For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616<br />

10/124<br />

Technical data<br />

<strong>Circuit</strong>-<strong>breakers</strong><br />

Technical data<br />

<strong>Circuit</strong>-<strong>breakers</strong><br />

10/125<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

NZM…1, NZM…2, NZM…3, NZM…4<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Rated uninterr<strong>up</strong>ted current max. 160 A Rated uninterr<strong>up</strong>ted current max. 250 A Rated uninterr<strong>up</strong>ted current max. 630 A Rated uninterr<strong>up</strong>ted current max. <strong>2000</strong> A<br />

NZMB1 NZMC1 NZMN1 NZMH1 NZMB2 NZMC2 NZMN2 NZMH2 NZMN3 NZMH3 NZMN4 NZMH4<br />

Switching capacity<br />

Rated short-circuit making capacity<br />

240 V I cm kA 63 121 187 220 63 121 187 330 187 330 105 275<br />

400/415 V I cm kA 53 76 105 220 53 76 105 330 105 330 105 187<br />

440 V I cm kA 53 63 74 74 53 63 74 286 74 286 74 187<br />

525 V I cm kA – 24 40 40 – 24 53 105 53 143 53 143<br />

690 V I cm kA – 14 17 17 – 9 40 40 40 74 40 105<br />

Rated short-circuit breaking capacity I cn<br />

I cu <strong>to</strong> IEC/EN 60947 operating sequence O-t- 240 V 50/60 Hz I cu kA 30 55 85 100 30 55 85 150 85 150 50 125<br />

CO<br />

400/415 V 50/60 Hz I cu kA 25 36 50 100 25 36 50 150 50 150 50 85<br />

440 V 50/60 Hz I cu kA 25 30 35 35 25 30 35 130 35 130 35 85 10)<br />

525 V 50/60 Hz I cu kA – 12 20 20 – 112 25 50 25 65 25 65<br />

690 V 50/60 Hz I cu kA – 8 10 10 – 8 20 20 20 35 20 50<br />

500 V DC I cu kA – – 15 30 – – 30 60 – – – –<br />

750 V DC I cu kA – – – – – – 30 60 – – – –<br />

I cu <strong>to</strong> IEC/EN 60947 operating sequence O-t-<br />

CO-t-CO<br />

240 V 50/60 Hz I cs kA 30 55 85 100 30 55 85 150 85 150 37 63<br />

400/415 V 50/60 Hz I cs kA 25 36 50 50 25 36 50 150 50 150 37 43<br />

440 V 50/60 Hz I cs kA 18.5 22.5 35 35 18.5 22.5 35 130 35 130 26 43<br />

525 V 50/60 Hz I cs kA – 6 10 10 – 9 25 37.5 13 33 19 49<br />

690 V 50/60 Hz I cs kA – 4 7.5 7.5 – 4 5 5 5 9 15 37<br />

Maximum low-voltage h.b.c. fuse 9) A gG/gL NZM.1-…20…100: 200<br />

NZM.1-…125, 160: 315<br />

355 355 355 355 NZMN3-…250, 400: 400<br />

NZMN3-…630: 630<br />

NZM…1, NZM…2, NZM…3, NZM…4<br />

NZMN4-…630…1250: 2 x 630<br />

NZMN4-…1600: 2 x 800<br />

NZMN4-<strong>2000</strong>: 2 x 1000<br />

Utilization category <strong>to</strong> IEC/EN 60947-2 A A A A A A A A A A B (<strong>2000</strong>A: A) B (<strong>2000</strong>A: A)<br />

Rated short-time withstand current<br />

t = 0.3 s I cw kA – – – – – – 1.9 1.9 3.3 3.3 19.2 19.2<br />

t = 1 s I cw kA – – – – – – 1.9 1.9 3.3 3.3 19.2 19.2<br />

Rated making and breaking capacity<br />

Rated operational current AC-1 400/415 V 50/60 Hz I e A 160 160 160 160 250 250 250 250 630 630 <strong>2000</strong> <strong>2000</strong><br />

