuel oil<br />

can leave the nozzle head, thus<br />

increasing safety.<br />

Nozzle recirculation on residual oil<br />

burners<br />

During prepurge on residual oil burners,<br />

heated oil circulates through the nozzle<br />

and oil line system so that on flame<br />

establishment the oil is at the correct<br />

temperature.<br />

Precise oil temperature regulation<br />

with a <strong>Weishaupt</strong> oil preheater<br />

<strong>Weishaupt</strong> residual oil burners are fitted<br />

with oil preheaters, which maintain the<br />

preheated temperature and thus the fuel<br />

viscosity constantly at the desired set<br />

value. This results in uniform atomisation<br />

and combustion efficiency.<br />

WKGL40/2-A<br />

Flame supervision<br />

The burner control box, which is fitted in<br />

the control panel, sequences burner<br />

operation automatically. It monitors the<br />

flame by means of a flame sensor.<br />

4


Model overview<br />

Types of regulation<br />

WKGL 70/2-A<br />

WKGL 70/2-A<br />

5


Description, installation example<br />

Burner types WK40 and WK50<br />

Burners operating with preheated<br />

combustion air are supplied with an<br />

insulated burner housing and a coolingair<br />

fan unit, for which a separate coolingair<br />

fan is supplied. An oil pump is fitted<br />

on oil and dual fuel (oil/gas) burners and<br />

residual oil burners are further equipped<br />

with an electric preheater. On request,<br />

the WK 40 burner can be supplied with a<br />

separate pump and preheater assembly -<br />

this is often the case with industrial<br />

installations. The burner housing is not<br />

insulated for burners operating at normal<br />

combustion air temperatures.<br />

Burner type WK70<br />

Burners operating either at normal<br />

combustion air temperatures or with<br />

preheated combustion air are both fitted<br />

with internal insulation as standard. For<br />

burners operating at normal combustion<br />

air temperatures the internal insulation<br />

serves as a sound absorber and<br />

consequently the burner noise level is<br />

below 85 dB(A). The pump and<br />

preheater assembly is supplied<br />

separately.<br />

Remote heating centre with <strong>Weishaupt</strong> WKGL50 and WKGL3 dual fuel burners - total rating 28 MW<br />

6<br />

WKGL50 - Service-friendly compact construction


<strong>Weishaupt</strong> control panel type WS 1218/40<br />

7


Model and capacity overview<br />

Type WK40 - standard version<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 500 1000 1500 2000 2500 3000 kW<br />

WKL40/1 ZM Oil 450 – 2200 38 – 185<br />

ZMH Oil 450 – 1800 38 – 152<br />

WKMS40/1 ZM Oil 550 – 2200 50 – 195<br />

ZMH Oil 550 – 1800 50 – 160<br />

WKG40/1 ZM N-Gas, LPG 300 – 2200<br />

ZMH N-Gas, LPG 300 – 1800<br />

WKGL40/1 ZM Oil 450 – 2200 38 – 185<br />

ZMH Oil 450 – 1800 38 – 152<br />

ZM N-Gas, LPG 300 – 2200<br />

ZMH N-Gas, LPG 300 – 1800<br />

WKGMS40/1 ZM Oil 550 – 2200 50 – 195<br />

ZMH Oil 550 – 1800 50 – 160<br />

ZM N-Gas, LPG 300 – 2200<br />

ZMH N-Gas, LPG 300 – 1800<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

1200 kW<br />

WKL40/2 ZM Oil 650 – 3000 55 – 250<br />

ZMH Oil 650 – 2500 55 – 210<br />

WKMS40/2 ZM Oil 750 – 3000 67 – 266<br />

ZMH Oil 750 – 2500 67 – 222<br />

WKG40/2 ZM N-Gas, LPG 400 – 3000<br />

ZMH N-Gas, LPG 400 – 2500<br />

WKGL40/2 ZM Oil 650 – 3000 55 – 250<br />

ZMH Oil 650 – 2500 55 – 210<br />

ZM N-Gas, LPG 400 – 3000<br />

ZMH N-Gas, LPG 400 – 2500<br />

WKGMS40/2 ZM Oil 750 – 3000 67 – 266<br />

ZMH Oil 750 – 2500 67 – 222<br />

ZM N-Gas, LPG 400 – 3000<br />

ZMH N-Gas, LPG 400 – 2500<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

1800 kW<br />

20°C combustion air temperature<br />

250°C combustion air temperature<br />

The full-tone and half-tone areas together show the total ratings<br />

range. When sizing burners ensure that the required nominal rating<br />

lies within one of the full-tone areas.<br />

N-Gas = Natural Gas E/LL<br />

LPG = Liquid Petroleum Gas B/P<br />

8


Model and capacity overview<br />

Type WK50 - standard version<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 1000 2000 3000 4000 5000 6000 kW<br />

