19.11.2014 Views

Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts

Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts

Circuit-breakers NZM1, 2, 3, 4 up to 2000 A - Moeller Electric Parts

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Engineering<br />

Direction of blow-out, minimum clearances, tube cable lugs<br />

f<br />

i<br />

10/109<br />

http://catalog.moeller.net<br />

Direction of blow-out<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Top, front Bot<strong>to</strong>m,<br />

rear<br />

<strong>NZM1</strong> X –<br />

NZM2 1) X X<br />

NZM3 X X<br />

NZM4 X –<br />

1) NZM B (C) – A … as <strong>NZM1</strong><br />

<strong>NZM1</strong>, NZM2, NZM3, NZM4<br />

<strong>Circuit</strong>-<strong>breakers</strong>, switch-disconnec<strong>to</strong>rs<br />

Minimum clearances<br />

between two adjacently mounted switches<br />

Minimum clearance a in mm<br />

b<br />

a<br />

b<br />

c<br />

d<br />

<strong>NZM1</strong> NZM2 NZM3 NZM4<br />

<strong>NZM1</strong> 0 5 5 15<br />

NZM2 5 5 5 15<br />

NZM3 5 5 5 15<br />

NZM4 15 15 15 15<br />

between switch and other parts<br />

Minimum clearances in mm<br />

b c d<br />

F 690 V 1000 V F 690 V 1000 V F 690 V 1000 V<br />

<strong>NZM1</strong> 0 – 60 – 0 –<br />

NZM2 1) 5 5 35 35 35 35<br />

NZM3 5 5 60 60 60 60<br />

NZM4 15 15 100 200 0 0<br />

1) NZM B (C) – A … C= 60 mm, d = 0 mm<br />

Dimensions<br />

g<br />

For pressing the cable lugs a press <strong>to</strong>ol K22, HK60/22 or EK22<br />

from the company Klauke is necessary with the following press inserts:<br />

R22/95 for 95 mm 2<br />

R22/120 for 120 mm 2<br />

R22/150 for 150 mm 2<br />

R22/185 for 185 mm 2<br />

R22/240 for 240 mm 2<br />

d<br />

e<br />

b<br />

c<br />

h<br />

a<br />

Cable lug For use with Rated cross Terminal bolt Dimensions in mm<br />

section<br />

mm 2 o a b c d e f g h i<br />

KS95-NZM7 NZM2 95 M8 53+2 23g0.5 18g0.2 10g1 19 8,5 25 13,5 4,4<br />

KS120-NZM7 NZM2 120 M8 56+2 23g0.5 19.5g0.2 10g1 19 8,5 26 15 4,4<br />

KS150-NZM7 NZM2 150 M8 61+2 23g0.5 21g0.2 10g1 19 8,5 30 16,5 4,4<br />

NZM2-XKS185 NZM2 185 M8 65g1.5 22g1 24g0.3 9 +1<br />

–0,5 19 +2,5<br />

–0,5 8,5 +0,05<br />

–0,1 30g2 19g0.4 7<br />

NZM3-XKS185 NZM3, NZM4 185 M10 65 24,5 24 11,5 18 10,5 30 19 7.0g0.8<br />

NZM3-XKS240 NZM3, NZM4 240 M10 72 31 26 11,5 19 10,5 35 21 5.0g0.8<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and S<strong>up</strong>port call KMparts.com (866) 595-9616