690 V 50/60 Hz I e A 160 160 160 160 250 250 250 250 630 630 <strong>2000</strong> <strong>2000</strong><br />

AC–-3 400/415 V 50/60 Hz I e A 160 160 160 160 250 250 250 250 630 630 1600 2) 1600 2)<br />

690 V 50/60 Hz I e A 160 160 160 160 250 250 250 250 630 630 1600 2) 1600 2)<br />

DC – -1 500 V DC I e A – – 125 125 – – 250 250 – – – –<br />

750 V DC I e A – – – – – – 250 250 – – – –<br />

DC – 3 500 V DC I e A – – 125 125 – – 250 250 – – – –<br />

750 V DC I e A – – – – – – 250 250 – – – –<br />

Lifespan, mechanical Operations <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 <strong>2000</strong>0 15000 15000 10000 10000<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

Maximum operating frequency<br />

Max. operating frequency Ops/h 120 120 120 120 120 120 120 120 60 60 60 60<br />

Lifespan, electrical<br />

AC-1 400/415 V 50/60 Hz Operations 10000 8) 7500 10000 10000 10000 8) 7500 10000 10000 5000 5000 3000 10) 3000 10)<br />

690 V 50/60 Hz Operations – 5000 7500 7500 – 5000 7500 7500 3000 3000 <strong>2000</strong> 10) <strong>2000</strong> 10)<br />

AC–-3 400/415 V 50/60 Hz Operations 7500 4) – 7500 7500 6500 4) – 6500 6500 <strong>2000</strong> <strong>2000</strong> <strong>2000</strong> 10) <strong>2000</strong> 10)<br />

690 V 50/60 Hz Operations – – 5000 5000 – 5000 5000 5000 <strong>2000</strong> <strong>2000</strong> 1000 10) 1000 10)<br />

DC – -1 500 V DC Operations 10000 10000 7500 7500<br />

750 V DC Operations 7500 7500<br />

DC – 3 500 V DC Operations 5000 5000 3000 3000<br />

750 V DC Operations – – – – – – 3000 3000 – – – –<br />

Current heat loss per pole at I 6) u W 16.7 16.7 16.7 16.7 19 19 19 19 40 40 97 (<strong>2000</strong> A) 97 (<strong>2000</strong> A)<br />

Total opening delay at short-circuit ms < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 25 F 415 V; < 35 > 415 V < 25 F 415 V; < 35 > 415 V<br />

Technical data, divergent from the products for the IEC market<br />

Switching capacity NA switches (UL489, CSA 22.2 No. 5.1)<br />

240 V 60 Hz kA 35 – 85 – 35 – 85 150 3) 85 150 3) 85 125<br />

480V 60Hz kA 25 1) – 35 1) – 25 – 35 100 3) 42 100 3) 42 85<br />

600 V 60 Hz kA – – – – 18 – 25 50 3) 35 50 3) 35 50<br />

Notes<br />

1) For NA switch switching capacity with NZM…1-…(C)NA the following applies: 480 Y/277 V from 60 A<br />

2) For AC-3 rated operational current with NZM4 the following applies: 400 V: max. 650 kW; 690 V: max. 600 kW<br />

3) For NA switch switching capacity with NZML2 and NZML3 the following applies: Current Limiting switch <strong>to</strong> UL489<br />

4) For 3-pole system protection circuit-breaker the AC-3 specification is not applicable<br />

5) For NA switch switching capacity with NZML4 at 240 V 60 Hz the following applies: on request<br />

6) For current heat loss per pole the specification refers <strong>to</strong> the maximum nominal current of the frame size.<br />

7) For 3-pole system protection circuit-breaker the following applies: 400/415 V 7500 switching operations<br />

8) Maximum back-<strong>up</strong> fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.<br />

9) F 1600 A<br />

10) Higher switching capacity on request