WKL50/1 ZM Oil 712 – 4000 60 – 337<br />

ZMH Oil 712 – 3200 60 – 270<br />

WKMS50/1 ZM Oil 1012 – 4000 90 – 356<br />

ZMH Oil 1012 – 3200 90 – 285<br />

WKG50/1 ZM N-Gas, LPG 600 – 4000<br />

ZMH N-Gas, LPG 600 – 3200<br />

WKGL50/1 ZM Oil 712 – 4000 60 – 337<br />

ZMH Oil 712 – 3200 60 – 270<br />

ZM N-Gas, LPG 600 – 4000<br />

ZMH N-Gas, LPG 600 – 3200<br />

WKGMS50/1 ZM Oil 1012 – 4000 90 – 356<br />

ZMH Oil 1012 – 3200 90 – 285<br />

ZM N-Gas, LPG 600 – 4000<br />

ZMH N-Gas, LPG 600 – 3200<br />

WKL50/2 ZM Oil 1125 – 6000 95 – 506<br />

ZMH Oil 1125 – 5000 95 – 420<br />

WKMS50/2 ZM Oil 1700 – 6000 150 – 534<br />

ZMH Oil 1700 – 5000 150 – 445<br />

WKG50/2 ZM N-Gas, LPG 800 – 6000<br />

ZMH N-Gas, LPG 800 – 5000<br />

WKGL50/2 ZM Oil 1125 – 6000 95 – 506<br />

ZMH Oil 1125 – 5000 95 – 420<br />

ZM N-Gas, LPG 800 – 6000<br />

ZMH N-Gas, LPG 800 – 5000<br />

WKGMS50/2 ZM Oil 1700 – 6000 150 – 534<br />

ZMH Oil 1700 – 5000 150 – 445<br />

ZM N-Gas, LPG 800 – 6000<br />

ZMH N-Gas, LPG 800 – 5000<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

Explanation of model designation<br />

WKG 40 / 1, version ZMH<br />

Index No. Preheated air version<br />

for capacity Mode of operation:<br />

range Sliding two stage<br />

Size<br />

(servomotor with 20 s runtime)<br />

Fuel:<br />

modulating<br />

L = distillate oil EL (servomotor with 42 s run time)<br />

MS = residual oil MS<br />

G = Gas<br />

<strong>Weishaupt</strong> burner series<br />

9


Model and capacity overview<br />

Type WK70 - standard version<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 2000 4000 6000 8000 10000 120000 kW<br />

WKL70/1-B ZM Oil 1200 – 7000 100 – 590<br />

ZMH Oil 1200 – 5600 100 – 472<br />

WKMS70/1-B ZM Oil 1800 – 7000 160 – 623<br />

ZMH Oil 1800 – 5600 160 – 498<br />

WKG70/1-B ZM N-Gas 1100 – 7000<br />

ZMH N-Gas 1100 – 5600<br />

WKGL70/1-B ZM Oil 1200 – 7000 100 – 590<br />

ZMH Oil 1200 – 5600 100 – 472<br />

ZM N-Gas 1100 – 7000<br />

ZMH N-Gas 1100 – 5600<br />

WKGMS70/1-BZM Oil 1800 – 7000 160 – 623<br />

ZMH Oil 1800 – 5600 160 – 498<br />

ZM N-Gas 1100 – 7000<br />

ZMH N-Gas 1100 – 5600<br />

WKL70/2-A ZM Oil 1800 –12000 150 –1012<br />

ZMH Oil 1800 – 9600 150 – 810<br />

WKMS70/2-A ZM Oil 2150 –12000 190 –1068<br />

ZMH Oil 2150 – 9600 190 – 854<br />

WKG70/2-A ZM N-Gas 1400 –12000<br />

ZMH N-Gas 1400 – 9600<br />

WKGL70/2-A ZM Oil 1800 –12000 150 –1012<br />

ZMH Oil 1800 – 9600 150 – 810<br />

ZM N-Gas 1400 –12000<br />

ZMH N-Gas 1400 – 9600<br />

WKGMS70/2-AZM Oil 2150 –12000 190 –1068<br />

ZMH Oil 2150 – 9600 190 – 854<br />

ZM N-Gas 1400 –12000<br />

ZMH N-Gas 1400 – 9600<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

4000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

20°C combustion air temperature<br />

250°C combustion air temperature<br />

The full-tone and half-tone areas together show the total ratings<br />

range. When sizing burners ensure that the required nominal rating<br />

lies within one of the full-tone areas.<br />

The capacity ranges are based on an installation altitude of 500 m<br />

above sea level.<br />

N-Gas = Natural Gas E/LL<br />

LPG = Liquid Petroleum Gas B/P<br />

10


Model and capacity overview<br />

Type WK50 - NR version<br />

Type WK70 - NR version<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 1000 2000 3000 4000 5000 6000 kW<br />

