Technical data<br />
Moulded Case Switch<br />
10/129<br />
http://catalog.moeller.net<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
NS1-...-NA<br />
max. 125A<br />
NS2-...-NA<br />
max. 250A<br />
NS…-…NA<br />
NS3-...-NA<br />
max. 600A<br />
Moulded Case Switch<br />
Rated peak withstand current<br />
U imp<br />
Main contacts V 6000 8000 8000 8000<br />
Auxiliary contacts V 6000 6000 6000 6000<br />
Rated operational voltage U e VAC 690 690 690 690<br />
Rated uninterr<strong>up</strong>ted current max.<br />
IEC/EN 60947-2 annex L I n A 125 250 600 1200<br />
UL489/CSA 22.2 No. 5.1 I n A 125 250 600 1200<br />
Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />
Rated insulation voltage U i V 690 1000 1000 1000<br />
NS2-...-NA<br />
max. 250A<br />
<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />
Switching capacity according <strong>to</strong> UL 489, CSA 22.2 No. 5.1<br />
240 V 60 Hz KA 85 150 150 85<br />
480 V 60 Hz KA 35 100 100 65<br />
600 V 60 Hz KA – 50 50 42<br />
Switching capacity, divergent from the products for the NA market<br />
Rated short-circuit making capacity 240 V 50/60 Hz I cm KA 187 330 330 187<br />
400/415 V 50/60 Hz I cm KA 105 330 330 154<br />
440 V 50/60 Hz I cm KA 74 286 286 143<br />
525 V 50/60 Hz I cm KA 53 105 143 84<br />
690 V 50/60 Hz I cm KA 17 53 74 74<br />
Rated short-circuit breaking capacity I cu <strong>to</strong><br />
I cc = I cu<br />
IEC/EN 60947<br />
according <strong>to</strong> IEC/EN 60947-2 Annex L test cycle<br />
O-t-CO<br />
I cs according<br />
<strong>to</strong><br />
IEC/EN 60947<br />
test cycle<br />
O-t-CO-t-CO<br />
Lifespan, mechanical<br />
(of which max. 50 % trip by shunt/undervoltage<br />
release)<br />
240 V 50/60 Hz I cu KA 85 150 150 85<br />
400/415 V 50/60 Hz I cu KA 50 150 150 70<br />
440 V 50/60 Hz I cu KA 35 130 130 65<br />
525 V 50/60 Hz I cu KA 20 50 85 40<br />
690 V 50/60 Hz I cu KA 10 20 35 35<br />
240 V 50/60 Hz I cs KA 85 150 150 43<br />
400/415 V 50/60 Hz I cs KA 50 150 150 35<br />
440 V 50/60 Hz I cs KA 35 130 130 33<br />
525 V 50/60 Hz I cs KA 10 37.5 33 20<br />
690 V 50/60 Hz I cs KA 7.5 5 9 18<br />
Operations <strong>2000</strong>0 <strong>2000</strong>0 15000 10000<br />
Maximum operating frequency ops./h 120 120 60 60<br />
Lifespan, electrical AC–-1 400/415 V 50/60 Hz Operations 10000 10000 5000 3000<br />
690 V 50/60 Hz Operations 7500 7500 3000 <strong>2000</strong><br />
AC-3 400/415 V 50/60 Hz Operations 7500 6500 <strong>2000</strong> <strong>2000</strong><br />
690V 50/60 Hz Operations 5000 5000 <strong>2000</strong> 1000<br />
Current heat loss per pole at I 1) u W 8.7 19 40 97<br />
Total downtime in a short-circuit ms < 10 < 10 < 10 < 25 F 415 V<br />
< 35 > 415 V<br />
Notes<br />
1) Details refer <strong>to</strong> the maximum nominal current of the frame size<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616