Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
10/138<br />
Technical data<br />
Undervoltage releases, shunt releases<br />
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />
NZM…-XU, NZM…-XA…<br />
<strong>NZM1</strong>(2/3)-XU...<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
NZM4-XU…<br />
Undervoltage release<br />
Rated control voltage<br />
Alternating voltage at 50/60 Hz U s V AC 24…600 24…600<br />
DC U s V DC 12…250 12…250<br />
Operating range<br />
Drop-out voltage x U s 0.35 – 0.7 0.35 – 0.7<br />
Pick-<strong>up</strong> voltage x U s 0.85 – 1.1 0.85 – 1.1<br />
Power consumption<br />
AC<br />
Pick-<strong>up</strong> AC VA 1.5 3.6<br />
Sealing AC VA 1.5 3.6<br />
DC<br />
Pick-<strong>up</strong> DC W 0.8 2.5<br />
Sealing DC W 0.8 2.5<br />
Max. opening delay (response time until the main circuits<br />
ms 19 23<br />
open)<br />
Minimum command time ms 10 – 15 10 … 15<br />
Terminal capacities<br />
Solid or flexible conduc<strong>to</strong>r with ferrule mm 2 1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
AWG 1 x (18 … 14)<br />
2 x (18 … 14)<br />
1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
1 x (18 … 14)<br />
2 x (18 … 14)<br />
http://catalog.moeller.net<br />
UVU-NZM<br />
Undervoltage releases, off-delayed<br />
Rated operational voltage<br />
Alternating voltage at 50/60 Hz U e V AC 24, 220 – 550<br />
DC U e V DC 24<br />
Inrush current (peak value) I e mA < 500<br />
Power consumption VA 50<br />
Delay time t sd ms 70 – 4000<br />
With additional external capaci<strong>to</strong>r, 90.000 μF f 35 V s To 16<br />
With additional external capaci<strong>to</strong>r, 30.000 μF f 35 V s To 8<br />
Terminal capacities<br />
Solid or flexible conduc<strong>to</strong>r with ferrule mm 2 1 x (0.5 – 2.5)<br />
2 x (0.5 – 1.5)<br />
<strong>NZM1</strong>(2/3)-XA... NZM4-XA... NZM2/3-XA...-MNS NZM4-XA…-MNS<br />
Shunt release<br />
Rated control voltage<br />
AC U s V AC 12…440 12…440 230 230<br />
DC U s V DC 12…440 12…440<br />
Frequency range Hz 0 – 400 0 – 400 50/60 50/60<br />
Operating range<br />
AC x U s 0.7…1.1 0.7…1.1 0.1…1.1 0.1…1.1<br />
DC x U s 0.7…1.1 0.7…1.1<br />
Power consumption<br />
Pick-<strong>up</strong> AC/DC VA/W 2.5 2.5 – –<br />
Sealing AC/DC VA/W 2.5 2.5 – –<br />
Maximum current consumption at 110% U s (230 V 50 Hz) A – – 0.5 1<br />
Max. opening delay (response time until the main circuits ms 20 22 20 22<br />
open)<br />
Duty fac<strong>to</strong>r ms L L 1000 ms 1000 ms<br />
Minimum command time ms 10 … 15 10 … 15 10 … 15 10 … 15<br />
Terminal capacities<br />
Solid or flexible conduc<strong>to</strong>r with ferrule mm 2 1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
AWG 1 x (18 … 14)<br />
2 x (18 … 14)<br />
1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
1 x (18 … 14)<br />
2 x (18 … 14)<br />
1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
1 x (18 … 14)<br />
2 x (18 … 14)<br />
1 x (0.75 … 2.5)<br />
2 x (0.75 … 2.5)<br />
1 x (18 … 14)<br />
2 x (18 … 14)<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616