WKG50/1 ZM-NR N-Gas, LPG 600 – 4000<br />

ZMH-NR N-Gas, LPG 600 – 3200<br />

WKGL50/1 ZM-NR Oil 712 – 4000 60 – 337<br />

ZMH-NR Oil 712 – 3200 60 – 270<br />

ZM-NR N-Gas, LPG 600 – 4000<br />

ZMH-NR N-Gas, LPG 600 – 3200<br />

WKG50/2 ZM-NR N-Gas, LPG 800/950 – 6000<br />

ZMH-NR N-Gas, LPG 800/950 – 5000<br />

WKGL50/2 ZM-NR Oil 1125 – 6000 95 – 506<br />

ZMH-NR Oil 1125 – 5000 95 – 420<br />

ZM-NR N-Gas, LPG 800/950 – 6000<br />

ZMH-NR N-Gas, LPG 800/950 – 5000<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 2000 4000 6000 8000 10000 120000 kW<br />

WKG70/1 ZM-NR N-Gas, LPG 1400 – 12000<br />

7000 kW<br />

ZMH-NR N-Gas, LPG 1400 – 9600<br />

5000 kW<br />

WKGL70/1-B ZM-NR Oil 1200 – 7000 100 – 590<br />

ZM-NR Oil 1200 – 5600 100 – 472<br />

4000 kW<br />

4000 kW<br />

ZM-NR N-Gas, LPG 1100 – 7000<br />

ZMH-NR N-Gas, LPG 1100 – 5600<br />

4000 kW<br />

4000 kW<br />

WKG70/2 ZM-NR N-Gas 1400 – 12000<br />

LPG 2000 – 12000<br />

ZMH-NR N-Gas 1400 – 9600<br />

LPG 2000 – 9600<br />

WKG70/2-A ZM-NR Oil 1800 – 12000 150 – 1012<br />

ZMH-NR Oil 1800 – 9600 150 – 810<br />

ZM-NR N-Gas 1400 – 12000<br />

LPG 2000 – 12000<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

Explanation of model designation<br />

WKG 40 / 1, version ZMH<br />

Index No. for Preheated air version<br />

capacity Mode of operation:<br />

range Sliding two stage<br />

Size<br />

(servomotor with 20 s runtime)<br />

Fuel:<br />

modulating<br />

L = distillate oil EL (servomotor with 42 s run time)<br />

MS = residual oil MS<br />

G = Gas<br />

<strong>Weishaupt</strong> burner series<br />

11


Model and capacity overview<br />

Type WK50 - version 1LN<br />

Type WK70 - versions LN/1LN<br />

<strong>Weishaupt</strong> Corporation<br />

6280 Danville Road<br />

Mississauga, ON L5T 2H7<br />

Ph: (905) 564 0946, Fax: (905) 564 0949<br />

www.weishaupt-corp.com<br />

Print No. 83006816, November 2000<br />

Printed in Germany. All rights reserved.<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 1000 2000 3000 4000 5000 6000 kW<br />

WKG50/1 ZM-1LN N-Gas, LPG 600 – 3600<br />

ZMH-1LN N-Gas, LPG 600 – 3000<br />

WKGL50/1 ZM-1LN Oil 800 – 3600 67 – 302<br />

ZMH-1LN Oil 800 – 3000 67 – 252<br />

ZM-1LN N-Gas, LPG 600 – 3600<br />

ZMH-1LN N-Gas, LPG 600 – 3000<br />

WKG50/2 ZM-1LN N-Gas, LPG 800/950 – 5500<br />

ZMH-1LN N-Gas, LPG 800/950 – 4800<br />

WKGL50/2 ZM-1LN Oil 1125 – 5500 95 – 462<br />

ZMH-1LN Oil 1125 – 4800 95 – 403<br />

ZM-1LN N-Gas, LPG 800/950 – 5500<br />

ZMH-1LN N-Gas, LPG 800/950 – 4800<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2000 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

2500 kW<br />

Burner Version Fuel Capacity range<br />

type kW kg/h 0 2000 4000 6000 8000 10000 120000 kW<br />

WKG70/1-B ZM-LN N-Gas 1200 – 7000<br />

ZMH-LN N-Gas 1200 – 5600<br />

3000 kW<br />

3000 kW<br />

WKG70/2-A ZM-LN N-Gas 1750 – 11000<br />

ZMH-LN N-Gas 1750 – 8800<br />

WKG70/2 ZM-1LN N-Gas 1100–12000<br />

ZMH-1LN N-Gas 1100– 9600<br />

ZM-1LN LPG 1400–12000<br />

ZMH-1LN LPG 1400– 9600<br />

WKGL70/2 ZM-1LN Oil 1900–12000 160–1012<br />

ZMH-1LN Oil 1900– 9600 160– 810<br />

ZM-1LN N-Gas 1100–12000<br />

LPG 1400–12000<br />

ZMH-1LN N-Gas 1100– 9600<br />

LPG 1400– 9600<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

5000 kW<br />

20°C combustion air temperature<br />

250°C combustion air temperature<br />

The full-tone and half-tone areas together show the total ratings<br />

range. When sizing burners ensure that the required nominal rating<br />

lies within one of the full-tone areas.<br />

The capacity ranges are based on an installation altitude of 500 m<br />

above sea level.<br />

N-Gas = Natural Gas E/LL<br />

LPG = Liquid Petroleum Gas B/P