Technical data<br />

<strong>Circuit</strong>-breaker, switch-disconnec<strong>to</strong>r for 1000 V AC, 3 pole<br />

10/127<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

NZMH2, N2<br />

max. 250 A<br />

NZM…2, NZM…3, NZM…4, N…<br />

NZMN3<br />

max. 630 A<br />

NZMH4, N4<br />

max. 1600 A<br />

General<br />

Utilization category A A A/B<br />

Maximum operating frequency Ops/h 120 60 60<br />

Lifespan<br />

mechanical (of which max. 50 % trip by shunt/<br />

<strong>2000</strong>0 15000 10000<br />

undervoltage release)<br />

electrical, AC-1 1000 V<br />

Switching 3000 1000 500<br />

operations<br />

Rated operational voltage U e V AC 1000 1000 1000<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

<strong>Circuit</strong>-<strong>breakers</strong><br />

Rated uninterr<strong>up</strong>ted current I u A 250 630 1600<br />

Rated short-circuit making capacity<br />

<strong>up</strong> <strong>to</strong> 1000 V 50/60 Hz I cm kA 17 17 40<br />

Rated short-circuit breaking capacity I cn<br />

I cu <strong>to</strong> IEC/EN 60947 operating sequence O-t-CO I cu kA 3 10 20<br />

I es <strong>to</strong> IEC/EN 60947 operating sequence O-t-CO-t-CO I cs kA 3 10 15<br />

Rated making and breaking capacity<br />

Rated operational current<br />

AC-1 250 630 1600<br />

Rated insulation voltage U i V 1000 1000 1000<br />

Use in IT power networks – – –<br />

Switch-disconnec<strong>to</strong>rs<br />

Rated uninterr<strong>up</strong>ted current I u A 250 1600<br />

Rated short-time withstand current I cw kA 3.5 – 25<br />

Rated making and breaking capacity<br />

Rated operational current<br />

AC-22/23A I e 250 1600<br />

Rated insulation voltage U i V 1000 – 1000<br />

Use in IT power networks – – –<br />

Rated conditional short-circuit current<br />

With back-<strong>up</strong> fuse A gG/gL N2-160…250-S1: 250 – –<br />

1000 V kA 10 – –<br />

With downstream fuse A gG/gL N2-160…250-S1: 250 – –<br />

1000 V kA 10 – –<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616