Technical data<br />

Temperature influence<br />

10/131<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Device Type<br />

Release<br />

type<br />

Reduction of the rated operational current (derating) under particular ambient<br />

conditions (according <strong>to</strong> IEC 947)<br />

Derating coefficient<br />

20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C<br />

Electronic release (E)<br />

System protection<br />

NZM...3(-4)-AE(F)250...500(-NA) E 1 1 1 1 1 1 1<br />

NZM...3(-4)-AE(F)550...630(-NA) E 1 1 1 1 0.9 0.85 0.8<br />

NZM...3(-4)-AE250...400 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...3(-4)-AE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73<br />

NZM...4(-4)-AE(F)600...1250(-NA) E 1 1 1 1 1 1 1<br />

NZM...4(-4)-AE1600 E 1 1 1 1 0.87 0.85 0.82<br />

NZM...4(-4)-AE630...1250 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...4(-4)-AE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8<br />

Systems protection, cable protection, selectivity and genera<strong>to</strong>r protection<br />

NZM...2(-4)-VE(F)100...175(-NA) (-S1) E 1 1 1 1 1 1 1<br />

NZM...2(-4)-VE(F)200...250(-NA) (-S1) E 1 1 1 1 0.9 0.85 0.8<br />

NZM...2(-4)-VE100...160 + XSV E with XSV 1 1 1 1 1 1 1<br />

NZM...2(-4)-VE250 + XSV E with XSV 1 1 1 0.94 0.88 0.84 0.81<br />

NZM...3(-4)-VE(F)250...500(-NA) E 1 1 1 1 1 1 1<br />

NZM...3(-4)-VE(F)550...630(-NA) E 1 1 1 1 0.9 0.85 0.8<br />

NZM...3(-4)-VE250...400 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...3(-4)-VE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73<br />

NZM...4(-4)-VE(F)600...1250(-NA) (-S1) E 1 1 1 1 1 1 1<br />

NZM...4(-4)-VE1600 (-S1) E 1 1 1 1 0.87 0.85 0.82<br />

NZM...4(-4)-VE630...1250 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...4(-4)-VE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8<br />

Mo<strong>to</strong>r protection<br />

NZM...2-ME(SE)90...140(-CNA) E 1 1 1 1 1 1 1<br />

NZM...2-ME(SE)220(-CNA) E 1 1 1 1 0.9 0.85 0.8<br />

NZM...2-ME90...140 + XSV E with XSV 1 1 1 1 1 1 1<br />

NZM...2-ME220 + XSV E with XSV 1 1 1 0.94 0.88 0.84 0.81<br />

NZM...3-ME(SE)220...350(-CNA) (-S1) E 1 1 1 1 1 1 1<br />

NZM...3-ME(SE)450(-CNA) (-S1) E 1 1 1 1 1 1 1<br />

NZM...3-ME220...350 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...3-ME450 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73<br />

NZM...4-ME550...875 (-S1) E 1 1 1 1 1 1 1<br />

NZM...4-ME1400 (-S1) E 1 1 1 1 1 1 1<br />

NZM...4-ME550...875 + XAV E with XAV 1 1 1 1 1 1 1<br />

NZM...4-ME1400 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8<br />

Switch-disconnec<strong>to</strong>r / Molded Case Switch<br />

N1(-4) -63, PN1(-4)-63, NS1-63-NA 1 1 1 1 1 1 1<br />

N1(-4) -100...125, PN1(-4)-100...125, NS1-100...125-NA 1 1 1 1 0.86 0.83 0.8<br />

N1(-4) -160, PN1(-4)-160 1 1 1 0.95 0.9 0.85 0.8<br />

N2(-4) -160...200, PN2(-4)-160...200, NS2-160...200-NA 1 1 1 1 1 1 1<br />

N2(-4) -250, PN2(-4)-200, NS2-250-NA 1 1 1 1 0.9 0.85 0.8<br />

N2(-4) -160...200 + XSV 1 1 1 1 1 1 1<br />

N2(-4) -250, NS2-250-NA 1 0.97 0.92 0.87 0.81 - -<br />

N3(-4)-400, PN3(-4)-400, NS3-400-NA 1 1 1 1 1 1 1<br />

N3(-4)-630, PN3(-4)-630, NS3-600-NA 1 1 1 1 0.9 0.85 0.8<br />

N3(-4)-400 + XAV 1 1 1 1 1 1 1<br />

N3(-4)-630 + XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73<br />

N4(-4)-630...1250, NS4-800...1200-NA 1 1 1 1 1 1 1<br />

N4(-4)-1600 1 1 1 1 0.87 0.85 0.82<br />

N4(-4)-630...1250 + XAV 1 1 1 1 1 1 1<br />

N4(-4)-1600 + XAV 1 0.98 0.93 0.89 0.85 0.83 0.8<br />

Leistungsschalter, Lasttrennschalter<br />

Notes<br />

The derating coefficient must be considered in accordance with the following table in order <strong>to</strong> determine the maximum permissible current loading at<br />

different ambient temperatures.<br />

Example:An NZM2-A250 should be operated at an ambient temperature of 65 °C.<br />

How high is the permissible rated operational current I e ?<br />

At 65 °C the derating coefficient is 0.85, this means I e = 250 A x 0.85 = 212.5 A.<br />