10/128<br />

Technical data<br />

Switch-disconnec<strong>to</strong>rs<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

PN…, N…<br />

PN1/N1<br />

max. 160 A<br />

PN2/N2<br />

max. 250 A<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

PN3/N3<br />

max. 630 A<br />

Switch-disconnec<strong>to</strong>rs<br />

Rated impulse withstand voltage U imp<br />

Main contacts V 6000 8000 8000 8000<br />

Auxiliary contacts V 6000 6000 6000 6000<br />

Rated operational voltage U e V AC 690 690 690 690<br />

Rated uninterr<strong>up</strong>ted current max.<br />

IEC/EN 60947-2 annex L I u A 160 250 630 1600<br />

Technical data, divergent from the<br />

products for the IEC market UL489,<br />

CSA 22.2 No. 5.1<br />

I u A 125 160 550 1200<br />

http://catalog.moeller.net<br />

N4<br />

max. 1600 A<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />

Rated insulation voltage U i V AC 690 690 1000 1000<br />

For use in IT electrical power networks V 690 690 690 525<br />

Switching capacity<br />

Rated short-circuit making capacity I cm kA 2.8 5.5 25 53<br />

Rated short-time withstand current<br />

t = 0.3 s I cw kA 2 3.5 1) 12 25<br />

t = 1 s I cw kA 2 3.5 1) 12 25<br />

Rated conditional short-circuit current<br />

With back-<strong>up</strong> fuse A gG/gL PN1(N1)-63…125: 125<br />

PN1(N1)-160: 160<br />

PN2(N2)-160…250: 250<br />

PN3(N3)-400…630:<br />

630<br />

400 … 415 V kA 100 100 100 100<br />

690 V kA 80 80 80 80<br />

With downstream fuse A gG/gL PN1(N1)-63…125: 125<br />

PN1(N1)-160: 160<br />

PN2(N2)-160…250: 250<br />

PN3(N3)-400…630:<br />

630<br />

400 … 415 V kA 100 100 100 100<br />

690 V kA 10 80 80 80<br />

Rated making and breaking capacity<br />

Rated operational current, AC-22/23A<br />

415 V I e A 160 250 630 1600<br />

690 V I e A 160 250 630 1600<br />

Lifespan, mechanical<br />

Opera<br />

<strong>2000</strong>0 <strong>2000</strong>0 15000 10000<br />

tions<br />

Maximum operating frequency Ops./h 120 120 60 60<br />

Lifespan, electrical <strong>to</strong> IEC/EN 60947-4-1<br />

section B<br />

AC-1<br />

400/415 V Opera<br />

10000 10000 4) 5000 3000<br />

tions<br />

690 V Opera<br />

tions<br />

7500 7500 4) 3000 <strong>2000</strong><br />

N4-630…1600: 2 x 800<br />

N4-630…1600: 2 x 800<br />

AC–-3<br />

400/415 V Opera<br />

tions<br />

690 V Opera<br />

tions<br />

7500 7500 5) 3000 <strong>2000</strong><br />

5000 5000 3)5) <strong>2000</strong> 1000<br />

Current heat loss per pole at I u<br />

2) W 12.7 16 40 97<br />

Notes<br />

1) The rated short time withstand current for PN2/N2 in conjunction with residual-current release NZM2-4-XFI... I cw = 1.5 kA<br />

2) The current heat loss per pole ratings refer <strong>to</strong> the maximum current rating of the frame size.<br />

3) For the electrical life at AC-3 for PN2/N2 the following applies: 690 V: max. 160 kW<br />

4) For 3-pole switch-disconnec<strong>to</strong>rs the following applies: 400/415 V 7500 switching operations; 690 V 5000 switching<br />

operations<br />

5) For 3-pole switch-disconnec<strong>to</strong>rs the following applies: 400/415 V 6000 switching operations; 690 V 4000 switching operations<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616